GREEN BUILDING NOTES
<br />1. CONSTRUCTION TO CONFORM TO CALIFORNIA ENERGY COMMISSION
<br />MANDATORY BUILDING STANDARDS.
<br />2. PROVIDE TEMPORARY VENTILATION DURING CONSTRUCTION IN
<br />ACCORDANCE WITH SECTION 5.504.1.3 OF CALIFORNIA GREEN
<br />BUILDING STANDARDS CODE.
<br />3. IF THE HVAC SYSTEM IS USED DURING CONSTRUCTION, USE RETURN
<br />AIR FILTERS WITH A MERV OF 8, BASED ON ASHRAE 52.2-1999, OR
<br />AN AVERAGE EFFICIENCY OF 30% BASED ON ASHRAE 52.1-1999.
<br />REPLACE ALL FILTERS IMMEDIATELY PRIOR TO OCCUPANCY.
<br />4. AT THE TIME OF ROUGH INSTALLATION OR DURING STORAGE ON THE
<br />CONSTRUCTION SITE AND UNTIL START-UP OF THE HEATING AND
<br />COOLING EQUIPMENT, ALL DUCTS AND OTHER RELATED AIR
<br />DISTRIBUTION COMPONENT EQUIPMENT SHALL BE COVERED WITH
<br />TAPE, PLASTIC, SHEETMETAL OR OTHER METHODS ACCEPTABLE TO THE
<br />ENFORCING AGENCY TO REDUCE THE AMOUNT OF DUST OR DEBRIS
<br />WHICH MAY COLLECT IN THE SYSTEM. CGBC 5.504.3.
<br />5. ADHESIVES, ADHESIVE BONDING PRIMERS, ADHESIVE PRIMERS,
<br />SEALANTS, SEALANT PRIMERS AND CAULKS SHALL COMPLY WITH
<br />LOCAL OR REGIONAL AIR POLLUTION CONTROL OR AIR QUALITY
<br />MANAGEMENT DISTRICT RULES WHERE APPLICABLE OR SCAQMD RULE
<br />1168 VOC LIMITS, AS SHOWN IN TABLES 5.504.4.1 AND 5.504.4.2
<br />AEROSOL ADHESIVES AND SMALLER UNIT SIZED OF ADHESIVES AND
<br />SEALANT OR CAULKING COMPOUNDS (IN UNITS OF PRODUCT, LESS
<br />PACKAGING WHICH DO NOT WEIGHT MORE THAN ONE POUND AND DO
<br />NOT CONSIST OF MORE THAN 16 FLUID OUNCES) SHALL COMPLY
<br />WITH STATEWIDE VOC STANDARDS AND OTHER REQUIREMENTS,
<br />INCLUDING PROHIBITIONS ON USE OF CERTAIN TOXIN COMPOUNDS, OF
<br />CALIFORNIA CODE OF REGULATIONS, TITLE 17, COMMENCING WITH
<br />SECTION 94507.0
<br />6. IN MECHANICAL VENTILATION BUILDING, PROVIDE REGULARLY OCCUPIED
<br />AREAS OF THE BUILDING WITH AIR FILTRATION MEDIA FOR OUTSIDE
<br />AND RETURN AIR PRIOR OCCUPANCY THAT PROVIDES AT LEAST A
<br />MERV 8. MERV 8 FILTERS SHALL BE INSTALLED PRIOR TO
<br />OCCUPANCY, AND RECOMMENDATIONS FOR MAINTENANCE WITH FILTERS
<br />OF THE SAME VALUE SHALL BE INCLUDED IN THE OPERATION AND
<br />MAINTENANCE MANUAL.
<br />7. MECHANICAL VENTILATION CALCULATED PER SECTION 120.1 OF THE
<br />CALIFORNIA ENERGY CODE, TITLE 24, SECTION 6.
<br />8. INSTALL HVAC, REFRIGERATION EQUIPMENT THAT DOES NOT CONTAIN
<br />CFCs OR HALONS.
<br />9. BUILDINGS SHALL MEET OR EXCEED THE PROVISIONS OF THE 2016
<br />CALIFORNIA BUILDING CODE, CHAPTER 12 (VENTILATION) AND CHAPTER
<br />14 (EXTERIOR WALL) FOR INDOOR MOISTURE CONTROL. 2016 CGC
<br />5.505.
