Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for MARCH AND BIANCHI CHEVRON as of August16, 2022. <br /> Open violations from November 19, 2021 inspection <br /> Violation#106 -Failure to submit and maintain a current facility plot plan/site map. <br /> OBSERVATION An accurate UST Monitoring Site Plan was not submitted <br /> -Map does not clearly identify the 87, 91, and diesel underground storage tanks <br /> REGULATION GUIDANCE: A site plan must be submitted identifying the locations where monitoring will be <br /> performed. The site plan must show the general layout of tanks and clearly identify locations of the following <br /> equipment, if installed: 1) monitoring panels; 2) in-tank liquid level probes (if used for leak detection); 3)devices <br /> monitoring tank annular spaces or vault, 4) devices monitoring product piping, 5)devices monitoring fill piping; 6) <br /> devices monitoring vent piping, 7)devices monitoring vapor recovery piping; 8)devices monitoring vent/transition <br /> sumps;9)devices monitoring under-dispenser containment; 10) line leak detectors; and 11)devices monitoring any <br /> other secondary containment areas. <br /> CORRECTIVE ACTION Immediately log into the California Environmental Reporting System (CERS)at <br /> http.//cers.calepa.ca gov/and upload a copy of the UST Monitoring Site Plan <br /> g -This violation was corrected ❑ This violation will be corrected by(date): <br /> ❑ Supporting documents included II <br /> Describe actions taken or will be taken to correct violation. OILS U_Lo (A) Aok—.( lbw <br /> Violation#110-Failure to submit the"Underground Storage Tank Statement of Understanding and <br /> Compliance Form". <br /> OBSERVATION The Underground Storage Tank Statement of Understanding and Compliance Form was not found <br /> in CERS. <br /> REGULATION GUIDANCE This form must be uploaded to the California Environmental Reporting System (CERS). <br /> CORRECTIVE ACTION Immediately log into the California Environmental Reporting System (CERS)at <br /> http//cers.calepa ca gov and upload the Underground Storage Tank Statement of Understanding and Compliance <br /> Form for this facility. <br /> This violation was corrected ❑ This violation will be corrected by (date): <br /> ❑ Supporting documents included <br /> rII <br /> Describe actions taken or will be taken to correct violation S (A-1 l <br /> Page 2 of 4 <br />