GREEN BUILDING NOTES <br />1. CONSTRUCTION TO CONFORM TO CALIFORNIA ENERGY COMMISSION <br />MANDATORY BUILDING STANDARDS. <br />2. PROVIDE TEMPORARY VENTILATION DURING CONSTRUCTION IN <br />ACCORDANCE WITH SECTION 5.504.1.3 OF CALIFORNIA GREEN <br />BUILDING STANDARDS CODE. <br />3. IF THE HVAC SYSTEM IS USED DURING CONSTRUCTION, USE RETURN <br />AIR FILTERS WITH A MERV OF 8, BASED ON ASHRAE 52.2-1999, OR <br />AN AVERAGE EFFICIENCY OF 30% BASED ON ASHRAE 52.1-1999. <br />REPLACE ALL FILTERS IMMEDIATELY PRIOR TO OCCUPANCY. <br />4. AT THE TIME OF ROUGH INSTALLATION OR DURING STORAGE ON THE <br />CONSTRUCTION SITE AND UNTIL START-UP OF THE HEATING AND <br />COOLING EQUIPMENT, ALL DUCTS AND OTHER RELATED AIR <br />DISTRIBUTION COMPONENT EQUIPMENT SHALL BE COVERED WITH <br />TAPE, PLASTIC, SHEETMETAL OR OTHER METHODS ACCEPTABLE TO THE <br />ENFORCING AGENCY TO REDUCE THE AMOUNT OF DUST OR DEBRIS <br />WHICH MAY COLLECT IN THE SYSTEM. CGBC 5.504.3. <br />5. ADHESIVES, ADHESIVE BONDING PRIMERS, ADHESIVE PRIMERS, <br />SEALANTS, SEALANT PRIMERS AND CAULKS SHALL COMPLY WITH <br />LOCAL OR REGIONAL AIR POLLUTION CONTROL OR AIR QUALITY <br />MANAGEMENT DISTRICT RULES WHERE APPLICABLE OR SCAQMD RULE <br />1168 VOC LIMITS, AS SHOWN IN TABLES 5.504.4.1 AND 5.504.4.2 <br />AEROSOL ADHESIVES AND SMALLER UNIT SIZED OF ADHESIVES AND <br />SEALANT OR CAULKING COMPOUNDS (IN UNITS OF PRODUCT, LESS <br />PACKAGING WHICH DO NOT WEIGHT MORE THAN ONE POUND AND DO <br />NOT CONSIST OF MORE THAN 16 FLUID OUNCES) SHALL COMPLY <br />WITH STATEWIDE VOC STANDARDS AND OTHER REQUIREMENTS, <br />INCLUDING PROHIBITIONS ON USE OF CERTAIN TOXIN COMPOUNDS, OF <br />CALIFORNIA CODE OF REGULATIONS, TITLE 17, COMMENCING WITH <br />SECTION 94507.0 <br />6. IN MECHANICAL VENTILATION BUILDING, PROVIDE REGULARLY OCCUPIED <br />AREAS OF THE BUILDING WITH AIR FILTRATION MEDIA FOR OUTSIDE <br />AND RETURN AIR PRIOR OCCUPANCY THAT PROVIDES AT LEAST A <br />MERV 8. MERV 8 FILTERS SHALL BE INSTALLED PRIOR TO <br />OCCUPANCY, AND RECOMMENDATIONS FOR MAINTENANCE WITH FILTERS <br />OF THE SAME VALUE SHALL BE INCLUDED IN THE OPERATION AND <br />MAINTENANCE MANUAL. <br />7. MECHANICAL VENTILATION CALCULATED PER SECTION 120.1 OF THE <br />CALIFORNIA ENERGY CODE, TITLE 24, SECTION 6. <br />8. INSTALL HVAC, REFRIGERATION EQUIPMENT THAT DOES NOT CONTAIN <br />CFCs OR HALONS. <br />9. BUILDINGS SHALL MEET OR EXCEED THE PROVISIONS OF THE 2016 <br />CALIFORNIA BUILDING CODE, CHAPTER 12 (VENTILATION) AND CHAPTER <br />14 (EXTERIOR WALL) FOR INDOOR MOISTURE CONTROL. 2016 CGC <br />5.505. <br />10. BUILDINGS MUST MEET THE MINIMUM REQUIREMENTS OF THE 2016 <br />CALIFORNIA BUILDING CODE, CHAPTER 12 (VENTILATION) FOR <br />MECHANICALLY OR NATURALLY VENTILATED SPACES. 