<br />10. BUILDINGS MUST MEET THE MINIMUM REQUIREMENTS OF THE 2016
<br />CALIFORNIA BUILDING CODE, CHAPTER 12 (VENTILATION) FOR
<br />MECHANICALLY OR NATURALLY VENTILATED SPACES. 2016 CGC
<br />5.506.1.
<br />Habit HVAC system T & B Scope of Work 2015
<br />All third party air balance companies used on Habit projects to be either NEBB or AABC certified and have current certification and
<br />applicable licensing. Note that complete and full air balance applies to ALL equipment servicing Habits TI space including HVAC,
<br />MAU, exhaust hood & fans restroom exhaust fans and PCU units (where occurs), regardless of who supplies equipment.
<br />1. Inspection
<br />• Inspect general condition of HVAC systems and installation. Record equipment data and compare with design
<br />requirements
<br />2. Testing: Test HVAC systems for proper operation
<br />• Inspect Rooftop units for proper operation:
<br />• Verify fan rotation
<br />• Measure/record motor amperage
<br />• Measure/record voltage
<br />• Verify sequence of operation (test heating/cooling modes)
<br />• Set T -Stats to Habit standards:
<br />o Occupied -7:30 a.m. to 11: 30 p.m. - 74 degrees cool 68 degrees heat - Fan setting - ON
<br />o Unoccupied -11:30 p.m. to 7:30 a.m.- 80 degrees cool 60 degrees heat - Fan setting - AUTO
<br />• Verify that all units have spare fan belt located inside unit
<br />• Verify duct smoke detectors are installed and connected (resets to be located in office)
<br />• Verify and set economizer's to engineered drawing specifications. See Mechanical sheets for data
<br />2.1. Make Up Air Unit (MAU)
<br />• Inspect MUA unit for proper operation:
<br />• Verify fan rotation
<br />• Measure/record motor amperage
<br />• Measure/record voltage
<br />• Verify sequence of operation (test heating/cooling modes)
<br />• Set evaporator thermostat adjustment per CaptiveAire specifications
<br />3. Balance and Verify:
<br />• Balance the kitchen exhaust system for proper heat and smoke capture removal. Verify proper performance with
<br />smoke emitter tests.
<br />• Balance the air conditioning & heating units for optimal air distribution and comfort
<br />• Correct fan rotation, belt tension, sheave alignment, damper position on all units. Check for clean filters and coils
<br />• Balance the building for proper fresh air quantities and pressurization in all areas of the store.
<br />4. Measurements:
<br />• Measure and record airflow, motor speed, motor amp draw, and compare to nameplate data and specifications.
<br />5. Adjustments:
<br />• Reduce fan speeds when possible to save fan energy and conditioned air, and reduce noise levels, while maintaining
<br />comfort.
<br />• Balanced system needs to maintain positive building pressure once complete
<br />6. Tolerance:
<br />• HVAC system airflows to be balanced within +/- S% of design.
<br />7. Performance Verification:
<br />• Upon completion of the balance, verify HVAC performance via slight positive building pressure, occupant comfort, and
<br />capture and containment of kitchen hoods
<br />S. Documentation & clarifications:
<br />• Submit a NEBB or AABC Certified test and balance report with findings including the equipment data, measurements,
<br />list of deficiencies, and recommendations. This information to be submitted directly to the architect of record for
<br />review, comment and approval by their respective mechanical engineer. Habit to be copied on these
<br />correspondences.
<br />• Provide equipment commissioning reports to architect of record. Habit to be copied on these correspondences.
<br />• Installing HVAC contractor cannot self -certify or be the preforming agent of T & B
<br />• If T & B report is incomplete of fails review, Habit at its own discretion may choose to have the entire system
<br />retested by an accredited air balance company of our choosing. The cost of said re -test will come at the direct
<br />expense of the contracted GC of the project.
<br />LOAD COMPONENT SUMMARY
<br />COOLING COIL PEAK
<br />San Jose, California
<br />Latitude
<br />AIR DEVICE SCHEDULE e
<br />deg
<br />HEATING COIL PEAK
<br />122.0
<br />PLAN
<br />at Time:
<br />Mini
<br />FACE
<br />NECK
<br />FLEX
<br />Sum of
<br />Barometric pressure
<br />Mo/Hr
<br />Healing Design
<br />MARK
<br />QTY.
<br />MODEL NO.
<br />SIZE
<br />SIZE
<br />SIZE
<br />TYPE
<br />OADB:
<br />36
<br />NOTES
<br />4,896.9
<br />A
<br />Plenum
<br />5
<br />*TITUS 30ORL
<br />16"x10"
<br />14"x8"
<br />NA
<br />DOUBLE DEFLECTION
<br />BAR SUPPLY
<br />2,3,5
<br />Winter design dry bulb
<br />B
<br />Sens. +Lat
<br />18
<br />*TITUS PAS
<br />16"06"
<br />8" RD.
<br />8" RD.
<br />PERFORATED
<br />SUPPLY
<br />DIFFUSER
<br />2,3,5
<br />Btu/h
<br />C
<br />Btu/h
<br />5
<br />*TITUS PAS
<br />12"02"
<br />6" RD.
<br />6" RD.
<br />PERFORATED
<br />SUPPLY
<br />DIFFUSER
<br />2,3,5
<br />UATD
<br />D
<br />-2000
<br />0
<br />*TITUS PAS
<br />16"x16"
<br />12" RD.
<br />12" RD.
<br />PERFORATED
<br />SUPPLY
<br />DIFFUSER
<br />1,3,5
<br />0
<br />E
<br />0
<br />4
<br />*TITUS PAR
<br />24"x24"
<br />14" RD.
<br />14" RD.
<br />PERFORATED
<br />SUPPLY
<br />DIFFUSER
<br />2,3,4,7
<br />0
<br />F
<br />0
<br />1
<br />*TITUS PAS
<br />24"x24"
<br />12" RD.
<br />12" RD.
<br />PERFORATED
<br />SUPPLY
<br />DIFFUSER
<br />2,3,4
<br />7,893
<br />G
<br />Roar Cond
<br />1
<br />*TITUS PAS
<br />24"x24"
<br />6" RD.
<br />6" RD.
<br />PERFORATED
<br />SUPPLY
<br />DIFFUSER
<br />2,3,4
<br />41
<br />H
<br />0
<br />1
<br />*TITUS PAR
<br />12"x24"
<br />6" RD.
<br />6" RD.
<br />PERFORATED
<br />TRANSFER GRILLE
<br />3,4,6
<br />2
<br />Glass/Door Cond
<br />-10,656
<br />3
<br />*TITUS PAR
<br />24"x24"
<br />16" RD.
<br />16" RD.
<br />PERFORATED
<br />RETURN
<br />GRILLE
<br />3,4
<br />Wall Cond
<br />-7,281
<br />-7,281
<br />2
<br />*TITUS PAR
<br />24"x24"
<br />20" RD.
<br />20" RD.
<br />PERFORATED
<br />RETURN
<br />GRILLE
<br />3,4,8
<br />0
<br />K
<br />0.00
<br />0
<br />*TITUS PDR
<br />48"x24"
<br />16" RD.
<br />16" RD.
<br />PERFORATED
<br />RETURN
<br />GRILLE
<br />3,4,8,9
<br />4,378
<br />L
<br />Adjacent Floor
<br />0
<br />*TITUS PDR
<br />24"x24"
<br />16" RD.
<br />16" RD.
<br />PERFORATED
<br />RETURN
<br />GRILLE
<br />3,4,8
<br />NOTES:
<br />Infiltration
<br />3,197
<br />3,197
<br />2
<br />1,305
<br />1
<br />Infiltration
<br />1.
<br />-7,710
<br />PROVIDE VERTICAL PATTERN
<br />CONTROLLER
<br />79,635
<br />0
<br />79,635
<br />38
<br />84,223
<br />56
<br />2.
<br />-34,125
<br />REFER TO
<br />PLAN FOR THROW PATTERN ORIENTATION
<br />Internal Loads
<br />3.
<br />PROVIDE MANUAL VOLUME DAMPER
<br />Lights
<br />11,132
<br />2,783
<br />4.
<br />7
<br />FRAME SHALL FIT LAY -IN CEILING MODULE
<br />7
<br />Lights
<br />0
<br />0
<br />0.00
<br />People
<br />5.
