Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> C C U N T AMENDED <br /> 6/22/2022 <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> J &L MARKET 8115 S EL DORADO ST, FRENCH CAMP May 23, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 713 CFR 112.7(e), 112.8(c)(6) Failed to test or inspect each container for integrity based on industry standards. <br /> OBSERVATION: Per Owner Karina Valdez,testing/inspections have not been conducted on the 10,000 gallon <br /> aboveground diesel tank for integrity based on industry standards. <br /> REGULATION GUIDANCE: REGULATION GUIDANCE: 112.8(c)(6)Test or inspect each aboveground container <br /> for integrity on a regular schedule and whenever you make material repairs.You must determine, in accordance <br /> with industry standards,the appropriate qualifications for personnel performing tests and inspections,the frequency <br /> and type of testing and inspections,which take into account container size, configuration, and design (such as <br /> containers that are: shop-built,field-erected, skid-mounted, elevated, equipped with a liner, double-walled, or <br /> partially buried). Examples of these integrity tests include, but are not limited to: visual inspection, hydrostatic <br /> testing, radiographic testing, ultrasonic testing, acoustic emissions testing, or other systems of non-destructive <br /> testing.You must keep comparison records and you must also inspect the container's supports and foundations. In <br /> addition, you must frequently inspect the outside of the container for signs of deterioration,discharges,or <br /> accumulation of oil inside diked areas. Records of inspections and tests kept under usual and customary business <br /> practices satisfy the recordkeeping requirements of this paragraph. <br /> 112.7(e) Inspections,tests, and records. Conduct inspections and tests required by this part in accordance with <br /> written procedures that you or the certifying engineer develop for the facility. You must keep these written <br /> procedures and a record of the inspections and tests, signed by the appropriate supervisor or inspector,with the <br /> SPCC Plan for a period of three years. Records of inspections and tests kept under usual and customary business <br /> practices will suffice for purposes of this paragraph. <br /> CORRECTIVE ACTION: Immediately conduct the necessary integrity testing and inspections on the 10,000 gallon <br /> aboveground storage tank based on industry standards, on a regular schedule. Maintain testing and inspection <br /> records. Submit a copy of the test/inspection results to the EHD. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> An inspection checklist was provided to the facility operator on May 24, 2022. The checklist was amended. <br /> Violation 102 was removed and violations 103, 110, 112, 202, 619, 620, 705, 706, and 713 were added. <br /> A complete report was finished on June 22, 2022 and replaces the initial checklist. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by July 22, 2022. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($152). To schedule an appointment, please call (209)468-3420. <br /> The following was observed during this inspection: one 10,000 gallon diesel tank <br /> The following was provided during this inspection: Schedule of free CUPA classes, SP001 monthly and annual <br /> FA0000110 PR0516364 SCO01 05/23/2022 <br /> EHD 28-01 Rev.12/06/2021 Page 9 of 10 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />