REVISIONS <br /> CALIFORNIA RETAIL FOOD CODE GENERAL NOTES LUMINAIRE SCHEDULE ELECTRICAL POWER SYMBOLS 1 BLDGREV1 12/31/21 <br /> ARTICLE 2. LIGHTING 1. THESE DRAWINGS ARE NOT TO BE USED FOR CONSTRUCTION ID MANUFACTURER OUTPUT VOLTAGE INPUTV.A DRIVERS HOUSING MOUNTING REMARKS I-Q DUPLEX RECEPTACLE, NEMA 5-15R, +18" UON <br /> 114252. UNLESS APPROVED BY THE BUILDING DEPARTMENT. TO LED � DOUBLE DUPLEX RECEPTACLE, NEMA 5-15R, +18" UON <br /> 2. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY, AND NOT A OBE SELECTED BY 2800 Lumens 120-277 28 0-10V STEEL PENDANT @ LED PENDANT LIGHTS k� SWITCHED DUPLEX RECEPTACLE OCCUPANCY SENSOR <br /> IN EVERY ROOM AND AREA IN WHICH ANY FOOD IS PREPARED OWNER 9'AFF <br /> MANUFACTURED, PROCESSED, OR IN WHICH INTENDED TO SHOW ROUTING OF CABLES AND CONDUITS WHICH 80CRI 3500°K CONTROLLED NEMA 5-15R +18" UON <br /> OR PREPACKAGED, SHALL BE DETERMINED IN THE FIELD U.O.N. DEVICES ARE NOT ' <br /> EQUIPMENT OR UTENSILS ARE CLEANED, SUFFICIENT NATURAL OR ' B NOTUSED <br /> SHOWN TO SCALE AND THEREFORE CANNOT ALWAYS BE SHOWN IN I,* DOUBLE DUPLEX WITH (1) SWITCHED DUPLEX OCCUPANCY <br /> ARTIFICIAL LIGHTING SHALL BE PROVIDED TO PRODUCE THE GOTHAM LED SENSOR CONTROLLED AND 1 DUPLEX NORMAL POWER <br /> FOLLOWING LIGHT INTENSITY, WHILE THE AREA IS IN USE: THEIR EXACT LOCATION. ( ) ( °° ) OFESS/ <br /> (A) AT LEAST 10-FOOT CANDLES AT A DISTANCE OF 30 C EVO 35/156AR MD LSS 1572 Lumens 120-277 18.5 0-10V STEEL RECESSED 6 LED DOWNLIGHT WITH COMMON FINISH COVER PLATE, NEMA 5-15R, +18 UON �D eft 091 <br /> INCHES ABOVE THE FLOOR, IN WALK-IN REFRIGERATION 3. EXISTING DEVICES SHOWN WERE TAKEN FROM EXISTING DRAWINGS, MVOLT EZ10 NPS80EZ 80CRI, 3500°K ��� `MAD (� F-A <br /> UNIT, DRY FOOD STORAGE AREAS.INSIDE EQUIPMENT SUCH NOT AS BUILT DRAWINGS AND LIMITED SITE SURVEYS, AND MAY LITHONIA NOTE: CONTROLLED RECEPTACLES TURN ON AUTOMATICALLY <br /> NOT BE COMPLETELY ACCURATE. THE ELECTRICAL TRADE SHALL LED WHEN AN OCCUPANT ENTERS THE SPACE. CONTROLLED <br /> AS REACH-IN AND UNDER-COUNTER REFRIGERATORS. 2TL2-40L-FW-Al2-MVOLT- 2X2 LED TROFFER WITH nLIGHT <br /> VISIT JOB SITE AND VERIFY CONDITIONS PRIOR TO BIDDING. NOTIFY D 4000 Lumens 120-277 35 0-10V STEEL RECESSED RECEPTACLES TURN OFF 15 MINUTES AFTER OCCUPANTS <br /> (B) AT LEAST 20-FOOT CANDLES FOR THE FOLLOWING: THE ARCHITECT/OWNER OF ANY DISCREPANCIES. EZ1-LP840-N80 80CRI, 4000°K CONTROL LEAVE THE SPACE. <br /> (1) AT A SURFACE WHERE FOOD IS PROVIDED FOR OR EQUIVALENT RECEPTACLE SUBSCRIPTS: * No. 67047 <br /> CONSUMER SELF-SERVICE OR WHERE FRESH PRODUCE 4. BRANCH CIRCUITRY MAY NOT BE SHOWN FOR EXISTING DEVICES. LED Exp. 09-30-2022 <br /> OR PREPACKAGED FOODS ARE SOLD OR OFFERED THE ELECTRICAL TRADE SHALL RELOCATE EXISTING BRANCH E 1500 Lumens 120-277 15 0-10V STEEL TO BE SELECTED BY WALL @ LED GOOSE NECK DECORATIVE GFI, GFCI or G = GROUND FAULT-CIRCUIT INTERRUPTER s� �/V I\- <br /> 9TF �F�� <br /> FOR CONSUMPTION. OWNER 9'AFF FIXTURES S= SHOW WINDOW RECEPTACLES OF C NO <br /> (2) AT A DISTANCE OF 30 INCHES ABOVE THE FLOOR IN CIRCUITRY AND MAKE ALL NECESSARY RECONNECTIONS AS 80CRI, 3500°K WP- WEATHER PROOF RECEPTACLES <br /> AND <br /> AREAS USED FOR HAND WASHING WARE WASHING, REQUIRED TO FACILITATE REMODEL. VERIFY ALL WORK REQUIRED ON THE JOB AND RECORD ON RECORD DRAWINGS. LITHONIA EXIT/EMERGENCY COMBO WITH EY NON-FUSED DISCONNECT SWITCH, SIZE AS REQUIRED <br /> EQUIPMENT AND UTENSIL STORAGE, AND IN TOILET LHQM LED R HO REMOTE LED HEAD. PROVIDE a FUSED DISCONNECT SWITCH WITH TIME DELAY FUSES SIZED PER UNIT <br /> (3) AT SURFACE IN ALL FOOD PREPARATION AREAS AND 5. ALL ELECTRICAL WORK SHALL CONFORM WITH THE 2019 EDITION OF <br /> ROOMS. X OR EQUIVALENT LED 120-277 4.3 - - MIN OF 90 MINS BACKUP NAMEPLATE OR AS NOTED. DISCONNECT SHALL ACCEPT MAXIMUM <br /> ROOMS DURING PERIODS OF CLEANING. THE CALIFORNIA ELECTRICAL CODE AS WELL AS ALL LOCAL CODES DURATION. RECOMMENDED FUSE SIZE. <br /> (C) AT LEAST 50-FOOT CANDLES AT A SURFACE WHERE A FOOD & REQUIREMENTS. LITHONIA EMERGENCY FIXTURE. PROVIDE OO Q JUNCTION BOX, SIZE AND TYPE AS REQUIRED <br /> EMPLOYEE IS WORKING WITH FOOD OR WORKING WITH 6. ALL EQUIPMENT INSTALLED OR CONNECTED BY ELECTRICAL TRADE Y ELM2 LEDSD LED 120-277 6 - - - MIN OF 90 MINS BACKUP <br /> UTENSILS SHALL BE LABELED OR CERTIFIED FOR ITS USE BY A NATIONALLY DURATION. ® RELAY PACK FOR CONTROLLED RECEPACLES <br /> SAWS OR EQUIPMENT SUCH AS KNIVES, SLICERS, GRINDERS, OR RECOGNIZED TESTING LABORATORY. <br /> WHERE EMPLOYEE SAFETY IS A FACTOR. AND IN OTHER 7. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR EXACTr COMBINATION TELE/DATA OUTLET, +18" UON. RING AND STRING. <br /> AREAS LOCATIONS OF EQUIPMENT. REFER TO MECHANICAL PLUMBING AND EXISTING PANEL SCHEDULE "Al"" " <br /> AND ROOMS DURING PERIODS OF CLEANING. ' U) 7 ® EXHAUST FAN, N.I.E.S., CONNECT AS REQUIRED <br /> ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR POWER ANDZ RECESSED MOUNTED 120/208V. 3 Ph. 4W. 200 AMP BUS Z <br /> 114252.1. CONTROL REQUIREMENTS AND WIRING DIAGRAMS.. NEMA 1 200 AMP MLO ui <br /> FED FROM 200A REMOTE CIRCUIT BREAKER VERIFY kAIC 2 BRANCH CIRCUIT PANEL, SEE PANEL SCHEDULES <br /> (A) EXCEPT AS SPECIFIED IN SUBVERSION (b), LIGHT BULBS 8. WHERE ELECTRICAL CONDUIT ENTERS A WALL, CEILING OR FLOOR, ° DESCRIPTION KVA BKR CKT Ph. A Ph. B Ph. C CKT BKR KVA DESCRIPTION 0 1 o SIGNAL OR CONTROL PANEL, TYPE AS INDICATED <br /> SHALL THE OPENING AROUND THE CONDUIT SHALL BE TIGHTLY SEALED. POS #11 0.36 20-1 1 1.6 2 20-1 1.24 ICE MAKER #31.1 <br /> BE SHIELDED, COATED, OR OTHERWISE SHATTER-RESISTANT . <br /> REF PREP TABLE #2 067 20-1 3 0.9 4 20-1 0.24 SODA MACHINE #31 <br /> 9. CONDUIT INSIDE BUILDING SHALL BE EMT OR RSC. FLEXIBLE STEEL IDENTIFICATION TAG FOR EQUIPMENT PROVIDED BY M.C. <br /> IN CONDUIT MAY BE USED IN SHORT LENGTHS WHERE FLEXIBILITY IS REF PREP TABLE #2 0.67 20-1 5 1.0 6 20-1 0.36 SODA COUNTER RECEPTS CONNECT EQUIPMENT AS INDICATED OR AS REQUIRED. <br /> AREAS WHERE THERE IS NON-PREPACKAGED REQUIRED FOR MOVEMENT OR VIBRATION. MEGA TOP SANDWICH #5 0.50 20-1 7 1.4 8 20-1 0.90 DINING RECEPTS <br /> READY-TO-EAT COOK AREA RECEPTS 0.18 20-1 9 0.7 10 20-1 0.50 SHOW WINDOW RECEPTS ELECTRICAL � G H T N G SYMBOLS <br /> FOOD, CLEAN EQUIPMENT, UTENSILS, AND LINENS, OR 10. FLEXIBLE METALLIC CONDUIT MAY BE USED FOR BRANCH CIRCUITS OVEN #7 1.68 20-1 11 1.7 12 20-1 SPARE <br /> UNWRAPPED SINGLE-USE ARTICLES. COOK AREA RECEPTS 0.18 20-1 13 0.4 14 20-1 0.18 ROOF RECEPTS <br /> B SHIELDED, COATED, OR OTHERWISE SHATTER-RESISTANT WHERE METALLIC CONDUIT IS SHOWN. METAL CLAD CABLE MAY BE <br /> ( ) USED FOR BRANCH CIRCUITS WHERE CONCEALED WITHIN WALLS. COOK AREA RECEPTS 0.18 20-1 15 0.2 16 20-1 SPARE RECESSED LIGHT FIXTURE - MOUNTED IN T-BAR <br /> BULBS NEED NOT BE USED IN AREAS USED ONLY FOR SPARE 20-1 17 1820-1 SPARE <br /> STORING PREPACKAGED FOOD IN UNOPENED PACKAGES, IF 11. PROVIDE A GROUNDING CONDUCTOR IN ALL FLEXIBLE CONDUITS. KITCHEN RECEPTS 0.36 20-1 19 0.4 20 20-1 SPARE ® RECESSED DOWNLIGHT <br /> THE INTEGRITY OF THE PACKAGES CANNOT BE AFFECTED LIGHTING 0.80 20-1 21 0.8 22 20-1 SPARE LED PENDANT LIGHT <br /> BY 12. THE COMPLETE SYSTEM SHALL BE GROUNDED PER CEC ART. 250. EMERGENCY LTG 0.10 20-1 23 0.3 24 20-1 0.20 HOOD #15 <br /> BROKEN GLASS FALLING ONTO THEM AND THE PACKAGES EXIT SIGN WITH EMERGENCY LIGHT <br /> ARE CAPABLE OF BEING CLEANED OF DEBRIS FROM SIGN 0.50 20-1 25 1.6 26 20-1 1.08 HEF-1 <br /> BROKEN 13. GENERAL PURPOSE 120V LIGHTING AND RECEPTACLE CIRCUITS 2.29 27 3.4 28 20-1 1.08 OVEN #14 NOTE: LETTER INDICATES FIXTURE TYPE - SEE FIXTURE <br /> OVER 100' LONG SHALL BE #10 CU,, U.O.N. GENERAL PURPOSE (E)AC-1 2.29 30-2 29 3.4 30 20-1 1.08 OVEN #14 SCHEDULE. <br /> (C) INFRARED AND OTHER HEAT LAMPS SHALL BE PROTECTED <br /> BULBS BEFORE THE PACKAGES ARE OPENED. 277V LIGHTING CIRCUITS OVER 300 LONG SHALL BE #10 CU, SPARE 20-1 31 0.7 32 20-1 0.67 MEAT SLICER #21 <br /> N <br /> O.N.AGAINST BREAKAGE BY A SHIELD SURROUNDING AND U. SPARE 20-1 33 0.5 34 20-1 0.48 1 DOOR FREEZER #17 NOTE: SMALL LETTER INDICATES CONTROL LEG. FOR FIXTURE TYPE <br /> EXTENDING BEYOND THE BULB SO THAT ONLY THE FACE SPARE 20-1 35 0.3 36 20-1 0.28 1 DOOR REF #18 - SEE FIXTURE SCHEDULE. SHADING = EMERGENCY FIXTURE. <br /> OF 14. PROVIDE TYPEWRITTEN SCHEDULES INDICATING LOAD DESCRIPTION FOR ALL CIRCUITS IN PANELBOARDS. SPARE 20-1 37 0.5 38 20-1 0.48 2 DOOR REF #19 <br /> THE BULB IS EXPOSED, OR BY USING APPROVED COATED SPARE 20-1 39 0.2 40 20-1 1 0.18 IPREP AREA RECEPTS <br /> SHATTER RESISTANT BULBS. 15. CONTRACTOR TO PERFORM TESTING, ADJUSTMENT AND REPORTING SPARE 20-1 41 1.2 42 1 20-1 1 1.20 IGREASE TRAP 4 LOW VOLTAGE DIMMER LIGHT SWITCH, +44" UON <br /> OF LIGHTING SYSTEMS PER CGBSC SECTION 5.410.4. SUBTOTAL: 6.4 6.6 7.9 $ SINGLE POLE LIGHT SWITCH, +44" UON <br /> CONNECTED LOAD 20.91 KVA DEMAND KVA 25.9 kVA <br /> FOOD SERV CE GENERAL N0TES 16. ELECTRICAL CONDUIT MUST IMMEDIATELY PENETRATE ROOF AND 25% OF LARGEST MOTOR 1.048 KVA DEMAND CURRENT 72.0 A os OCCUPANCY SENSOR, CEILING MOUNTED <br /> RUN ALONG THE UNDERSIDE OF ROOF STRUCTURE. 25% OF CONTINUOUS LOAD 3.96 KVA <br /> 1. LIGHTING FIXTURES IN AREAS WHERE FOOD IS PREPARED OR OPEN DAYLIGHT CONTROLS, CEILING MOUNTED >_ <br /> FOOD IS STORED OF WHERE UTENSILS ARE CLEANED SHALL HAVE 17. DURING THE COURSE OF TI CONSTRUCTION THERE ARE NO SWITCH SUBCRIPTS: a, b, c, etc. = DEVICE CONTROLLED. Z <br /> A SHATTER-PROOF LENS AND ARE READILY CLEANABLE. PENETRATIONS OF ELECTRICAL LINES AT THE EXTERIOR WALLS OF <br /> THE TENANT PREMISES. EXTERIOR WALL PENETRATIONS RELATING <br /> 2. LIGHTING INTENSITY SHALL NOT BE LESS THAN 50 FOOT CANDLES TO TI WORK IS PROHIBITED. <br /> AT 30" ABOVE FLOOR IN FOOD PREPARATION AREAS. ABBREVIATIONS LIST <br /> 3. FOOD AND UTENSIL STORAGE ROOMS REFRIGERATION STORAGE 0 <br /> AND TOILET ROOMS SHALL NOT BE LESS THAN 10 FOOT CANDLES, A AMPERE PVC POLYVINYL CHLORIDE <br /> AT +30" ABOVE FLOOR. A.F.F. ABOVE FINISHED FLOOR CONDUIT V �O <br /> AL ALUMINUM (R) RELOCATED <br /> 4. ALL ELECTRICAL WORK SHALL CONFORM WITH THE CURRENT C. CONDUIT SEC. SECONDARY Z Z J ((y)EDITION