Laserfiche WebLink
SAN J 0 A Q I I I Irl Environmental Health Department <br /> C o u N T AMENDED <br /> 6/22/2022 <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> J &L MARKET 8115 S EL DORADO ST, FRENCH CAMP May 23, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 620 CFR 112.7(f)(1) Failed to train personnel on all discharge prevention details listed in this section. <br /> OBSERVATION: It appears that the oil handling personnel were not adequately trained, as required.A leak was <br /> observed in the 10,000 gallon diesel aboveground storage tank during the inspection. Owner Karina Valdez was <br /> unsure on the steps to take to handle the release. Did not observe adequate training for Karina,the oil-handling <br /> personnel, regarding the following: <br /> -Discharge procedure protocols <br /> -The contents of the SPCC Plan. <br /> REGULATION GUIDANCE: (f)(1)At a minimum,train your oil-handling personnel in the operation and maintenance <br /> of equipment to prevent discharges; discharge procedure protocols; applicable pollution control laws, rules, and <br /> regulations; general facility operations; and,the contents of the facility SPCC Plan. <br /> CORRECTIVE ACTION: Immediately provide adequate training to all oil handling personnel and submit a copy of <br /> the training log and training content to the EHD. <br /> This is a Class II violation. <br /> 705 CFR 112.8(c)(1)Container not compatible with oil stored and/or storage conditions. <br /> OBSERVATION: Failed to use containers with material and construction compatible with material stored and <br /> conditions of storage such as pressure and temperature. The 10,000 gallon aboveground tank was observed <br /> leaking diesel fuel during the inspection from a hole in the tank. The tank is not compatible or adequate to store the <br /> product. <br /> REGULATION GUIDANCE: (c)(1)Not use a container for the storage of oil unless its material and construction are <br /> compatible with the material stored and conditions of storage such as pressure and temperature. <br /> CORRECTIVE ACTION: Immediately remove all oil stored in non-compatible containers. Store oil in containers with <br /> material and construction compatible with the material stored and conditions of storage such as pressure and <br /> temperature. Obtain properly constructed tanks that are third-party listed for use as Aboveground Storage of <br /> Combustible or Flammable Liquids. Ensure that the SPCC plan is adequate for the facility. Submit proof of <br /> correction to the EHD. <br /> This is a Class II violation. <br /> FA0000110 PR0516364 SCO01 05/23/2022 <br /> EHD 28-01 Rev.12/06/2021 Page 7 of 10 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />