Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUN r <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> PELICAN RENEWABLES LLC 3028 NAVY DR, STOCKTON October 26, 2022 <br /> SPCC Plan Requirements for Onshore Facilities(excluding production facilities) <br /> 719 CFR 112.8(c)(11) Failed to locate properly or provide sufficient secondary containment for mobile/portable containers ❑V ❑R ❑COS <br /> 720 CFR 112.8(d)(1) Failed to take corrective action on buried piping when exposed for any reason ❑V ❑R ❑COS <br /> 721 CFR 112.8(d)(1) Failed to provide corrosion protection for buried piping ❑V ❑R ❑COS <br /> 722 CFR 112.8(d)(2) Failed to cap/blank-flange connection at transfer point and mark its origin if not in service ❑V ❑R ❑COS <br /> 723 CFR 112.8(d)(3) Failed to design pipe supports to minimize abrasion/corrosion and to allow for expansion/contraction ❑V ❑R ❑COS <br /> 724 CFR 112.8(d)(4) Failed to regularly inspect aboveground valves,piping,and appurtenances ❑V ❑R ❑COS <br /> 725 CFR 112.8(d)(4) Failed to conduct integrity and leak testing on buried piping any time it is worked on ❑V ❑R ❑COS <br /> 726 CFR 112.8(d)(5) Failed to adequately warn vehicles entering facility to protect piping and other transfer operations ❑V ❑R ❑COS <br /> 727 CFR 112.7(a)(1), Plan failed to adequately describe overfill prevention methods for each container ❑V ❑R ❑COS <br /> 112.8(c)(8) <br /> Other Violations <br /> 4010 See below Unlisted Administration/Documentation violation ❑V ❑R ❑COS <br /> 4020 See below Unlisted Training violation u V ❑R ❑COS <br /> 4030 See below Unlisted Operations/Maintenance violation n V ❑R ❑COS <br /> 4040 See below Unlisted Release/Leaks/Spills violation ❑V ❑R ❑COS <br /> 4050 See below Unlisted Abandonment/Illegal Disposal/Unauthorized Treatment violation u V u R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 203 CFR 112.3 Failure to implement the SPCC Plan. <br /> OBSERVATION: The Spill Prevention, Control, and Countermeasure(SPCC)Plan was not implemented, as <br /> required. Monthly secondary containment tank inspections and trainings were not conducted by the facility as per <br /> their SPCC plan. <br /> REGULATION GUIDANCE: 112.3: The owner or operator or an onshore or offshore facility subject to this section <br /> must prepare in writing and implement a Spill Prevention Control and Countermeasure Plan (hereafter"SPCC Plan" <br /> or"Plan")," in accordance with § 112.7 and any other applicable section. 25270.4.5.(a):An owner or operator shall <br /> conduct periodic inspections of the storage tank to ensure compliance with Part 112 (commencing with Section <br /> 112.1)of Subchapter D of Chapter I of Title 40 of the Code of Federal Regulations. In implementing the spill <br /> prevention control and countermeasure plan, an owner or operator shall fully comply with the latest version of the <br /> regulations contained in Part 112(commencing with Section 112.1)of Subchapter D of Chapter I of Title 40 of the <br /> Code of Federal Regulations. <br /> CORRECTIVE ACTION: Implement the SPCC plan, as required. Submit proof of correction to the EHD. <br /> This is a Class II violation. <br /> FA0019299 PR0530029 SCO01 10/26/2022 <br /> EHD 28-01 Rev.12/06/2021 Page 4 of 11 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />