Laserfiche WebLink
## KEY NOTES <br /> Z <br /> w <br /> 0 <br /> U <br /> �1 ELECTRICAL CONDUIT(S)TO ENTER SUMP 2" MIN U <br /> ABOVE HIGHEST PRODUCT PENETRATION. w <br /> U <br /> �2 LOCATE ELECTRICAL JUNCTION BOX IN UPWARDp Q <br /> POSITION AT HIGHEST LOCATION IN SUMP RISER n a <br /> FOR EASY ACCESS FROM ABOVE. <br /> c U <br /> �3 SUMP SENSOR TO REST AT LOWEST POINT OF p <br /> SUMP ENCLOSURE ON PRODUCT PIPING SIDE OF w <br /> a <br /> SUMP. TANK CONTRACTOR TO SUPPLY ALL j <br /> BRACKETS AND CLAMPS FOR 2-POINT MOUNTING w <br /> OF THE 2" FRP SLEEVE. <br /> N <br /> ® SET MANHOLE COVERS 1"ABOVE THE FINISHM N <br /> GRADE AND SLOPE CONCRETE AWAY FROM 0 <br /> co <br /> MANWAY COVERS AT 2% GRADE. C) <br /> POSITION BALL VALVE FOR UNOBSTRUCTED USE <br /> OF SHUT-OFF HANDLE. <br /> © STP POWER CONDUITS MUST BE RUN IN Proto 12-01-2020 <br /> SEPARATE RACEWAY. ENTIRE WIRING RUN MUST <br /> BE IN RIGID PVC COATED GALVANIZED STEEL <br /> CONDUIT. USE ONLY ROB ROY CONDUIT TYPES <br /> "PERMA-COAT", "PLASTI-BOND" OR"KORKAP", NO <br /> PVC OR RNC CONDUIT ALLOWED. <br /> co <br /> ❑7 USE ONLY ROB ROY CONDUIT TYPES co <br /> "PERMA-COAT", "PLASTI-BOND" OR"KORKAP" o <br /> ELECTRICAL CONDUITS AT FIBERGLASS TANK <br /> SUMPS OR WHERE BRAVO F-17-RR OR F-10-RR (n <br /> ENTRY FITTINGS ARE CALLED OUT. X <br /> MAINTAIN 8"TO 10" CLR U Lu LoJ J <br /> FROM TOP OF MANHOLE COVER MAINTAIN 8"TO 10" CLR <br /> 19 TO TOP OF WT COVER 19 Z r 00 r <br /> FROM TOP OF MANHOLE COVER Z Q <br /> 4 WATERTIGHT COVER WITH 4 TO TOP OF WT COVER * U Lo W <br /> OBSERVATION PORT WATERTIGHT COVER WITH of Q m 0 <br /> 20 <br /> ALIGN PORT WITH ATG 20 OBSERVATION PORT z Q Q O <br /> CONCRETE TANK SLAB ° a ° ALIGN PORT WITH ATG W z U W <br /> CONCRETE TANK SLAB TRIM MH SKIRT TO MAINTAIN 2"TO 4" ° a ° > Q W <br /> 01 0 ° ° BETWEEN SUMP SECURE FOAM PIPE 01 TRIM MH SKIRT TO MAINTAIN � \\ U U) J <br /> ° e 10 2"TO 4" BETWEEN SUMP W / O (n (� <br /> 11 e INSULATION TO BOTTOM OF MH SKIRT. a <br /> p a SECURE FOAM PIPE INSULATION J � w Z � Y z <br /> ° ADD INSULATION AS REQUIRED TO 2 ° a <br /> 2 ° PREVENT CONCRETE FROM BEING TO BOTTOM OF MH SKIRT w W W M Q U) <br /> EXPLOSION PROOF 2 EXPLOSION PROOF J-BOX <br /> EXPLOSION PROOF o POURED ON SEALED MANHOLE J-BOX TYP (POWER) I" m co <br /> J-BOX TYP (POWER) (FOR SENSORS) Y U) <br /> 2 EXPLOSION PROOF J-BOX ELEC SEAL-OFF— <br /> ELEC SEAL-OFF (FOR SENSORS) 5 30 E 2 <br /> 5 30 m m E m m 2" SCHED 40 GALV PIPE FITTINGS p <br /> CONDUIT AND LBY'S TO 6 FOR REGULAR AND PREMIUM C) <br /> CONDUIT AND LBY'S TO 6 ELEC SEAL-OFF STP POWER CONNECTION BY GC M <br /> STP POWER CONNECTION -----E]CONDUIT FROM ANNULAR SPACE CONDUIT FROM ELEC ROOM 6 ELEC SEAL-OFF <br /> CONDUIT FROM ELEC 6 MANHOLE FOR SENSORS FOR STP POWER <br /> 1 7 6 1 7 CONDUIT FROM ANNULAR SPACE <br /> ROOM FOR STP POWER MANHOLE FOR SENSORS <br /> FUEL PLUMBING TREE XERXES DW SUMP SUPPLIED- <br /> ------ <br /> 1 REF 5-G4.1 w/TANKS (TYP) 1 7 <br /> QO 06 FUEL PIPING TREE <br /> 2" SCHED 40 BLACK IRON G0 Q0 REF 5-G4.1 <br /> PIPE FITTINGS FOR 2" SCHED 40 GALVANIZED 06 <br /> DIESEL BY GC SUMP SENSOR BRACKET PIPE FITTINGS FOR REGULAR W <br /> U-BOLTED TO ATG RISER (2 LOC) AND PREMIUM BY GC GO <br /> 2" FRP X 33" LONG MIN 03 PIPE CLAMPS, SENSOR BRACKETS 2" FRP X 33" LONG MIN 03 SUMP SENSOR BRACKET <br /> (BEYOND) FOR SUMP SENSOR AND U-BOLTS BY GC (BEYOND) FOR SUMP SENSOR U-BOLTED TO ATG RISER (2 LOC) <br /> HOUSING 1"CLR FROM TANK HOUSING 1"CLR FROM TANK PIPE CLAMPS, SENSOR BRACKETS <br /> 0505 AND U-BOLTS BY GC W <br /> 3 3 <br /> 58 58 > o 8 >o <br /> 16 55 ° � moos w <br /> 11 10 c a C) E w <br /> STRIKE PLATES STRIKE PLATES 2' co ° <br /> co <br /> BY TANK MFR c 'o � � ° ~ <br /> BY TANK MFR ° � 'O � � <br /> Q o E o <br /> � � �� oE C7 <br /> z v 3 Q ° ° <br /> O ^ c E ° J <br /> rl N Q °¢O Q <br /> 0 <br /> N <br /> co <br /> SECTION SECTION <br /> � � U <br /> 0 co <br /> co <br /> ROTATE VIEW AS REQUIRED FOR FIELD CONDITION ROTATE VIEW AS REQUIRED FOR FIELD CONDITION NOTE: <br /> NOTE: VACUUM KIT(NOT SHOWN) ca <br /> VACUUM KIT(NOT SHOWN) TO BE MOUNTED TO ATG RISER. — a <br /> ELECTRICAL PENETRATIONS INTO SUMP ARE SHOWN FOR TO BE MOUNTED TO ATG RISER. ELECTRICAL PENETRATIONS INTO SUMP ARE SHOWN FOR REF SHEET G12.2 ~ <br /> REFERENCE ONLY-COORDINATE LOCATIONS WITH REF SHEET G12.2 TYP 03 REFERENCE ONLY-COORDINATE LOCATIONS WITH FOR VACUUM ZONES AND DETAILS. O <br /> 03 SHEET G9 AND FIELD CONDITIONS FOR VACUUM ZONES AND DETAILS. SHEET G9 AND FIELD CONDITIONS <br /> 02 TYP 02 <br /> 11 MINIMUM 4'-0"STRAIGHT RUN OF TYP 11 MINIMUM 4'-0"STRAIGHT RUN OF 00 0 O U) <br /> PIPING PRIOR TO FIRST CHANGE PIPING PRIOR TO FIRST CHANGE 04 O <br /> 06 OF DIRECTION FITTING TYP 06 OF DIRECTION FITTING W Z <br /> 03 03 2" FRP X 33" LONG MIN03 2" FRP X 33" LONG MIN (n U <br /> (BEYOND) FOR SUMP SENSOR TYP 03 (BEYOND) FOR SUMP SENSOR Q m <br /> 160 0 HOUSING 1"CLR FROM TANK TYP 16 0 0 HOUSING 1" CLR FROM TANK m <br /> 0 0 0 0 N <br /> 0 0 05 G0 0 0 05 U <br /> 3 3 <br /> G01 10 p U <br /> S1 DESICCANT BAG W/HANGER S1 DESICCANT BAG W/HANGER (n 0 0 U <br /> FUEL PIPING TREE <br /> FUEL PLUMBING TREE (2) PER SUMP BELOW DISCHARGE) (2) PER SUMP I I m , Z <br /> BELOW DISCHARGE o o ( ° ° Z o o <br /> ( ) o SUMP SENSOR BRACKET Z o o <br /> REF 5-G4.1 ° SUMP SENSOR BRACKET REF 5-G4.1 <br /> ° U-BOLTED TO ATG RISER (2 LOC) ° U-BOLTED TO ATG RISER (2 LOC) o ¢ a z z <br /> CONDUIT AND LBY'S TO 6 0 o PIPE CLAMPS, SENSOR BRACKETS CONDUIT AND LBY'S TOE----. 0 o PIPE CLAMPS, SENSOR BRACKETS W a 4 W a <br /> STP POWER CONNECTION ° AND U-BOLTS BY GC ° o o <br /> � ° ° STP POWER CONNECTION ° O AND U-BOLTS BY GC <br /> o <br /> N EXPLOSION PROOF 2 o s E EXPLOSION PROOF 2 ° <br /> ° Z x <br /> ---E]EXPLOSION PROOF J-BOX N N o � ¢ o a o <br /> �i J-BOX(FOR STP POWER) ° J-BOX(FOR STP POWER) o <br /> 7 1 S12 0 <br /> ------E]EP J-BOX TYP (SENSORS) 7 1 S12 ° (FOR SENSORS) <br /> Z V V Cn <br /> CD <br /> N o o <br /> S12 1 7 <br /> CONDUIT FROM ELEC 6 0 o CONDUIT FROM ELEC ROOM 6 o <br /> N <br /> ., ROOM FOR STP POWER FOR STP POWER <br /> 7 CONDUIT FROM ANNULAR SPACEW <br /> MANHOLE FOR SENSORS <br /> N V ~ r <br /> 7 CONDUIT FROM ANNULAR SPACE o ``' ¢ W � o o o <br /> MANHOLE FOR SENSORS o <br /> 75 <br /> RS o a Z = o <br /> 0 0 0 0 <br /> 0 <br /> 0 0 <br /> Z 0 0 0 0 <br /> XERXES 42" EIGHT SIDED DW 5 ? v `,t✓ <br /> SUMP-SUPPLIED w/TANK(TYP) 0 0- XERXES 42" EIGHT SIDED DW Q FFL <br /> L <br /> SUMP-SUPPLIED w/TANK(TYP) + C3 <br /> 04 <br /> REF SECTION <br /> REF SECTION u ; <br /> o PLAN PLAN <br /> Y <br /> Z <br /> N � <br /> SHEET: <br /> mZ D ESE STP SUMP DETA � S REGULAR AND PREMIUM STP SUMP DETAILSG4 . 0cz:jc-D <br /> FUELING - USA CA <br />