OF THE CALIFORNIA ELECTRICAL CODE AND ALL STATE C.0. CONDUIT ONLY, WITH TYP. TYPICAL CO LO <br /> AND LOCAL REQUIREMENTS AND CODES. <br /> PULL LINE UG UNDERGROUND0_15. VERIFY ALL OUTLET LOCATIONS PRIOR TO ROUGH-IN. CLG CEILING UON UNLESS OTHERWISE NOTED = <br /> (E) EXISTING V VOLTS 0 U Q <br /> 6. COORDINATE DEMOLITION WORK WITH ARCHITECTURAL DRAWINGS. GND. GROUND WP WEATHERPROOF = Q U <br /> 1 � <br /> 7. PROVIDE TYPEWRITTEN SCHEDULES INDICATING LOAD DESCRIPTION KVA KILO VOLT AMP W WIRE MSB MAIN SWITCHBOARD W/ WITH 0 � <br /> FOR ALL CIRCUITS IN PANELBOARDS, ON PANEL DOOR. PRI. PRIMARY XFMR TRANSFORMER <br /> TO (E) MSB � C/) U <br /> 8. USE ONLY INSULATED CONDUCTORS IN CIRCUITS. CONDUCTORS = <br /> SHALL BE SIZED PER NEC AND DRAWINGS (MINIMUM #12 COPPER). WIRE AND CONDUIT LEGEND 0) U <br /> MINIMUM CONDUCTOR INSULATION SHALL BE 'THW' OR 'THWN' FOR 0 Ln <br /> CONDUCTORS SIZE #6 AWG AND LARGER. NO ROMEX ALLOWED. CONDUIT RUN CONCEALED IN WALL OR ABOVE CLG. N 01,_ <br /> WHERE PVC CONDUIT IS USED, A GROUND WIRE SIZED PER NEC - - UNDERGROUND CONDUIT. <br /> ART. 250-45 (EQUIPMENT GROUND) SHALL BE PULLED. (E)200A FEEDER - HOME RUN, NUMBER OF ARROWS INDICATE NUMBER OF CIRCUITS <br /> 9. FINAL CONNECTIONS TO ALL DIRECT CONNECTED KITCHEN IN HOME RUN. NO CROSSBARS INDICATE (2)#12 <br /> EQUIPMENT SHALL BE WITH U.L. APPROVED LIQUID-TIGHT CONDUIT, CONDUCTORS IN 1 /2" CONDUIT. CONDUCTOR SIZE IS #12, <br /> PROVIDED WITH GROUND WIRE SIZED PER NEC ART 250-95. CONDUIT SIZE IS 1/2" UNLESS OTHERWISE NOTED. DATE 09/15/2021 <br /> LONGER CROSS BAR INDICATES NEUTRAL, SHORTER INDICATES SCALE AS <br /> PHASE. ARC INDICATES GROUND. NOTED <br /> 10. CONDUIT INSIDE BUILDING SHALL BE EMT OR RSC. FLEXIBLE O CONDUIT UP. DRAWN MSK <br /> CONDUIT ,AY BE USED WITH OWNER APPROVAL. ALL EXPOSED (E) CONDUIT DOWN. J0B <br /> FLEX CONDUIT SHALL BE SEAL-TIGHT OR EQUAL. PANES � /� 21035 <br /> 1 �/ " SO CORD WHIP TO EQUIPMENT. SIZE AS MENTIONED SHEET TITLE <br /> 11. ALL JUNCTION BOXES SHALL BE 4 SQUARE, UNLESS NOTED A ON PLAN <br /> OTHERWISE. ELECTRICAL <br /> 12. VERIFY MOUNTING HEIGHTS AND LOCATIONS OF ALL ELECTRICAL NOTES, <br /> OUTLETS, J-BOZES, ETC. WITH OWNER PRIOR TO ROUGH-IN. <br /> 13. ALL SWITCHES TO BE 36" MINIMUM, 48" MAXIMUM A.F.F. SYMBOLS, <br /> 14. PROVIDE RECEPTACLE, DISCONNECT SWITCH, ETC. AS REQUIRED BY SCHEDULES <br /> CONFIGURATION EQUIPMENT BWITH FINAL EQUIPMENT SELECTION.EING INSTALLED. VERIFY RECEPTACLE PARTIAL SINGLE LINE DIAGRAM & LEGEND <br /> 1 <br /> SHEET <br /> E1 . 0 <br />