Laserfiche WebLink
5. Deficiency Title: ATG Fuel Level Incorrect <br />Facility/Location: <br />AAFES Distribution Center <br />Facility Tank No.: <br />AST 3 <br />Tank Type/Size: <br />DW AST / 12,000 -gallons { <br />Fuel Grade: <br />Diesel <br />7 <br />Description of <br />Have certified Veeder Root technician adjust liquid level on <br />Repairs/Scope of Work: <br />ATG system. <br />Project Regumirement: <br />STI SP001 Section 7.1.9.3 <br />The AST was manually measured to verify the liquid level <br />Current Situation: <br />gauge matched the level in the tank. The liquid level <br />gauge was correct; however, the Veeder Root 350 <br />Automatic Tank Gauge (ATG) system was off 1.5". <br />Tank may be overfilled if fuel is ordered based off <br />the ATG system. <br />Remarks/Special None. <br />Considerations: <br />91 Page <br />