Laserfiche WebLink
LDT 5000 Field Test Apparatus <br /> ,#�o Tanknology Line Leak Detector Test Page 1 of 1 <br /> Work Order: 2356783 Date: 7/18/2022 <br /> Site Name/ID: Fed Ex Ground/953 <br /> Address: 5655 Hood Way <br /> City: Tracy State: CA Zip: 95377 <br /> Tank ID DIESEL 1 NORTH <br /> Product Diesel <br /> Product Line 1 <br /> Tested From 8 <br /> Existing/New Existing <br /> Mechanical/Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD <br /> Serial No. Nr <br /> Pump Operating Pressure(psi) 40.00 <br /> Calibrated Leak(ml/min) 189.0 <br /> Calibrated Leak(gph) 3.00 <br /> Holding PSI <br /> N/A for Electronic LD's <br /> Resiliency(ml) <br /> *NIA for Electronic LD's <br /> Metering PSI <br /> N/A for Electronic LD's <br /> Opening Time(sec) <br /> *N/A for Electronic LD's <br /> Test Results Pass <br /> Technician Comments: <br /> Technician Name: Brent Bowen Certification#: 99937 <br /> Technician Signature: Expire Date: 10/2/2022 <br /> Environmental Compliance for Petroleum Systems <br /> 02022 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />