Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2356828 Date: 9/22/2022 <br /> Site Name/ID. 7-ELEVEN 41187/41187 <br /> Address: 1829 N Wilson Way <br /> City: Stockton State: CA Zip: 95204 <br /> Tank ID 87 Pul Dsl <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 12 12 12 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. U.R. U.R. U.R. <br /> Pump Operating Pressure(psi) 30.00 29.00 32.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 30.00 31.00 36.00 <br /> NIA for Electronic Lo's <br /> Resiliency(ml) 250.00 155.00 100.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 14 15 18 <br /> NIA for Electronic Lo's <br /> Opening Time(sec) 2 5 4 <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: Expire Date: 11/7/2024 <br /> Environmental Compliance for Petroleum Systems <br /> @2022 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />