Laserfiche WebLink
UGETTLER-RYAN INC. FORM 1 GR Job # 22204658 <br /> SUMMARY OF SOURCE TEST DATA <br /> SOURCE INFORMATION FACILITY PARAMETERS <br /> GDF Name and Address GDF Representative and Title PHASE II SYSTEM TYPE <br /> Arco 7147 Vince Caluag (Check One) <br /> 1206 E. March Lane <br /> Stockton, CA 95210 GDF Phone No Balance <br /> 916-858-9907 Hirt <br /> Permit Conditions Source,GDF Vapor Recovery System Red Jacket <br /> CCVP Hasstech <br /> Healy <br /> GDF a Other <br /> A/C Manifolded? Yes No <br /> Operating Parameters <br /> Number of Nozzles Served by Tank 41 10 Number of Nozzles Served by Tank#3 <br /> Number of Nozzles Served by Tank#2 10 Number of Nozzles Served by Tank#4 <br /> Applicable Regulations: VR-203-1 and VR-204-1 VN Recommended <br /> Source Test Results and Comments <br /> Tank#: 1 2 3 4 <br /> 1. Product Grade 87 91 <br /> 2. Actual Tank Capacity,gallons 9728 9728 <br /> 3. Gasoline Volume Total 6505 8143 <br /> 4. Ullage,gallons (#2-#3) 4408 2823 2585 <br /> S. Initial Pressure, inches H2O 2.00 <br /> 6. Pressure After 1 Minute, inches H2O 2.00 <br /> 7. Pressure After 2 Minutes, inches H2O 2.01 <br /> 8. Pressure After 3 Minutes, inches H2O 2.03 <br /> 9. Pressure After 4 Minutes, inches H2O 2.04 <br /> 10, Final Pressure After 5 Minutes, inches H2O 2.04 <br /> 11. Allowable Final Pressure 1.68 <br /> Test Conducted by: Test Company: Date of Test: <br /> Darnell Smith Gettler-Ryan Inc. 10/27/2022 <br /> California Air Resource Board March 17, 1999 <br /> TP-201.3, Page 14 <br />