Laserfiche WebLink
Underground Storage Tank <br /> econda�t Containment Testing Report Form <br /> 8 . SUMP/ UDC TEST <br /> Test Method Developed by ❑ Manufacturer Dlndustry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum QHydrostatic <br /> Test Equipment Used : Incon TS STS , <br /> Sump/ UDC ID Piping Vault Fill/ Piping <br /> Sump Manufacturer Bravo Containment <br /> Sump Depth ( inches ) 32 60 <br /> Sump Bottom to Top of 18 27 <br /> Highest Pipe Penetration <br /> ( inches ) <br /> Test Start Time 12 : 18 12 : 34 <br /> Initial Reading 4 . 3941 6 . 0768 <br /> Test End Time 12 : 33 12 : 49 <br /> Final Reading 4 . 3936 6 . 0763 <br /> Change in Reading 0 , 0005 0 . 0005 <br /> Pass/ Fail Criteria 0 . 002 0 . 002 <br /> Tightness Test Results FPass ❑ Fail FvlPass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/ UDC ID <br /> Sump Manufacturer <br /> Sump Depth ( inches ) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> ( inches ) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/ Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail" and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section . <br /> Page 3 of 5 <br />