TYPICAL
<br />(e) PANEL
<br />"L130"
<br />(e) PANEL
<br />"H130"
<br />SCALE: 1/4"=1'-0"
<br />NORTH
<br /> POWER FLOOR PLAN
<br />.\Arch\2020-09-10\OrlandosPatio_v20_wmitchellLHLVL-LDA._ASI_CMYK.Logo-2754932.jpg
<br />HCSEngineering
<br />50 years HTI
<br />M
<br />SC.DRAHCIR
<br />No. E14303
<br />Exp. 6-30-21
<br />E
<br />LECTR I C A LREGISTERED P R O F ESSION
<br />A
<br />L
<br />ENGI
<br />NEERE
<br />OF CAL I F O R NIASTA
<br />T
<br />4512 Feather River Dr #F, Stockton, CA 95219
<br />209-478-8270 | www.hcs-eng.com
<br />Richard C. Smith, PE richard@hcs-eng.com
<br />Bhupendra Patel, PE bhupendra@hcs-eng.com
<br />Elizabeth Aguilar elizabeth@hcs-eng.com
<br />PROJECT # 2020.383
<br />October 2019
<br />C32705PETERNICHOLAS
<br />R
<br />OSADOLICEN S E D A RC
<br />HI
<br />T
<br />ECTSTAT
<br />E
<br />OF C A L IF O RNIAChecked By:
<br />Drawn By:
<br />Project No.:
<br />LDA Partners, LLP
<br />Designers & Architects
<br />222 Central Court
<br />Stockton, CA 95204
<br />209.943.0405
<br />www.ldapartners.com
<br />Client:
<br />Architect:
<br />Project:
<br />MMS/GJT
<br />RCS
<br />2018.383
<br />12/21/2020
<br />NITRO BOBA TI-SUITE A130 AT
<br />STONE CREEK VILLAGE,
<br />STOCKTON, CA
<br />ADRESS LINE 1
<br />Mr. Vy H Vy & Mrs. Jenny
<br />Pham
<br />xxx.xxx.xxxx
<br />ADRESS LINE 2
<br />ADDRESS LINE 1
<br />ADDRESS LINE 2
<br />No.Description Date By
<br />LEGEND
<br />E1.0
<br />GENERAL NOTES:
<br />1. ELECTRICAL INSTALLATION SHALL COMPLY WITH TITLE 24, CALIFORNIA
<br />CODE OF REGULATIONS, INCLUDING THE FOLLOWING:
<br />TITLE 24, CCR, PART 2, 2016 CBC
<br />TITLE 24, CCR, PART 3, 2016 CEC
<br />TITLE 24, CCR, PART 4, 2016 CMC
<br />TITLE 24, CCR, PART 9, 2016 CFC
<br />ALL APPLICABLE LOCAL CODES.
<br />2. ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL LICENSES, ETC.
<br />REQUIRED TO CARRY ON AND COMPLETE THE WORK. PERMIT BY OWNER.
<br />3. PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT, TRANSPORTATION AND
<br />PERFORM ALL OPERATIONS NECESSARY FOR ANY REASONABLE INCIDENTAL TO PROPER
<br />EXECUTION AND COMPLETION OF ALL "ELECTRICAL WORK" WHETHER SPECIFICALLY
<br />MENTIONED OR NOT; ALL AS INDICATED, SPECIFIED HEREIN, AND/OR IMPLIED THEREBY TO
<br />CARRY OUT THE APPARENT INTENT THEREOF.
<br />4. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERS'
<br />LABORATORIES, INC., SHALL MEET THEIR REQUIREMENTS AND SHALL BEAR THEIR LABEL
<br />WHEREVER STANDARDS HAVE BEEN ESTABLISHED AND LABEL SERVICE IS REGULARLY
<br />FURNISHED BY THAT AGENCY.
<br />5. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SIZE
<br />AND LOCATIONS OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE,
<br />CONTRACTOR SHALL MAKE USE OF ALL DATA IN ALL CONTRACT DOCUMENTS AND VERIFY
<br />THIS INFORMATION AT THE SITE. CONTRACTOR SHALL BE RESPONSIBLE FOR LAYING OUT
<br />AND INSTALLING HIS WORK TO AVOID INTERFERENCE WITH OTHER TRADES.
<br />6. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THWN UNLESS OTHERWISE
<br />NOTED OR REQUIRED BY CODE.
<br />NAMEPLATES & IDENTIFICATION:
<br />INSTALL ENGRAVED NAMEPLATES FOR EACH PANELBOARD, CABINET, DISCONNECT, ETC.
<br />NAMEPLATES SHALL BE SECURELY FASTENED TO THE EQUIPMENT WITH #4 PHILLIPS
<br />ROUND HEAD CADMIUM PLATED SELF-TAPPING SCREWS, BRASS BOLT, OR WITH A PLASTIC
<br />RESIN ADHESIVE GLUE, GOODYEAR "PLIEBOND" OR EQUAL.
<br />WIRING METHODS:
<br />1. ALL WIRING SHALL BE INSTALLED IN STEEL CONDUITS, CONCEALED IN WALL AND
<br />CEILING U.O.N.
<br />2. MINIMUM CONDUIT SIZE SHALL BE 1/2". MINIMUM ACCEPTABLE CONDUITS ARE
<br /> A. GALVANIZED RIGID STEEL.
<br /> B. GALVANIZED STEEL EMT.
<br /> C. LIQUID TIGHT STEEL FLEX - FOR FINAL CONNECTION TO OUTDOOR EQUIPMENT.
<br /> D. FLEXIBLE STEEL CONDUIT - FOR INDOOR FINAL CONNECTIONS TO
<br /> MECHANICAL EQUIPMENT (NOT TO EXCEED 36").
<br /> E. PVC CONDUIT SCHEDULE 40, UNDERGROUND.
<br />3. NMC CABLING SYSTEMS ARE NOT ALLOWED IN THIS BUILDING.
<br />4. MC CABLING SYSTEMS ARE NOT ALLOWED IN THIS BUILDING.
<br />WIRING DEVICES:
<br />UNITS SHALL BE EQUAL TO THE DEVICES SET FORTH HEREIN, IN STANDARD COLORS
<br />(BROWN, WHITE, GREY, BEIGE OR IVORY) AS SELECTED BY THE ARCHITECT:
<br /> A. WIRING DEVICES LEVITON # HUBBELL # P & S #
<br /> DUPLEX CONV. OUT. 15A 5262 5262 5262
<br /> DUPLEX GFI CONV. OUT. GF5262
<br />DEVICE PLATES:
<br />1. ALL DEVICE PLATES FOR INDOOR USE SHALL BE SMOOTH NYLON OR APPROVED EQUAL
<br />UNLESS OTHERWISE NOTED. ALL DEVICE PLATES FOR OUTDOOR USE SHALL BE RAISED
<br />METAL.
<br />2. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 1/2" RAISED STEEL PLATES.
<br />WEATHERPROOF COVERS TO BE SNAP TYPE COVERS.
<br />SUPPORTS:
<br />1. FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FOR ALL
<br />ELECTRICAL ENCLOSURES, CONDUITS AND EQUIPMENT.
<br />2. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS, TO
<br />METAL WITH MACHINE SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION ANCHORS
<br />AND MACHINE SCREWS OR BOLTS.
<br />GROUNDING:
<br />1. GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND
<br />SPECIFICALLY INCLUDING SWITCHBOARD, PANELBOARDS, MOTOR CASES, ETC.
<br />PANELBOARDS:
<br />UNITS SHALL BE FLUSH OR SURFACE MOUNTED AS INDICATED ON THE PANEL SCHEDULE,
<br />WITH THE NUMBER AND SIZE OF BREAKERS INDICATED ON THE PANEL SCHEDULE. SINGLE
<br />POLE, TWO POLE AND THREE POLE BREAKERS SHALL BE BOLT-ON TYPE. THE PANEL
<br />DOORS SHALL HAVE FLUSH TYPE LOCKS, ALL LOCKS SHALL BE KEYED ALIKE AND HAVE
<br />TYPEWRITTEN DIRECTORIES INDICATING FIXTURES, EQUIPMENT, OR OUTLETS SERVICED BY
<br />EACH BREAKER. ALL BUSSING SHALL BE COPPER.
<br />WORKING CLEARANCES FOR PANELS & SWITCHBOARDS
<br />1. COORDINATE WITH OTHER TRADES TO ENSURE CODE REQUIRED WORKING
<br />CLEARANCES, ACCESS, ETC. FOR PANELS AND SWITCHBOARDS PER C.E.C. SECTIONS
<br />110-16 AND 384-4.
<br />TESTING:
<br />1. THE ENTIRE ELECTRICAL INSTALLATION SHALL BE FREE FROM SHORT CIRCUITS AND
<br />IMPROPER GROUNDS. TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY AND
<br />GROUNDS BEFORE ANY FIXTURES OR EQUIPMENT ARE CONNECTED AND WHETHER SUCH
<br />TESTS INDICATE FAULTY INSULATION OR OTHER DEFECTS, THEY SHALL BE LOCATED,
<br />REPAIRED AND RETESTED AT THE CONTRACTOR'S EXPENSE.
<br />ELECTRICAL SPECIFICATIONS
|