Laserfiche WebLink
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ARCO AMPM 2056 CRESTWOOD AVE, MANTECA June 27, 2022 <br /> Single-Walled Non-Pressurized Piping <br /> 404 CCR 2643(e),2661(f) Failure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair(pre-1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 104 CCR 2632(d)(1), 2634(d)Failure to have an approved UST Monitoring Plan. <br /> OBSERVATION: The monitoring plan is not current and/or not approved by the EHD. <br /> -The monitoring plan incorrectly lists VMI 99LD2000 for all three tanks, but a Veeder Root PLLD was observed on <br /> all three tanks. <br /> -The monitoring plan incorrectly lists that the 91 tank does periodic ELD testing <br /> REGULATION GUIDANCE: The monitoring plan must be uploaded to the California Environmental Reporting <br /> System (CERS). <br /> CORRECTIVE ACTION: Immediately log into CERS, make the necessary changes, and submit for review by the <br /> EHD. <br /> This is a minor violation. <br /> 107 HSC 25292.2; CCR 2711(a)(11)Failure to submit and maintain complete and current financial responsibility <br /> documents. <br /> OBSERVATION: Financial responsibility documents have not been submitted to the EHD. The most recent <br /> Certificate of Financial Responsibility uploaded in CERS is dated 6/5/2021 but the most recent document observed <br /> on site was dated 8/5/2021. The forms have also not been re-signed. The Certificate of Financial Responsibility <br /> have dates that have been whited out. <br /> REGULATION GUIDANCE: Current financial responsibility documents are required to be submitted annually. <br /> CORRECTIVE ACTION: Immediately log into the California Environmental Reporting System (CERS)at <br /> http://cers.calepa.ca.gov/, and obtain new dates and signatures, upload the required documents. <br /> This is a repeat violation, Class ll. <br /> 115 CCR 2638(c), 2638(d) Failure to submit"Monitoring System Certification Form"within 30 days of completion of the <br /> test. <br /> OBSERVATION:Annual monitoring system certification and leak detector testing was performed on 6/30/2021 and <br /> a test report was submitted on 9/2/2021, 33 days late. <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the tests. <br /> CORRECTIVE ACTION: Take all necessary precautions to ensure testing and submittal of test reports are <br /> performed in a timely manner. <br /> This is a minor violation. <br /> FA0024277 PR0542283 SCO01 06/27/2022 <br /> EHD 23-01 Rev.12/06/2021 Page 4 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />