Laserfiche WebLink
Item <br />Code Reference <br />Finding <br />Recommendation <br />Unit <br />Qty <br />3. <br />NFPA 30 Section <br />The AST is not equipped with <br />Place signage on all approachable sides <br />EA <br />4 <br />21.7.2.1; NFPA 704 <br />NFPA 704 signs that can be <br />of the tank. <br />seen from all approachable <br />sides. <br />4. <br />STI SP001 Section <br />The Convault concrete casing is <br />Cracks should be repaired, and <br />LF <br />15 <br />7.8.3 <br />porous and cracked in areas, <br />concrete sealed in accordance with <br />with evidence of water seeping <br />manufacturer recommendations. <br />through cracks on several areas <br />CONVAULT tanks must be evaluated <br />of the tank. There is also an <br />and repaired in accordance with the <br />area on top of the tank that was <br />manufacturer's recommendations. <br />drilled, and studs installed. <br />5. <br />STI SP001 Section <br />The AST was manually <br />Reprogram the ATG system to match <br />EA <br />1 <br />7.1.9.3 <br />measured to verify the liquid <br />the liquid level in the tank. <br />level gauge matched the level <br />in the tank. The liquid level <br />gauge was correct; however, <br />the Veeder Root 350 <br />Automatic Tank Gauge (ATG) <br />system was off 1.5". <br />6. <br />NFPA 30 Section <br />The tank is not grounded. <br />Install a grounding rod near the tank <br />EA <br />1 <br />6.5.4.2 <br />and connect the tank to the ground. <br />7. <br />OSHA Title 8, <br />The fuel emergency stop is a <br />Install a panic -type push button <br />EA <br />1 <br />subchapter <br />circuit breaker; it should be a <br />emergency fuel shutoff switch. <br />7.20.144.5572 <br />panic -type push button. <br />8. <br />NFPA 30 Section <br />The fuel dispenser emergency <br />Install a new emergency breakaway <br />EA <br />2 <br />6.9.2 <br />breakaway coupling is leaking on <br />coupler on both dispensers. <br />the dispenser next to the scale. <br />9. <br />NFPA 30 Section <br />The dispensing pump located on <br />Have a certified fuel system repair <br />EA <br />4 <br />6.9.2 <br />top of the AST is leaking at <br />technician evaluate and repair the <br />several locations. <br />dispensing pump. <br />Notes: <br />AST <br />ATG <br />NFPA <br />OSHA <br />= aboveground storage tank <br />= automatic tank gauge <br />= Nation Fire Protection Association <br />= Occupational Safety and Health Administration <br />• - <br />