Laserfiche WebLink
S A N J Q Q Q U IN Environmental Health Department <br /> C O U N T Y Time In: <br /> Time Out: <br /> Greorness grows here. <br /> Underground Storage Tank Program Service Request Inspection Report <br /> Name of Facility: AISLE 1 #2356 Date: 10/07/2022 <br /> Address: 4219 E MORADA LN , STOCKTON 95212 <br /> Requestor: MARTY WEITHMAN, SERVICE STATION SYSTEMS INC Telephone: (408)213-6038 <br /> Program Element: 2308-UST RETROFIT Request#: SR0085607 <br /> Inspection Type: 298-UST RETROFIT REPAIR INSPECTION <br /> Onsite Service Technician: Steven White ICC Service Tech/Installer Exp. Date: 06/17/2024 <br /> Manufacturer training: FF, 04/05/24 <br /> OVERALL INSPECTION NOTES AND COMMENTS <br /> NOTES <br /> On site to witness overfill prevention of the 87, 91 and Diesel drop tubes. <br /> Verified flapper functionality. <br /> Verified shut off at<95% using Xerxes tank charts. <br /> Verified the presence of ball floats. Ball floats were removed on site. <br /> Facility is approved to receive fuel in the 87, 91 and diesel tanks. <br /> The person in charge is responsible for ensuring that the above mentioned facility is in compliance with all applicable sections of the California Health and <br /> Safety Code.If a reinspection is required,fees will be assessed at the current hourly rate. <br /> Received by: Name and Title: Emailed to Marty Weithman, Contrac <br /> EH Specialist: GABRIELA GARCIA-MEJIA Phone: (209)616-3037 <br /> FA0016523 SR0085607 SC298 10/07/2022 <br /> EHD 23-01 Rev.09/16/2020 Page 1 of 1 Underground Storage Tank Program Service Request Inspection Report <br />