2016 CGC <br />5.506.1. <br />Habit HVAC system T & B Scope of Work 2015 <br />All third party air balance companies used on Habit projects to be either NEBB or AABC certified and have current certification and <br />applicable licensing. Note that complete and full air balance applies to ALL equipment servicing Habits TI space including HVAC, <br />MAU, exhaust hood & fans restroom exhaust fans and PCU units (where occurs), regardless of who supplies equipment. <br />1. Inspection <br />• Inspect general condition of HVAC systems and installation. Record equipment data and compare with design <br />requirements <br />2. Testing: Test HVAC systems for proper operation <br />• Inspect Rooftop units for proper operation: <br />• Verify fan rotation <br />• Measure/record motor amperage <br />• Measure/record voltage <br />• Verify sequence of operation (test heating/cooling modes) <br />• Set T -Stats to Habit standards: <br />o Occupied -7:30 a.m. to 11: 30 p.m. - 74 degrees cool 68 degrees heat - Fan setting - ON <br />o Unoccupied -11:30 p.m. to 7:30 a.m.- 80 degrees cool 60 degrees heat - Fan setting - AUTO <br />• Verify that all units have spare fan belt located inside unit <br />• Verify duct smoke detectors are installed and connected (resets to be located in office) <br />• Verify and set economizer's to engineered drawing specifications. See Mechanical sheets for data <br />2.1. Make Up Air Unit (MAU) <br />• Inspect MUA unit for proper operation: <br />• Verify fan rotation <br />• Measure/record motor amperage <br />• Measure/record voltage <br />• Verify sequence of operation (test heating/cooling modes) <br />• Set evaporator thermostat adjustment per CaptiveAire specifications <br />3. Balance and Verify: <br />• Balance the kitchen exhaust system for proper heat and smoke capture removal. Verify proper performance with <br />smoke emitter tests. <br />• Balance the air conditioning & heating units for optimal air distribution and comfort <br />• Correct fan rotation, belt tension, sheave alignment, damper position on all units. Check for clean filters and coils <br />• Balance the building for proper fresh air quantities and pressurization in all areas of the store. <br />4. Measurements: <br />• Measure and record airflow, motor speed, motor amp draw, and compare to nameplate data and specifications. <br />5. Adjustments: <br />• Reduce fan speeds when possible to save fan energy and conditioned air, and reduce noise levels, while maintaining <br />comfort. <br />• Balanced system needs to maintain positive building pressure once complete <br />6. Tolerance: <br />• HVAC system airflows to be balanced within +/- S% of design. <br />7. Performance Verification: <br />• Upon completion of the balance, verify HVAC performance via slight positive building pressure, occupant comfort, and <br />capture and containment of kitchen hoods <br />S. Documentation & clarifications: <br />• Submit a NEBB or AABC Certified