<br />0
<br />FRAME SHALL FIT GYPSUM BOARD CEILING/SURFACE
<br />17
<br />18,150
<br />12
<br />People
<br />0
<br />6.
<br />0.00
<br />TRANSFER
<br />GRILLE
<br />0
<br />36,191
<br />17
<br />36,191
<br />24
<br />Misc
<br />0
<br />7.
<br />0.00
<br />DOWN DISCHARGE TYPE SUPPLY
<br />AIR DIFFUSER
<br />2,783
<br />86,406
<br />41
<br />65,473
<br />44
<br />Sub Total =_>
<br />8.
<br />0
<br />PAINT THE
<br />SHEET METAL BACKING BLACK
<br />AT THE RETURN
<br />AIR
<br />0
<br />0
<br />0
<br />0
<br />Ceiling Load
<br />0
<br />GRILLES IN
<br />THE DINING ROOM.
<br />Ventilation Load
<br />0
<br />0
<br />41,472
<br />20
<br />0
<br />0
<br />9.
<br />0
<br />FABRICATE
<br />PLENUM BOX FOR RETURN AIR GRILLE IN FIELD.
<br />REFER TO MECHANICAL
<br />0
<br />0
<br />FLOOR PLAN FOR SIZE.
<br />0
<br />0
<br />Adi Air Trans Heat
<br />0
<br />0
<br />0
<br />Dehumid. Ov Sizing
<br />*
<br />OR EQUAL APPROVED IN WRITING BY OWNER/OWNER'S
<br />REPRESENTATIVE
<br />0
<br />O,uUndr Sizing
<br />LOAD COMPONENT SUMMARY
<br />COOLING COIL PEAK
<br />San Jose, California
<br />Latitude
<br />CLG SPACE PEAK
<br />deg
<br />HEATING COIL PEAK
<br />122.0
<br />Peaked
<br />at Time:
<br />Mini
<br />7 / 17
<br />Elevation
<br />MUMc
<br />Sum of
<br />Barometric pressure
<br />Mo/Hr
<br />Healing Design
<br />Air density
<br />Outside
<br />Air:
<br />OADBM/B/HR: 79/66/76
<br />OADB.
<br />Peaks
<br />Density -specific heat product
<br />OADB:
<br />36
<br />Latent heat factor
<br />4,896.9
<br />Space
<br />Plenum
<br />Net
<br />Percent
<br />Space
<br />Percent
<br />-F
<br />Space Peak
<br />Coil Peak
<br />Percent
<br />Winter design dry bulb
<br />Sons, +Lat.
<br />Sens. +Lat
<br />Toni
<br />Of Total
<br />Sensible
<br />Of Total
<br />0.95
<br />Space Sens
<br />Tot Sens
<br />Of Total
<br />SMOKE DETECTOR
<br />Btu/h
<br />Blu/h
<br />Btu/h
<br />I%)
<br />Btu/h
<br />(%)
<br />Design simulation period
<br />S u t
<br />Btu/h
<br />I%)
<br />Envelope Loads
<br />Heating load methodology
<br />UATD
<br />2000
<br />-2000
<br />EF -4
<br />TOILET
<br />Envelope Loads
<br />SIZE
<br />ROWS
<br />4000
<br />Skylite Solar
<br />0
<br />0
<br />0
<br />0
<br />0
<br />0
<br />Skylite Solar
<br />0
<br />0
<br />0.00
<br />Skylite Cond
<br />0
<br />0
<br />0
<br />0
<br />0
<br />0
<br />Skylite Cond
<br />0
<br />0
<br />0.00
<br />Roof Cond
<br />8,172
<br />0
<br />8,172
<br />4
<br />7,893
<br />5
<br />Roar Cond
<br />-0.100
<br />A,100
<br />2.29
<br />Glass Solar
<br />57,848
<br />0
<br />57,848
<br />28
<br />60,630
<br />41
<br />Glass Solar
<br />0
<br />0
<br />0.00
<br />Glass/Door Cond
<br />1,339
<br />0
<br />1,339
<br />1
<br />2,421
<br />2
<br />Glass/Door Cond
<br />-10,656
<br />-10,656
<br />5.96
<br />Wall Cond
<br />9,079
<br />0
<br />9,079
<br />4
<br />11,974
<br />6
<br />Wall Cond
<br />-7,281
<br />-7,281
<br />4.07
<br />Partition/Door
<br />0
<br />2• INTERLOCK FAN WITH LIGHTSWITCH.
