Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 9. COMMENTS <br /> udc 1/2 and udc 7/8 failed after 3 attempts. suggestion to restest1/2 when station is idle not when <br /> traffic is around the store, fuel dilevery may have contributed to the failed test due to vibrations. <br /> 7/8 has definite small leak at top of udc where rim meets skirt. <br /> failed fill sump <br /> this failed 3 times after attempts to find bubbles on line or boots. further repairs may be needed. <br /> line pressure test 5psi on aux diesel line failed after 30 seconds of entering pressure. attempts 3 <br /> bravo boot installed on western fiberglass sumps <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 5 of 5 <br />