Laserfiche WebLink
Seismic/Anchoring: <br /> Civil engineer wet stamped seisriic/dynamic/hydrostatic load calculations provided <br /> as Attachment"D". The tank wrll not slide or overturn during a seismic event. <br /> F <br /> ic/Anchoring findings: The to as designed and operated, and the contain which it is located are adequately anchored and are seismically sound. <br /> s: K(3 <br /> Leak Test: 191(g)(9)/192(k)(10) <br /> The waste oil storage ta�ilc and ancillary equipment were sealed and <br /> subjected to a slight positive pressure. A bubble test was performed on all <br /> tank seams and connections with no indication of leakage and good <br /> pressure retention. The 3econdary containment space was completely <br /> empty. <br /> rIntegrity testing findings: Based on t e above noted integrity test and the results <br /> ned from that test,the tank has su ficient integrity for its intended use. <br /> ls: Ie15 <br /> Tank Drawing: 19l(g)(2)(E)/l92(k)(2)(E)) <br /> Tank and fittings: See Attachment`B" <br /> Tank Dimensions (primary storage): <br /> 3.75' wide x 3.75' deep x 4.92' tall <br /> Tank Height: <br /> Overall: 5.29' <br /> Tank Gross Capacity (Volume) 500 gallons <br /> Lodi Honda 5 Title 22 Waste Oil Assessment <br />