Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> GRIN INVESTMENTS INC DBA:ARCO AM/PM 6009 N EL DORADO ST, STOCKTON November 30, 2022 <br /> Single-Walled Non-Pressurized Piping <br /> 404 CCR 2643(e),2661(f) Failure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair(pre-1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 205 CCR 2712(i) Failure to submit and have current UST Monitoring Plan readily accessible at the facility. <br /> OBSERVATION:An approved copy of the monitoring plans were not available for inspection. <br /> REGULATION GUIDANCE:A copy of these plans shall be accessible on site at all times. <br /> CORRECTIVE ACTION: Immediately locate and retain a copy on site. <br /> This is a repeat violation, Class II. <br /> 208 CCR 2716(a-e) Failure to comply with the designated operator inspection requirements. <br /> OBSERVATION: The designated operator failed to check and note all required items on the visual inspection <br /> reports.The missing information included the following from the inspection reports: <br /> -alarms were not addressed on monthly reports. <br /> REGULATION GUIDANCE: During the visual inspection,the designated operator shall check that all required <br /> testing and maintenance for the UST system have been completed and shall check all required items on the report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing visual inspections at this facility are including <br /> all of the required information on the reports. <br /> This is a repeat violation, Class II. <br /> 307 HSC 25290.1(c3), 25290.2(c3) Failure to keep water out of the secondary containment system (post-Jul 2003). <br /> OBSERVATION:Water was found in the 87 submersible turbine pump(STP)sump and the Diesel fill sump. <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION: The service technician removed approximately 1/4 cup of liquid from the 87 and Diesel <br /> sumps and returned the sensors to their proper locations. Immediately contact a properly licensed, trained, and <br /> certified contractor to address the water intrusion into the 87 STP sump and Diesel fill sump under permit and <br /> inspection of the EHD. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 12/30/2022. <br /> FA0024188 PR0542116 SCO01 11/30/2022 <br /> EHD 23-01 Rev.12/06/2021 Page 4 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />