Laserfiche WebLink
Visual inspection of containment area: 66264.193(e)(2) <br /> The secondary containment sh 11 is in fair condition with no evidence of damage, <br /> cracks or leakage. <br /> The secondary containment was completely empty at time of inspection. <br /> Secondary Containment findings: The secondary containment system is of <br /> sufficient capacity and condition for tf e containment of releases from all tanks and <br /> ancillary equipment. Initials: Kia <br /> Section 2 —Used Coolant Storage <br /> Tank Assessment Page: <br /> Tank Name/marking: <br /> Used Coolant Storage 1 ank <br /> U/L S/N 489775 <br /> Tank age: 191(g)(3)/192(k)(3): 17 years <br /> Remaining service life: 191(g)(10)/192(k)(11): 33 years <br /> Tank Construction: <br /> Shape: Rectangular <br /> Orientation: 191(g)(1)/192(k)(1 Horizontal <br /> Location (above/below ground) Above Ground <br /> Material of construction: 191(g)(2)(A)/I92(k)(2)(A) <br /> ASTM A-36 Carbon St el <br /> Thickness and method used todetermine: 191(g)(2)(B)/192(k)(2)(B) <br /> Wall Thickness: 0.1196' (11 gauge) <br /> Measured with a Dwyer(Ultrasonic Thickness Gauge <br /> Model UTG, S/N N757016. <br /> Lodi Honda 7 Title 22 Waste Oil Assessment <br />