Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for MARCH AND BIANCHI CHEVRON as of August 16 , 2022 . <br /> Open violations from November 30, 2021 inspection <br /> Violation #304 - Failure to construct, operate , and maintain primary containment as product-tight. <br /> OBSERVATION: Little amounts of oil was observed in under dispenser containment sump ( UDCs) 7/8 , 9/ 10 and <br /> 11/ 12 indicating a leak in the primary containment. <br /> REGULATION GUIDANCE: All primary containment for the UST system must be product tight. <br /> CORRECTIVE ACTION : Immediately have a properly licensed , trained , and certified contractor repair or replace the <br /> failed component(s) , under permit and inspection of the EHD if necessary . <br /> ❑ This violation was corrected ❑ This violation will be corrected by ( date) : <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> Violation #315 - Failure to maintain interstitial space to detect leaks before release to environment ( post-Jul <br /> 2004 ) . <br /> OBSERVATION The diesel smart sensor failed when tested . <br /> REGULATION GUIDANCE: The interstitial space of the UST shall be maintained , as designed , under constant <br /> vacuum or pressure such that a breach in the primary or secondary containment is detected before the hazardous <br /> substance is released into the environment. <br /> CORRECTIVE ACTION : Correct immediately by having a properly licensed , trained , and certified contractor replace <br /> the failed component with a functional component ( LG 113-x listed , if applicable) , and obtain a permit within one <br /> business day from the EHD , if needed . If the failed component can ' t be replaced immediately , there is a possibility <br /> that the [GRADE] UST system may be red tagged to prevent fuel inputs . <br /> ❑ This violation was corrected ❑ This violation will be corrected by (date) : <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> Open violations from November 19, 2021 inspection <br /> Page 1 of 4 <br />