Laserfiche WebLink
Section 1 — <br /> Waste Oil Storage <br /> Tank Assessment Page: <br /> Tank Name/marking: <br /> Waste Oil Storage Taut <br /> Tank age: 191(g)(3)/192(k)(3): 17 years <br /> Remaining service life: 191(g)(10)/192(k)(11): 33 years <br /> Tank Construction: <br /> Shape: Rectangular <br /> Orientation: 191(g)(1)/192(k)(1) Horizontal <br /> Location (above/below ground): Above Ground <br /> Material of construction: 191(g (2)(A)/192(k)(2)(A) <br /> ASTM A-36 Carbon steel <br /> Thickness and method used todetermine: 191(g)(2)(B)/192(k)(2)(B) <br /> Wall Thickness: 0.1196 ' (11 gauge) <br /> Measured with a Dwyer Ultrasonic Thickness Gauge <br /> Model UTG, S/N N757016. <br /> Lining material &thickness (if pplicable): None <br /> Corrosion Protection equipmen': 191(g)(5)/192(k)(5) <br /> External protection is provided by primer and enamel coating <br /> applied to sandblast prepped surfaces. The interior does not <br /> require a protective coating due to the nature of the contents. <br /> Spill Prevention: 191(g)(5)/192( I0) <br /> The tank is equipped with a JB 007 high level prevention system <br /> which senses the tank level and shuts off the air supply <br /> to the fill pump when the level exceeds the working capacity. <br /> Lodi Honda 2 Title 22 Waste Oil Assessment <br />