<br />0
<br />0
<br />0
<br />0
<br />PartitioNDoor
<br />0
<br />0
<br />0.00
<br />Floor
<br />0
<br />0
<br />0
<br />0
<br />0
<br />Floor
<br />4,378
<br />4,378
<br />2.45
<br />Adjacent Floor
<br />0
<br />0
<br />0
<br />0
<br />0
<br />0
<br />Adjacent Floor
<br />0
<br />0
<br />0
<br />Infiltration
<br />3,197
<br />3,197
<br />2
<br />1,305
<br />1
<br />Infiltration
<br />-7,710
<br />-7,710
<br />4.31
<br />Sub Total =_>
<br />79,635
<br />0
<br />79,635
<br />38
<br />84,223
<br />56
<br />Sub Total =_>
<br />-34,125
<br />-34,125
<br />19.09
<br />Internal Loads
<br />Internal Loads
<br />Lights
<br />11,132
<br />2,783
<br />13,915
<br />7
<br />11,132
<br />7
<br />Lights
<br />0
<br />0
<br />0.00
<br />People
<br />36,300
<br />0
<br />36,300
<br />17
<br />18,150
<br />12
<br />People
<br />0
<br />0
<br />0.00
<br />Misc
<br />36,191
<br />0
<br />36,191
<br />17
<br />36,191
<br />24
<br />Misc
<br />0
<br />0
<br />0.00
<br />Sub Total =_>
<br />83,623
<br />2,783
<br />86,406
<br />41
<br />65,473
<br />44
<br />Sub Total =_>
<br />0
<br />0
<br />0.00
<br />Ceiling Load
<br />0
<br />0
<br />0
<br />0
<br />0
<br />0
<br />Ceiling Load
<br />0
<br />0
<br />0.00
<br />Ventilation Load
<br />0
<br />0
<br />41,472
<br />20
<br />0
<br />0
<br />Ventilation Load
<br />0
<br />-75,647
<br />42.31
<br />Adj Air Trans Heat
<br />0
<br />0
<br />0
<br />0
<br />0
<br />Adi Air Trans Heat
<br />0
<br />0
<br />0
<br />Dehumid. Ov Sizing
<br />0
<br />0
<br />O,uUndr Sizing
<br />-69,012
<br />-69,012
<br />38.60
<br />Ov/Undr Sizing
<br />0
<br />0
<br />0
<br />0
<br />0
<br />Exhaust Heal
<br />D
<br />0.00
<br />Exhaust Heat
<br />-730
<br />-730
<br />0
<br />OA Preheat Diff.
<br />D
<br />0.00
<br />Sup. Fan Heat
<br />2,019
<br />1
<br />RA Preheat Diff.
<br />0
<br />0.00
<br />Rat. Fan Heat
<br />0
<br />0
<br />0
<br />Additional Reheat
<br />0
<br />0.00
<br />Duct Heat Pkup
<br />0
<br />0
<br />0
<br />Underflr Sup Ht Plop
<br />0
<br />0
<br />Underfir Sup Ht Pkup
<br />0
<br />0.00
<br />Supply Air Leakage
<br />0
<br />0
<br />0
<br />Supply Air Leakage
<br />0
<br />0.00
<br />Grand Total ==>
<br />163,258
<br />2,053
<br />208,802
<br />100.00
<br />149,696
<br />100.00
<br />Grand Total ==>
<br />-103,137
<br />-178,784
<br />100.00
<br />WEATHER
<br />Location
<br />San Jose, California
<br />Latitude
<br />37.0
<br />deg
<br />Longitude
<br />122.0
<br />deg
<br />Time Zone
<br />8
<br />KITCHEN
<br />Elevation
<br />70
<br />ft
<br />Barometric pressure
<br />29.8
<br />in. Hg
<br />Air density
<br />0.0759
<br />Ib/cu ft
<br />Air specific heat
<br />0.2444
<br />Btul
<br />Density -specific heat product
<br />1.1125
<br />Btu/h-cfm-°F
<br />Latent heat factor
<br />4,896.9
<br />Btu-min/h-cu ft
<br />Enthalpy factor
<br />4.5511
<br />Ib-min/hr-cu ft
<br />Summer design dry bulb
<br />85.2
<br />-F
<br />Summer design wet bulb
<br />63.9
<br />-F
<br />Winter design dry bulb
<br />36.0
<br />-F
<br />Summer clearness number
<br />1.05
<br />Winter clearness number
<br />0.95
<br />O.A.
<br />Summer ground reflectance
<br />0.20
<br />SMOKE DETECTOR
<br />Winter ground reflectance
<br />0.20
<br />R.A.
<br />Carbon Dioxide Level
<br />400
<br />ppm
<br />Design simulation period
<br />January - December
<br />Cooling load methodology
<br />TETD-TA1
<br />TE
<br />Heating load methodology
<br />UATD
<br />2000
<br />EQUIPMENT AIR BALANCE SCHEDULE
<br />HVAC
<br />SYMBOLS LEGEND
<br />SUPPLY AIR
<br />CFM
<br />®
<br />SUPPLY AIR DIFFUSER
<br />Z
<br />RETURN AIR GRILLE
<br />R.A.G.
<br />RETURN AIR GRILLE
<br />KITCHEN
<br />VOLUME DAMPER
<br />-G-
<br />GAS LINE
<br />SIZE
<br />I TYPE
<br />T.G.C.
<br />TENANT GENERAL CONTRACTOR
<br />-D-
<br />CONDENSATE DRAIN LINE
<br />DIFF.
<br />DIFFUSER
<br />G.C.
<br />GENERAL CONTRACTOR
<br />M❑
<br />MOTORIZED DAMPER
<br />M.D.
<br />MANUAL DAMPER
<br />R. L.
<br />REFRIGERANT LIQUID LINE
<br />208
<br />SMOKE DETECTION DEVICE
<br />F.C.
<br />FLEXIBLE CONNECTION
<br />R. D.
<br />REFRIGERANT DISCHARGE LINE
<br />QT
<br />THERMOSTAT
<br />6480
<br />AIR DEVICE TYPE
<br />R.S.
<br />REFRIGERANT SUCTION LINE
<br />HOOD -1
<br />AIR VOLUME IN
<br />O.A.
<br />OUTDOOR AIR
<br />SD
<br />SMOKE DETECTOR
<br />HOOD -1
<br />CUBIC FEET/MINUTE (CFM)
<br />R.A.
<br />RETURN AIR
<br />GAS HEAT CAPACITY
<br />3000
<br />-3000
<br />EF -3
<br />S.A.
<br />SUPPLY AIR
<br />TE
<br />TOILET EXHAUST
<br />AFUE%
<br />2000
<br />EQUIPMENT AIR BALANCE SCHEDULE
<br />UNIT
<br />AREA
<br />SERVED
<br />SUPPLY AIR
<br />CFM
<br />RETURN AIR
<br />CFM
<br />OUTSIDE AIR
<br />CFM
<br />MAKE-UP AIR
<br />CFM
<br />EXHAUST AIR
<br />CFM
<br />PRESSURE
<br />CFM
<br />RTU -1
<br />KITCHEN
<br />4000
<br />3090
<br />910
<br />SIZE
<br />I TYPE
<br />+910
<br />RTU -2
<br />DINING
<br />4000
<br />3000
<br />1000
<br />ii
<br />+1000
<br />AIR CFM
<br />CARRIER
<br />48HCDl2
<br />1440.
<br />10.0
<br />208
<br />60
<br />3
<br />MAU-1
<br />HOOD
<br />910
<br />1
<br />20x24xl
<br />6480
<br />CNM
<br />+6480
<br />EF -1
<br />HOOD -1
<br />3000
<br />-3000
<br />EF -2
<br />HOOD -1
<br />COOLING CAPACITY
<br />COOLING CAPACITY
<br />GAS HEAT CAPACITY
<br />3000
<br />-3000
<br />EF -3
<br />HOOD -2
<br />EVAPORATOR
<br />CFM
<br />EER
<br />AFUE%
<br />2000
<br />-2000
<br />EF -4
<br />TOILET
<br />OUTPUT
<br />SIZE
<br />ROWS
<br />4000
<br />150
<br />-150
<br />EF -5
<br />TOILET
<br />148.0
<br />82
<br />12.36
<br />3
<br />150
<br />-150
<br />TOTALS
<br />MBH
<br />8000
<br />6090
<br />1910
<br />6480
<br />8300 CFM
<br />+90
<br />NEW ROOFTOP UNIT SCHEDULE (RTU -1 -KITCHEN)
<br />MFR.