test and balance report with findings including the equipment data, measurements, <br />list of deficiencies, and recommendations. This information to be submitted directly to the architect of record for <br />review, comment and approval by their respective mechanical engineer. Habit to be copied on these <br />correspondences. <br />• Provide equipment commissioning reports to architect of record. Habit to be copied on these correspondences. <br />• Installing HVAC contractor cannot self -certify or be the preforming agent of T & B <br />• If T & B report is incomplete of fails review, Habit at its own discretion may choose to have the entire system <br />retested by an accredited air balance company of our choosing. The cost of said re -test will come at the direct <br />expense of the contracted GC of the project. <br />LOAD COMPONENT SUMMARY <br />COOLING COIL PEAK <br />San Jose, California <br />Latitude <br />AIR DEVICE SCHEDULE e <br />deg <br />HEATING COIL PEAK <br />122.0 <br />PLAN <br />at Time: <br />Mini <br />FACE <br />NECK <br />FLEX <br />Sum of <br />Barometric pressure <br />Mo/Hr <br />Healing Design <br />MARK <br />QTY. <br />MODEL NO. <br />SIZE <br />SIZE <br />SIZE <br />TYPE <br />OADB: <br />36 <br />NOTES <br />4,896.9 <br />A <br />Plenum <br />5 <br />*TITUS 30ORL <br />16"x10" <br />14"x8" <br />NA <br />DOUBLE DEFLECTION <br />BAR SUPPLY <br />2,3,5 <br />Winter design dry bulb <br />B <br />Sens. +Lat <br />18 <br />*TITUS PAS <br />16"06" <br />8" RD. <br />8" RD. <br />PERFORATED <br />SUPPLY <br />DIFFUSER <br />2,3,5 <br />Btu/h <br />C <br />Btu/h <br />5 <br />*TITUS PAS <br />12"02" <br />6" RD. <br />6" RD. <br />PERFORATED <br />SUPPLY <br />DIFFUSER <br />2,3,5 <br />UATD <br />D <br />-2000 <br />0 <br />*TITUS PAS <br />16"x16" <br />12" RD. <br />12" RD. <br />PERFORATED <br />SUPPLY <br />DIFFUSER <br />1,3,5 <br />0 <br />E <br />0 <br />4 <br />*TITUS PAR <br />24"x24" <br />14" RD. <br />14" RD. <br />PERFORATED <br />SUPPLY <br />DIFFUSER <br />2,3,4,7 <br />0 <br />F <br />0 <br />1 <br />*TITUS PAS <br />24"x24" <br />12" RD. <br />12" RD. <br />PERFORATED <br />SUPPLY <br />DIFFUSER <br />2,3,4 <br />7,893 <br />G <br />Roar Cond <br />1 <br />*TITUS PAS <br />24"x24" <br />6" RD. <br />6" RD. <br />PERFORATED <br />SUPPLY <br />DIFFUSER <br />2,3,4 <br />41 <br />H <br />0 <br />1 <br />*TITUS PAR <br />12"x24" <br />6" RD. <br />6" RD. <br />PERFORATED <br />TRANSFER GRILLE <br />3,4,6 <br />2 <br />Glass/Door Cond <br />-10,656 <br />3 <br />*TITUS PAR <br />24"x24" <br />16" RD. <br />16" RD. <br />PERFORATED <br />RETURN <br />GRILLE <br />3,4 <br />Wall Cond <br />-7,281 <br />-7,281 <br />2 <br />*TITUS PAR <br />24"x24" <br />20" RD. <br />20" RD. <br />PERFORATED <br />RETURN <br />GRILLE <br />3,4,8 <br />0 <br />K <br />0.00 <br />0 <br />*TITUS