Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 8. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Tank ID (one OPE per column) 87 91 DSL <br /> Are both vent and tank riser piping �/ Yes Yes Yes Yes <br /> secondarily contained? No No No No <br /> OPE Model oPw 71so oPw 7190 oPw 71so <br /> What is the OPE response when activated? 21 Shut off �/ Shut off A Shut off Shut off <br /> (Check all that apply.) Flow Flow Flow Flow <br /> estricts []Restricts estricts Restricts <br /> Flow Flow Flow Flow <br /> Audible Audible Audible Audible <br /> Alarm Alarm Alarm Alarm <br /> Visual Visual Visual Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent piping Yes* Yes` Yes* Yes* <br /> that may interfere with the OPE operation? No No �/ No No <br /> At what level in the tank is the OPE set to <br /> activate? Inches from bottom of tank) 77 i�etl '6 s�e�� '6 i�4p <br /> What is the percent capacity of the tank at <br /> 90$ 89% 89$ <br /> which the OPE activates? <br /> Is the OPE in proper operating condition to �/ Yes �/ Yes �/ Yes Yes <br /> respond when the stored substance 71 No No No No <br /> reaches the designated regulatory level? <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results / Pass Pass Pass Pass <br /> Fail Fail Fail Fail <br /> 8. COMMENTS <br /> Describe all results marked "Fail"and each proposed remedy. <br /> * Mark here if: <br /> Flow restrictors interfere with overfill prevention and equipment repairs required. <br /> Additional copies of this page may be attached. <br /> Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s) <br /> Page 2of2 <br />