<br />MODEL NO.
<br />TOTAL
<br />c
<br />00
<br />VOLTS
<br />HZ
<br />PH
<br />MCA
<br />MOCP
<br />MIN. OUTSIDE
<br />FILTERS
<br />FILTERS
<br />NO.1
<br />SIZE
<br />I TYPE
<br />ILo
<br />UNIT WT.
<br />UNIT AT.
<br />SIZE
<br />N
<br />w
<br />ii
<br />AIR CFM
<br />AIR CFM
<br />CARRIER
<br />48HCDl2
<br />1440.
<br />10.0
<br />208
<br />60
<br />3
<br />48.8
<br />70.0
<br />910
<br />1
<br />20x24xl
<br />MERV 8
<br />CNM
<br />LBS.TOTAL
<br />LBSTOTAL
<br />TONS
<br />COOLING CAPACITY
<br />COOLING CAPACITY
<br />GAS HEAT CAPACITY
<br />GAS HEAT CAPACITY
<br />EVAP. COIL
<br />EVAP. COIL
<br />CFM
<br />EVAPORATOR
<br />CFM
<br />EER
<br />AFUE%
<br />FAN MOTOR
<br />SENSIBLE
<br />TOTAL
<br />INPUT
<br />OUTPUT
<br />SIZE
<br />ROWS
<br />4000
<br />89.6
<br />119.5
<br />11.5
<br />180.0
<br />148.0
<br />82
<br />12.36
<br />3
<br />MBH
<br />1.0 HP
<br />MBH
<br />MBH
<br />MBH
<br />MBH
<br />SQ.FT.
<br />1. INCLUDES FAN AND MOTOR HEAT.
<br />2. CONTRACTOR SHALL PROVIDE HONEYWELL PRESTIGE IAQ KIT MODEL YTHX9421R7001WW.
<br />3. BLOWER FAN MAINTAINS CONTINUOUS OPERATION DURING OCCUPIED HOURS.
<br />NOTES:
<br />INSTALLED OPTION FAULT DETECTION & DIAGNOSTICS (FDD) WITH BAROMETRIC RELIEF.
<br />1. INCLUDES FAN AND MOTOR HEAT.
<br />6. UNIT EQUIPPED WITH MULTI -SPEED AIR VOLUME BLOWER. BOTH THE LOW SPEED
<br />2. CONTRACTOR SHALL PROVIDE HONEYWELL PRESTIGE AQ KIT MODEL YTHX9421R7001WW.
<br />BALANCED TO CFM SPECIFIED.
<br />3. BLOWER FAN MAINTAINS CONTINUOUS OPERATION DURING OCCUPIED HOURS.
<br />8. INCLUDES FACTORY INSTALLED SUPPLY SMOKE DETECTOR.
<br />4. INCLUDES FACTORY INSTALLED LOW LEAK ECONOMIZER FACTORY
<br />EXHAUST FAN SCHEDULE (EF -4 + EF -5)
<br />INSTALLED OPTION FAULT DETECTION & DIAGNOSTICS (FDD) WITH BAROMETRIC RELIEF.
<br />MODEL NO.
<br />5. PROVIDE 14' ROOF CURB.
<br />DRIVE
<br />6. UNIT EQUIPPED WITH MULTI -SPEED AIR VOLUME BLOWER. BOTH THE LOW SPEED
<br />NOMINAL
<br />MINIMUM POSITION AND THE HIGH SPEED MINIMUM POSITION SETTING SHALL BE
<br />SONES
<br />BALANCED TO CFM SPECIFIED.
<br />PH
<br />7. INCLUDES NON -POWER CONVENIENCE OUTLET
<br />WEIGHT
<br />8. INCLUDES FACTORY INSTALLED SUPPLY SMOKE DETECTOR.
<br />NEW ROOFTOP UNIT SCHEDULE (RTU -2 -DINING)
<br />MFR.
<br />MODEL N0.
<br />TOTALMIN.
<br />c
<br />00
<br />VOLTS
<br />HZ
<br />PH
<br />MCA MOCP
<br />U�ommW
<br />OUTSIDE
<br />FILTERS
<br />1NO.1
<br />SIZE I
<br />TYPE
<br />H
<br />ILo
<br />UNIT WT.
<br />SIZE
<br />U
<br />N
<br />w
<br />ii
<br />AIR CFM
<br />CARRIER
<br />48HCD12
<br />1440
<br />10
<br />208
<br />60
<br />3
<br />48.8
<br />70.0
<br />1000
<br />1
<br />20x24xl
<br />MERV 8
<br />CNM
<br />LBS.TOTAL
<br />TONS
<br />COOLING CAPACITY
<br />GAS HEAT CAPACITY
<br />EVAP. COIL
<br />EVAPORATOR
<br />CFM
<br />EER
<br />AFUE%
<br />FAN MOTOR
<br />SENSIBLE
<br />TOTAL
<br />INPUT
<br />OUTPUT
<br />SIZE
<br />ROWS
<br />4000
<br />89.6
<br />119.5
<br />11.5
<br />180.0
<br />148.0
<br />82
<br />12.36
<br />3
<br />1.0 HP
<br />MBH
<br />MBH
<br />MBH
<br />MBH
<br />SQ.FT.
<br />NOTES:
<br />1. INCLUDES FAN AND MOTOR HEAT.
<br />2. CONTRACTOR SHALL PROVIDE HONEYWELL PRESTIGE IAQ KIT MODEL YTHX9421R7001WW.
<br />3. BLOWER FAN MAINTAINS CONTINUOUS OPERATION DURING OCCUPIED HOURS.
<br />4. INCLUDES FACTORY INSTALLED LOW LEAK ECONOMIZER FACTORY
<br />INSTALLED OPTION FAULT DETECTION & DIAGNOSTICS (FDD) WITH BAROMETRIC RELIEF.
<br />5. PROVIDE 14" ROOF CURB.
<br />6. UNIT EQUIPPED WITH MULTI -SPEED AIR VOLUME BLOWER. BOTH THE LOW SPEED
<br />MINIMUM POSITION AND THE HIGH SPEED MINIMUM POSITION SETTING SHALL BE
<br />BALANCED TO CFM SPECIFIED.
<br />7. INCLUDES NON -POWER CONVENIENCE OUTLET
<br />8. INCLUDES FACTORY INSTALLED SUPPLY SMOKE DETECTOR.
<br />EXHAUST FAN SCHEDULE (EF -4 + EF -5)
<br />MANUFACTURER
<br />MODEL NO.
<br />TOTAL S.P.
<br />IN WG.
<br />DRIVE
<br />MOTOR
<br />NOMINAL
<br />CFM
<br />SONES
<br />VOLTS
<br />PH
<br />HZ
<br />WEIGHT
<br />HP
<br />RPM
<br />GREENHECK
<br />SP -13150
<br />0.375"
<br />DIRECT
<br />128 W
<br />1.050
<br />150
<br />3.5
<br />120
<br />1
<br />60
<br />10 LBS.
<br />NOTES:
<br />1. PROVIDE BACKDRAFT DAMPER.
<br />2• INTERLOCK FAN WITH LIGHTSWITCH.
<br />sea/
<br />Csn•u/bnf
<br />OLD
<br />c
<br />N
<br />c
<br />00
<br />E `
<br />NV
<br />p q
<br />�oN
<br />p0er
<br />OLD
<br />c
<br />Vv
<br />c
<br />00
<br />•I_N
<br />p q
<br />�oN
<br />p0er
<br />U�ommW
<br />M
<br />LU
<br />N
<br />LU
<br />Q
<br />M
<br />LU
<br />IL0
<br />O
<br />H
<br />ILo
<br />U
<br />N
<br />w
<br />ii
<br />Q
<br />.0
<br />O
<br />U
<br />>-
<br />LU
<br />O
<br />LU
<br />~
<br />Z
<br />~
<br />U)
<br />M
<br />Q
<br />CNM
<br />C0
<br />LU
<br />J
<br />0
<br />UJ
<br />U
<br />C0
<br />J
<br />U_
<br />Z
<br />2
<br />0
<br />UJ
<br />G
<br />Project Number 17-536
<br />Plan Check Number
<br />10/12/17 /\ ISSUEFORPERMIT
<br />M300