PDR <br />48"x24" <br />16" RD. <br />16" RD. <br />PERFORATED <br />RETURN <br />GRILLE <br />3,4,8,9 <br />4,378 <br />L <br />Adjacent Floor <br />0 <br />*TITUS PDR <br />24"x24" <br />16" RD. <br />16" RD. <br />PERFORATED <br />RETURN <br />GRILLE <br />3,4,8 <br />NOTES: <br />Infiltration <br />3,197 <br />3,197 <br />2 <br />1,305 <br />1 <br />Infiltration <br />1. <br />-7,710 <br />PROVIDE VERTICAL PATTERN <br />CONTROLLER <br />79,635 <br />0 <br />79,635 <br />38 <br />84,223 <br />56 <br />2. <br />-34,125 <br />REFER TO <br />PLAN FOR THROW PATTERN ORIENTATION <br />Internal Loads <br />3. <br />PROVIDE MANUAL VOLUME DAMPER <br />Lights <br />11,132 <br />2,783 <br />4. <br />7 <br />FRAME SHALL FIT LAY -IN CEILING MODULE <br />7 <br />Lights <br />0 <br />0 <br />0.00 <br />People <br />5. <br />0 <br />FRAME SHALL FIT GYPSUM BOARD CEILING/SURFACE <br />17 <br />18,150 <br />12 <br />People <br />0 <br />6. <br />0.00 <br />TRANSFER <br />GRILLE <br />0 <br />36,191 <br />17 <br />36,191 <br />24 <br />Misc <br />0 <br />7. <br />0.00 <br />DOWN DISCHARGE TYPE SUPPLY <br />AIR DIFFUSER <br />2,783 <br />86,406 <br />41 <br />65,473 <br />44 <br />Sub Total =_> <br />8. <br />0 <br />PAINT THE <br />SHEET METAL BACKING BLACK <br />AT THE RETURN <br />AIR <br />0 <br />0 <br />0 <br />0 <br />Ceiling Load <br />0 <br />GRILLES IN <br />THE DINING ROOM. <br />Ventilation Load <br />0 <br />0 <br />41,472 <br />20 <br />0 <br />0 <br />9. <br />0 <br />FABRICATE <br />PLENUM BOX FOR RETURN AIR GRILLE IN FIELD. <br />REFER TO MECHANICAL <br />0 <br />0 <br />FLOOR PLAN FOR SIZE. <br />0 <br />0 <br />Adi Air Trans Heat <br />0 <br />0 <br />0 <br />Dehumid. Ov Sizing <br />* <br />OR EQUAL APPROVED IN WRITING BY OWNER/OWNER'S <br />REPRESENTATIVE <br />0 <br />O,uUndr Sizing <br />LOAD COMPONENT SUMMARY <br />COOLING COIL PEAK <br />San Jose, California <br />Latitude <br />CLG SPACE PEAK <br />deg <br />HEATING COIL PEAK <br />122.0 <br />Peaked <br />at Time: <br />Mini <br />7 / 17 <br />Elevation <br />MUMc <br />Sum of <br />Barometric pressure <br />Mo/Hr <br />Healing Design <br />Air density <br />Outside <br />Air: <br />OADBM/B/HR: 79/66/76 <br />OADB. <br />Peaks <br />Density -specific heat product <br />OADB: <br />36 <br />Latent heat factor <br />4,896.9 <br />Space <br />Plenum <br />Net <br />Percent <br />Space <br />Percent <br />-F <br />Space Peak <br />Coil Peak <br />Percent <br />Winter design dry bulb <br />Sons, +Lat. <br />Sens. +Lat <br />Toni <br />Of Total <br />Sensible <br />Of Total <br />0.95 <br />Space Sens <br />Tot Sens <br />Of Total <br />SMOKE DETECTOR <br />Btu/h <br />Blu/h <br />Btu/h <br />I%) <br />Btu/h <br />(%) <br />Design simulation period <br />S u t <br />Btu/h <br />I%) <br />Envelope Loads <br />Heating load methodology <br />UATD <br />2000 <br />-2000 <br />EF -4 <br />TOILET <br />Envelope Loads <br />SIZE <br />ROWS <br />4000 <br />Skylite Solar <br />0 <br />0 <br />0 <br />0 <br />0 <br />0 <br />Skylite Solar <br />0 <br />0 <br />0.00 <br />Skylite Cond <br />0 <br />0 <br />0 <br />0 <br />0 <br />0 <br />Skylite Cond <br />0 <br />0 <br />0.00 <br />Roof Cond <br />8,172 <br />0 <br />8,172 <br />4 <br />7,893 <br />5 <br />Roar Cond <br />-0.100 <br />A,100 <br />2.29 <br />Glass Solar <br />57,848 <br />0 <br />57,848 <br />28 <br />60,630 <br />41 <br />Glass Solar <br />0 <br />0 <br />0.00 <br />Glass/Door Cond <br />1,339 <br />0 <br />1,339 <br />1 <br />2,421 <br />2 <br />Glass/Door Cond <br />-10,656 <br />-10,656 <br />5.96 <br />Wall Cond <br />9,079 <br />0 <br />9,079 <br />4 <br />11,974 <br />6 <br />Wall Cond <br />-7,281 <br />-7,281 <br />4.07 <br />Partition/Door <br />0 <br />2• INTERLOCK FAN WITH LIGHTSWITCH. <br />0 <br />0 <br />0 <br />0 <br />PartitioNDoor <br />0 <br />0 <br />0.00 <br />Floor <br />0 <br />0 <br />0 <br />0 <br />0 <br />Floor <br />4,378 <br />4,378 <br />2.45 <br />Adjacent Floor <br />0 <br />0 <br />0 <br />0 <br />0 <br />0 <br />Adjacent Floor <br />0 <br />0 <br />0 <br />Infiltration <br />3,197 <br />3,197 <br />2 <br />1,305 <br />1 <br />Infiltration <br />-7,710 <br />-7,710 <br />4.31 <br />Sub Total =_> <br />79,635 <br />0 <br />79,635 <br />38 <br />84,223 <br />56 <br />Sub Total =_> <br />-34,125 <br />-34,125 <br />19.09 <br />Internal Loads <br />Internal Loads <br />Lights <br />11,132 <br />2,783 <br />13,915 <br />7 <br />11,132 <br />7 <br />Lights <br />0 <br />0 <br />0.00 <br />People <br />36,300 <br />0 <br />36,300 <br />17 <br />18,150 <br />12 <br />People <br />0 <br />0 <br />0.00 <br />Misc <br />36,191 <br />0 <br />36,191 <br />17 <br />36,191 <br />24 <br />Misc <br />0 <br />0 <br />0.00 <br />Sub Total =_> <br />83,623 <br />2,783 <br />86,406 <br />41 <br />65,473 <br />44 <br />Sub Total =_> <br />0 <br />0 <br />0.00 <br />Ceiling Load <br />0 <br />0 <br />0 <br />0 <br />0 <br />0 <br />Ceiling Load <br />0 <br />0 <br />0.00 <br />Ventilation Load <br />0 <br />0 <br />41,472 <br />20 <br />0 <br />0 <br />Ventilation Load <br />0 <br />-75,647 <br />42.31 <br />Adj Air Trans Heat <br />0 <br />0 <br />0 <br />0 <br />0 <br />Adi Air Trans Heat <br />0 <br />0 <br />0 <br />Dehumid. Ov Sizing <br />0 <br />0 <br />O,uUndr Sizing <br />-69,012 <br />-69,012 <br />38.60 <br />Ov/Undr Sizing <br />0 <br />0 <br />0 <br />0 <br />0 <br />Exhaust Heal <br />D <br />0.00 <br />Exhaust Heat <br />-730 <br />-730 <br />0 <br />OA Preheat Diff. <br />D <br />0.00 <br />Sup. Fan Heat <br />2,019 <br />1 <br />RA Preheat Diff. <br />0 <br />0.00 <br />Rat. Fan Heat <br />0 <br />0 <br />0 <br />Additional Reheat <br />0 <br />0.00 <br />Duct Heat Pkup <br />0 <br />0 <br />0 <br />Underflr Sup Ht Plop <br />0 <br />0 <br />Underfir Sup Ht Pkup <br />0 <br />0.00 <br />Supply Air Leakage <br />0 <br />0 <br />0 <br />Supply Air Leakage <br />0 <br />0.00 <br />Grand Total ==> <br />163,258 <br />2,053 <br />208,802 <br />100.00 <br />149,696 <br />100.00 <br />Grand Total ==> <br />-103,137 <br />-178,784 <br />100.00 <br />WEATHER <br />Location <br />San Jose, California <br />Latitude <br />37.0 <br />deg <br />Longitude <br />122.0 <br />deg <br />Time Zone <br />8 <br />KITCHEN <br />Elevation <br />70 <br />ft <br />Barometric pressure <br />29.8 <br />in. Hg <br />Air density <br />0.0759 <br />Ib/cu ft <br />Air specific heat <br />0.2444 <br />Btul <br />Density -specific heat product <br />1.1125 <br />Btu/h-cfm-°F <br />Latent heat factor <br />4,896.9 <br />Btu-min/h-cu ft <br />Enthalpy factor <br />4.5511 <br />Ib-min/hr-cu ft <br />Summer design dry bulb <br />85.2 <br />-F <br />Summer design wet bulb <br />63.9 <br />-F <br />Winter design dry bulb <br />36.0 <br />-F <br />Summer clearness number <br />1.05 <br />Winter clearness number <br />0.95 <br />O.A. <br />Summer ground reflectance <br />0.20 <br />SMOKE DETECTOR <br />Winter ground reflectance <br />0.20 <br />R.A. <br />Carbon Dioxide Level <br />400 <br />ppm <br />Design simulation period <br />January - December <br />Cooling load methodology <br />TETD-TA1 <br />TE <br />Heating load methodology <br />UATD <br />2000 <br />EQUIPMENT AIR BALANCE SCHEDULE <br />HVAC <br />SYMBOLS LEGEND <br />SUPPLY AIR <br />CFM <br />® <br />SUPPLY AIR DIFFUSER <br />Z <br />RETURN AIR GRILLE <br />R.A.G. <br />RETURN AIR GRILLE <br />KITCHEN <br />VOLUME DAMPER <br />-G- <br />GAS LINE <br />SIZE <br />I TYPE <br />T.G.C. <br />TENANT GENERAL CONTRACTOR <br />-D- <br />CONDENSATE DRAIN LINE <br />DIFF. <br />DIFFUSER <br />G.C. <br />GENERAL CONTRACTOR <br />M❑ <br />MOTORIZED DAMPER <br />M.D. <br />MANUAL DAMPER <br />R. L. <br />REFRIGERANT LIQUID LINE <br />208 <br />SMOKE DETECTION DEVICE <br />F.C. <br />FLEXIBLE CONNECTION <br />R. D. <br />REFRIGERANT DISCHARGE LINE <br />QT <br />THERMOSTAT <br />6480 <br />AIR DEVICE TYPE <br />R.S. <br />REFRIGERANT SUCTION LINE <br />HOOD -1 <br />AIR VOLUME IN <br />O.A. <br />OUTDOOR AIR <br />SD <br />SMOKE DETECTOR <br />HOOD -1 <br />CUBIC FEET/MINUTE (CFM) <br />R.A. <br />RETURN AIR <br />GAS HEAT CAPACITY <br />3000 <br />-3000 <br />EF -3 <br />S.A. <br />SUPPLY AIR <br />TE <br />TOILET EXHAUST <br />AFUE% <br />2000 <br />EQUIPMENT AIR BALANCE SCHEDULE <br />UNIT <br />AREA <br />SERVED <br />SUPPLY AIR <br />CFM <br />RETURN AIR <br />CFM <br />OUTSIDE AIR <br />CFM <br />MAKE-UP AIR <br />CFM <br />EXHAUST AIR <br />CFM <br />PRESSURE <br />CFM <br />RTU -1 <br />KITCHEN <br />4000 <br />3090 <br />910 <br />SIZE <br />I TYPE <br />+910 <br />RTU -2 <br />DINING <br />4000 <br />3000 <br />1000 <br />ii <br />+1000 <br />AIR CFM <br />CARRIER <br />48HCDl2 <br />1440. <br />10.0 <br />208 <br />60 <br />3 <br />MAU-1 <br />HOOD <br />910 <br />1 <br />20x24xl <br />6480 <br />CNM <br />+6480 <br />EF -1 <br />HOOD -1 <br />3000 <br />-3000 <br />EF -2 <br />HOOD -1 <br />COOLING CAPACITY <br />COOLING CAPACITY <br />GAS HEAT CAPACITY <br />3000 <br />-3000 <br />EF -3 <br />HOOD -2 <br />EVAPORATOR <br />CFM <br />EER <br />AFUE% <br />2000 <br />-2000 <br />EF -4 <br />TOILET <br />OUTPUT <br />SIZE <br />ROWS <br />4000 <br />150 <br />-150 <br />EF -5 <br />TOILET <br />148.0 <br />82 <br />12.36 <br />3 <br />150 <br />-150 <br />TOTALS <br />MBH <br />8000 <br />6090 <br />1910 <br />6480 <br />8300 CFM <br />+90 <br />NEW ROOFTOP UNIT SCHEDULE (RTU -1 -KITCHEN) <br />MFR. <br />MODEL NO. <br />TOTAL <br />c <br />00 <br />VOLTS <br />HZ <br />PH <br />MCA <br />MOCP <br />MIN. OUTSIDE <br />FILTERS <br />FILTERS <br />NO.1 <br />SIZE <br />I TYPE <br />ILo <br />UNIT WT. <br />UNIT AT. <br />SIZE <br />N <br />w <br />ii <br />AIR CFM <br />AIR CFM <br />CARRIER <br />48HCDl2 <br />1440. <br />10.0 <br />208 <br />60 <br />3 <br />48.8 <br />70.0 <br />910 <br />1 <br />20x24xl <br />MERV 8 <br />CNM <br />LBS.TOTAL <br />LBSTOTAL <br />TONS <br />COOLING CAPACITY <br />COOLING CAPACITY <br />GAS HEAT CAPACITY <br />GAS HEAT CAPACITY <br />EVAP. COIL <br />EVAP. COIL <br />CFM <br />EVAPORATOR <br />CFM <br />EER <br />AFUE% <br />FAN MOTOR <br />SENSIBLE <br />TOTAL <br />INPUT <br />OUTPUT <br />SIZE <br />ROWS <br />4000 <br />89.6 <br />119.5 <br />11.5 <br />180.0 <br />148.0 <br />82 <br />12.36 <br />3 <br />MBH <br />1.0 HP <br />MBH <br />MBH <br />MBH <br />MBH <br />SQ.FT. <br />1. INCLUDES FAN AND MOTOR HEAT. <br />2. CONTRACTOR SHALL PROVIDE HONEYWELL PRESTIGE IAQ KIT MODEL YTHX9421R7001WW. <br />3. BLOWER FAN MAINTAINS CONTINUOUS OPERATION DURING OCCUPIED HOURS. <br />NOTES: <br />INSTALLED OPTION FAULT DETECTION & DIAGNOSTICS (FDD) WITH BAROMETRIC RELIEF. <br />1. INCLUDES FAN AND MOTOR HEAT. <br />6. UNIT EQUIPPED WITH MULTI -SPEED AIR VOLUME BLOWER. BOTH THE LOW SPEED <br />2. CONTRACTOR SHALL PROVIDE HONEYWELL PRESTIGE AQ KIT MODEL YTHX9421R7001WW. <br />BALANCED TO CFM SPECIFIED. <br />3. BLOWER FAN MAINTAINS CONTINUOUS OPERATION DURING OCCUPIED HOURS. <br />8. INCLUDES FACTORY INSTALLED SUPPLY SMOKE DETECTOR. <br />4. INCLUDES FACTORY INSTALLED LOW LEAK ECONOMIZER FACTORY <br />EXHAUST FAN SCHEDULE (EF -4 + EF -5) <br />INSTALLED OPTION FAULT DETECTION & DIAGNOSTICS (FDD) WITH BAROMETRIC RELIEF. <br />MODEL NO. <br />5. PROVIDE 14' ROOF CURB. <br />DRIVE <br />6. UNIT EQUIPPED WITH MULTI -SPEED AIR VOLUME BLOWER. BOTH THE LOW SPEED <br />NOMINAL <br />MINIMUM POSITION AND THE HIGH SPEED MINIMUM POSITION SETTING SHALL BE <br />SONES <br />BALANCED TO CFM SPECIFIED. <br />PH <br />7. INCLUDES NON -POWER CONVENIENCE OUTLET <br />WEIGHT <br />8. INCLUDES FACTORY INSTALLED SUPPLY SMOKE DETECTOR. <br />NEW ROOFTOP UNIT SCHEDULE (RTU -2 -DINING) <br />MFR. <br />MODEL N0. <br />TOTALMIN. <br />c <br />00 <br />VOLTS <br />HZ <br />PH <br />MCA MOCP <br />U�ommW <br />OUTSIDE <br />FILTERS <br />1NO.1 <br />SIZE I <br />TYPE <br />H <br />ILo <br />UNIT WT. <br />SIZE <br />U <br />N <br />w <br />ii <br />AIR CFM <br />CARRIER <br />48HCD12 <br />1440 <br />10 <br />208 <br />60 <br />3 <br />48.8 <br />70.0 <br />1000 <br />1 <br />20x24xl <br />MERV 8 <br />CNM <br />LBS.TOTAL <br />TONS <br />COOLING CAPACITY <br />GAS HEAT CAPACITY <br />EVAP. COIL <br />EVAPORATOR <br />CFM <br />EER <br />AFUE% <br />FAN MOTOR <br />SENSIBLE <br />TOTAL <br />INPUT <br />OUTPUT <br />SIZE <br />ROWS <br />4000 <br />89.6 <br />119.5 <br />11.5 <br />180.0 <br />148.0 <br />82 <br />12.36 <br />3 <br />1.0 HP <br />MBH <br />MBH <br />MBH <br />MBH <br />SQ.FT. <br />NOTES: <br />1. INCLUDES FAN AND MOTOR HEAT. <br />2. CONTRACTOR SHALL PROVIDE HONEYWELL PRESTIGE IAQ KIT MODEL YTHX9421R7001WW. <br />3. BLOWER FAN MAINTAINS CONTINUOUS OPERATION DURING OCCUPIED HOURS. <br />4. INCLUDES FACTORY INSTALLED LOW LEAK ECONOMIZER FACTORY <br />INSTALLED OPTION FAULT DETECTION & DIAGNOSTICS (FDD) WITH BAROMETRIC RELIEF. <br />5. PROVIDE 14" ROOF CURB. <br />6. UNIT EQUIPPED WITH MULTI -SPEED AIR VOLUME BLOWER. BOTH THE LOW SPEED <br />MINIMUM POSITION AND THE HIGH SPEED MINIMUM POSITION SETTING SHALL BE <br />BALANCED TO CFM SPECIFIED. <br />7. INCLUDES NON -POWER CONVENIENCE OUTLET <br />8. INCLUDES FACTORY INSTALLED SUPPLY SMOKE DETECTOR. <br />EXHAUST FAN SCHEDULE (EF -4 + EF -5) <br />MANUFACTURER <br />MODEL NO. <br />TOTAL S.P. <br />IN WG. <br />DRIVE <br />MOTOR <br />NOMINAL <br />CFM <br />SONES <br />VOLTS <br />PH <br />HZ <br />WEIGHT <br />HP <br />RPM <br />GREENHECK <br />SP -13150 <br />0.375" <br />DIRECT <br />128 W <br />1.050 <br />150 <br />3.5 <br />120 <br />1 <br />60 <br />10 LBS. <br />NOTES: <br />1. PROVIDE BACKDRAFT DAMPER. <br />2• INTERLOCK FAN WITH LIGHTSWITCH. <br />sea/ <br />Csn•u/bnf <br />OLD <br />c <br />N <br />c <br />00 <br />E ` <br />NV <br />p q <br />�oN <br />p0er <br />OLD <br />c <br />Vv <br />c <br />00 <br />•I_N <br />p q <br />�oN <br />p0er <br />U�ommW <br />M <br />LU <br />N <br />LU <br />Q <br />M <br />LU <br />IL0 <br />O <br />H <br />ILo <br />U <br />N <br />w <br />ii <br />Q <br />.0 <br />O <br />U <br />>- <br />LU <br />O <br />LU <br />~ <br />Z <br />~ <br />U) <br />M <br />Q <br />CNM <br />C0 <br />LU <br />J <br />0 <br />UJ <br />U <br />C0 <br />J <br />U_ <br />Z <br />2 <br />0 <br />UJ <br />G <br />Project Number 17-536 <br />Plan Check Number <br />10/12/17 /\ ISSUEFORPERMIT <br />M300 <br />