Laserfiche WebLink
The secondary containment capacity of 286 gallons will contain 100% of the tank <br /> capacity and ancillary equipment. This meets the requirement specified in <br /> 22CCx66265.1920)(1). <br /> Visual inspection of containment area: 66264.193(e)(2) <br /> The secondary containment sh ll is in fair condition with no evidence of damage, <br /> cracks or leakage. There are several minor areas of missing paint. These areas are <br /> coated with a mist of oil and will not corrode. <br /> The secondary containment was completely empty at time of inspection. <br /> Secondary Containment findings: The secondary containment system is of <br /> sufficient capacity and condition for the containment of releases from all tanks and <br /> ancillary equipment. Initials: IC 13 <br /> Initial Discrepancies and Corrections I aken: <br /> Discrepancy: None <br /> Correction Taken: None <br /> Attachments <br /> Attachment"A" System Elevat on and Plan View <br /> Attachment`B" Waste Oil Storage Tank <br /> Attachment "C"Used Coolant Storage tank <br /> Attachment"D" Seismic/dyn is/hydrostatic Load Calculations <br /> Lodi Honda 12 Title 22 Waste Oil Assessment <br />