Laserfiche WebLink
Environmental Health Department <br />Aboveground Petroleum Storage Act Inspection Report <br />Date: <br />March 30, 2022 <br /> Facility Address: <br /> 240 Doak Blvd, RIPON <br /> Facility Name: <br /> RIPON FUEL FACILITY <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br /> 721 CFR 112.8(d)(1) Failed to provide corrosion protection for buried piping. <br />OBSERVATION: Section 2.4 of the SPCC plan states that the facility has no buried piping. Buried piping observed <br />during the inspection from fuel tank to fuel island. <br />REGULATION GUIDANCE: (d)(1) Provide buried piping that is installed or replaced on or after August 16, 2002, <br />with protective wrapping and coating. You must also cathodically protect such buried piping installations or <br />otherwise satisfy the corrosion protection standards for piping in part 280 of this chapter or a State program <br />approved under part 281 of this chapter. If a section of the buried line is exposed for any reason, you must carefully <br />inspect it for deterioration. If you find corrosion damage, you must undertake additional examination and corrective <br />action, as indicated by the magnitude of the damage. <br />CORRECTIVE ACTION: Ensure the SPCC plan adequately discusses buried piping. Provide proof of correction to <br />the EHD. <br />This is a Class II violation. <br />Overall Inspection Comments: <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, by April 30, 2022. <br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br />of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br />($152). To schedule an appointment, please call (209) 468-3420. <br />The following was observed during this inspection: One 10,000 gallon diesel, one 10,000 gallon gasoline <br />The following was provided during this inspection: Schedule of free CUPA classes, [list everything that was <br />provided, hard copies or via email] <br />AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br />THIS FACILITY BACK INTO COMPLIANCE. <br />THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Inspector Phone: <br /> KRISTINA SAETERN, EH Specialist <br /> Inspector:March 30, 2022 Date: <br />Printed Name and Title: <br />Emailed to James Pease, Public Work Director <br />(209) 616-3045 <br />FA0019249 PR0528648 SC001 03/30/2022 <br />EHD 28-01 Rev. 12/06/2021 Aboveground Petroleum Storage Act OIRPage 6 of 6 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD