My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
SR0085076_OWTS
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
A
>
AHERN
>
29700
>
4200 – Liquid Waste Program
>
SR0085076_OWTS
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
9/30/2022 4:13:58 PM
Creation date
9/29/2022 9:09:49 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
4200 – Liquid Waste Program
FileName_PostFix
OWTS
RECORD_ID
SR0085076
PE
4201
FACILITY_NAME
AHERN TRUCK STOP
STREET_NUMBER
29700
Direction
S
STREET_NAME
AHERN
STREET_TYPE
RD
City
TRACY
Zip
95304
APN
25502014
ENTERED_DATE
3/29/2022 12:00:00 AM
SITE_LOCATION
29700 S AHERN RD
P_LOCATION
99
P_DISTRICT
005
QC Status
Approved
Scanner
SJGOV\tsok
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
207
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
28 <br /> Paul W. Donoho, R.E.H.S. #6227 <br /> (530) 701-9972 <br /> d _ oO&M <br /> COMMERCIAL - <br /> Maintenance • • <br /> 4.Splice the float wires to the wires from the control panel following 3.Remove the inoperative pump and replace it with a new one of the <br /> the wiring schematics provided in Appendix F.Attach the common same type,Push the pump cable through the watertight card grip <br /> wire with the other commons using the waterproof wire nut.It may into the electrical splice box.Leave an adequate length of electrical <br /> be necessary to replace this wire nut with a new watertight wire cord coiled inside the riser to allow for easy removal of the pump. <br /> nut.Always use watertight wire nuts or heat shrink splice kits for all Tighten the cord grip by hand,not by tool;then test the tightness <br /> connections! of the cord grip by tugging on the cord.A cable is secure when the <br /> 5.Replace the float in the collar,using the same tether length,and cord grip is tight enough to prevent slippage.An adequate length of <br /> return the assembly to the pump vault. cord should be left within the splice box to allow for easy removal for <br /> future disconnecting and re-splicing. <br /> 6.Reconnect power and test the unit per the instructions provided in <br /> the"Start-up&Operation"section of this manual. 4.5plice the pump wires to the appropriate wires from the control <br /> panel following the wiring schematics provided in Appendix F.Always <br /> Removing&Replacing Inoperative Pumps use watertight wire nuts or heat shrink splice kits for all connections! <br /> IMPORTANT!Before doing any work on either the wiring to the 5.Reattach the discharge plumbing assembly and carefully lower the <br /> level contral floats and pump or inside the control panel,switch off pump into the flow inducer alongside the Biotuh&pump vault.Be <br /> the power to the system at the service entrance panel and set the careful not to lower the pump by the cable or to pinch the cable <br /> circuit breakers in the panel to their-OFF""positions. when lowering it into the flow inducer.Reconnect the union and open <br /> the ball valve, <br /> 1.Close the ball valve on the discharge plumbing assembly,disconnect <br /> Me union,and carefully remove the pump and attached plumbing 6.Reconnect power and test the unit per the instructions provided in <br /> from the tank.Disconnect the pump from the discharge plumbing the"Start-up&Operation"section of this manual. <br /> assembly. <br /> 2.Remove the stainless steel screws from the splice box lid,being <br /> careful not to drop the screws into the tank. If the splice box was <br /> submerged,or 4 there is a crack in the conduit,there may be water <br /> in the splice box.If this is the case,remove the water with a baster, <br /> sponge,or other appropriate method.Loosen the cord grip at the <br /> splice box and identify the appropriate splice for the pump.Cut out <br /> the splices and label the wires. <br /> AIM-OM-qTx-3,aev.�2.1,05115 •�Copyright Orencd Systems®,Inc�Property of Orenco Systems®,Inc.Do not reproduce or dlsVlhute without written au3horiz8fion from erencm 500-348-9843 <br />
The URL can be used to link to this page
Your browser does not support the video tag.