22'-3"50'-5 3/4"1A2.01/4" = 1'-0"REFLECTED CEILING PLANNORTHNOTE:REFER TO A0.0 FOR GENERAL NOTESAND NOTES TO BIDDERSPLAN5/8" GYP BD TYP1-1/4" COMPRES STRUT & (4) 12 GALAT BRACING WIRESSPLAYED 90 DEG APART TYP@ 12'-0" OC MAX EA WAY6" MAX4'-10 1/8"MIN <br />12 GA VERT WIRE HANGERS @4'-0" OC MAX EA WAY TYP4 PLACESTYPICAL <br />4' <br />-0 <br />" <br /> TYP <br />.2'-0"2'-0"CEILING TILES TYPSUSPEND ACOUSTIC CEILING SYSTEM FROM STRUCT ABV AS FOLLOWS:FROM WOOD STRUCT: #10 CLOSED EYE SCREW.FROM STL PURLINS: 'HILTI' CC27/DN22 COMBINATION CL'G CLIPS/SHOT PINS(ICBO NO. 2388, LARR NO. 2582) OR EQ, OR CLAMP ON 'UNISTRUT' CHANNELS@ 4'-0" OC, PARALLEL W/MAIN RUNNERS BELOW.FROM STL BAR JOISTS: TIE THRU BOTTOM FLANGES.FROM CONCRETE/STL DECK OR CONCRETE DECK: 'HILTI' TB 27 S12 (ICBO NO.2388, LARR NO. 2582) OR EQ.COMPRESSTRUTMAIN RUNNERS @4'-0" OC MAX TYP6'-0" MAX12 GA WIRE SPLAYEDIN FOUR DIRECTIONS90° APART @ 12'-0" OCMAX, EA WAY45°6'-6"1" 10'-0" PAIR 1-5/8" x 25 GA STUDS PAIR 2-1/2" x 25 GA STUDS 8'-6"BACK-TO-BACK:BACK-TO-BACK:1-1/2 " 15'-0" MAX10'-0" MAX4'-0" MAX HGT5'-2"1/2" EMT: 3/4" ACOUSTIC TILEPANELS TYPCROSS RUNNER2'-0MAX12 GA GALV WIRE HANGERS @ 4'-0"OC MAX TYP UP TO STRUCT ABVTYPREFER TO A1.0FOR WALL TYPECONT 2" (MIN.) ALUMHORIZONTAL LEG2"SUSPENDED ACOUST CLG SYSTEM, 'DONN' DX OR EQ(ICC ER-1222, LARR NO. 25764) TYP, UNO5A2.0N.T.S.SUSPENDED CEILING DETAILHANGER ATTACHMENT DEVICES SHALL BE AN APPROVED TYPE. SUSPENSION WIRES SHALL NOT BESMALLER THAN No. 12 GAUGE SPACED @ 4'-0" O.C. ALONG EACH MAIN RUNNER. EACH WIRE SHALL BEATTACHED TO THE CEILING MEMBER AND THE SUPPORT ABOVE WITH A MINIMUM OF THREE TURNS.CONNECTION DEVICES AT THE SUPPORTING CONSTRUCTION SHALL BE CAPABLE OF CARRYING NOTLESS THAN 100 POUNDS. WIRES SHALL NOT HANG MORE THAN 1 IN 6 OUT OF PLUMB UNLESSCOUNTERSLOPING WIRES ARE PROVIDED. A TRAPEZE SHALL BE USED WHERE OBSTRUCTIONSPRECLUDE DIRECT SUSPENSION.CEILING MOUNTED AIR TERMINALS OR SERVICES WEIGHING LESS THAN 20 POUNDS SHALL BEPOSITIVELY ATTACHED TO THE MAIN RUNNERS OR CROSS RUNNERS WITH THE SAME CARRYINGCAPACITY AS MAIN RUNNERS. SERVICES WEIGHING 20 POUNDS BUT LESS THAN 56 POUNDS SHALLHAVE, IN ADDITION TO THE ABOVE, TWO No. 12 GAUGE HANGERS CONNECTED FROM THE TERMINALOR SERVICE TO THE STRUCTURE ABOVE. THESE WIRES MAY BE SLACK. SERVICES WEIGHING MORETHAN 56 POUNDS SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVE BY APPROVEDHANGERS.ALL PARTITIONS SHALL BE BRACED INDEPENDENTLY FROM THE CEILING SYSTEM.TERMINAL ENDS OF EACH CROSS RUNNER AND MAIN RUNNER SHALL BE INDEPENDENTLYSUPPORTED A MAXIMUM OF 8" FROM THE WALL OR CEILING DISCONTINUITY WITH No. 12 GAUGEWIRE.HORIZONTAL RESTRAINTS SHALL BE EFFECTED BY FOUR No. 12 GAUGE WIRES SECURED TO THEMAIN RUNNER WITHIN 2" OF THE CROSS RUNNER INTERSECTION AND SPLAYED 90 DEGREES FROMEACH OTHER AT AN ANGLE NOT TO EXCEED 45 DEGREES FROM THE PLANE OF THE CEILING. A STRUTFASTENED TO THE MAIN RUNNER SHALL BE EXTENDED UP AND FASTENED TO THE STRUCTURALMEMBERS SUPPORTING THE ROOF OR FLOOR ABOVE. THE STRUT SHALL BE ADEQUATE TO RESISTTHE VERTICAL COMPONENT INDUCED BY THE BRACING WIRES. THESE HORIZONTAL RESTRAINTPOINTS SHALL BE PLACED 12'-0" ON CENTER IN BOTH DIRECTIONS WITH THE FIRST POINT WITHIN 6'-0"FROM EACH WALL. ATTACHMENT OF THE RESTRAINT WIRES SHALL BE ADEQUATE FOR THE LOADIMPOSED.LATERAL FORCE BRACING MEMBERS SHALL BE SPACED A MINIMUM 0F 6" FROM ALL HORIZONTALPIPING OR DUCTWORK THAT IS NOT PROVIDED WITH BRACING RESTRAINTS FOR HORIZONTALFORCES. BRACING WIRES SHALL BE ATTACHED TO THE GRID AND TO THE STRUCTURE IN SUCH AMANNER THAT THEY CAN SUPPORT A DESIGN LOAD OF NOT LESS THAN 200 POUNDS OR THE ACTUALDESIGN LOAD, WHICHEVER IS GREATER, WITH A SAFETY FACTOR OF 2.PERIMETER MEMBERS SHALL BE CONSIDERED AS AESTHETIC CLOSURES WITH NO STRUCTURALVALUE. ENDS OF MAIN RUNNERS AND CROSS RUNNERS SHALL BE TIED TOGETHER TO PREVENTSPREADING. MAIN RUNNERS AND CROSS RUNNERS MAY BE ATTACHED AT TWO ADJACENT WALLSWITH CLEARANCE BETWEEN THE WALL AND RUNNERS MAINTAINED AT THE OTHER TWO WALLS.INTERMEDIATE AND HEAVY DUTY CEILING SYSTEMS SHALL BE USED FOR SUPPORT OF LIGHTFIXTURES. ALL LIGHTING FIXTURES SHALL BE POSITIVELY ATTACHED TO THE SUSPENDED CEILINGSYSTEM. THE ATTACHMENT DEVICE SHALL HAVE A CAPACITY OF 100% OF THE LIGHTING FIXTUREWEIGHT ACTING IN ANY DIRECTION. WHEN INTERMEDIATE SYSTEMS ARE USED, No. 12. GAUGEHANGER WIRES SHALL BE ATTACHED TO THE GRID MEMBERS WITHIN 3" OF EACH CORNER OF EACHFIXTURE. TANDEM FIXTURES MAY UTILIZE COMMON WIRES. WHEN HEAVY DUTY SYSTEMS ARE USED,SUPPLEMENTAL HANGERS ARE NOT REQUIRED IF A 48" MODULAR PATTERN IS FOLLOWED.LIGHTING FIXTURES WEIGHING LESS THAN 56 POUNDS SHALL HAVE, IN ADDITION TO THE ABOVEREQUIREMENTS, TWO No. 12 GAUGE HANGERS CONNECTED FROM THE FIXTURE HOUSING TO THESTRUCTURE ABOVE. THESE WIRES MAY BE SLACK. LIGHTING FIXTURES WEIGHING 56 POUNDS ORMORE SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVE BY APPROVED HANGERS.PENDANT-HUNG LIGHTING FIXTURES SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVEUSING No. 9 GAUGE WIRES OR APPROVED ALTERNATE SUPPORT WITHOUT USING THE CEILINGSYSTEM FOR DIRECT SUPPORT.NOTE: A HEAVY DUTY T-BAR GRID SYSTEM SHALL BE USED. THE SYSTEM SHALL BE INSTALLED INACCORDANCE WITH THE PROVISIONS OF ASTM C 635 AND ASTMC 636. SECTION 1613.1 CBCTHE WIDTH OF THE PERIMETER SUPPORTING CLOSURE ANGLE SHALL NOT BE LESS THAN 2 INCHES INEACH ORTHOGONAL HORIZONTAL DIRECTION,ONE END OF THE CEILING GRID SHALL BE ATTACHEDTO THE CLOSURE ANGLE. THE OTHER END IN EACH HORIZONTAL DIRECTION SHALL HAVE A 0.75 INCHCLEARANCE FROM THE WALL AND SHALL REST UPON, AND BE FREE TO SLIDE ON A CLOSURE ANGLE.EXCEPT WHERE RIGID BRACES ARE USED TO LIMIT LATERAL DEFLECTIONS, SPRINKLERHEADS, OR OTHER PENETRATIONS SHALL HAVE A 2 INCH OVERSIZE RING, SLEEVE, ORADAPTOR THROUGH THE CEILING TILE TO ALLOW FOR FREE MOVEMENT OF AT LEAST 1 INCHOF CEILING MOVEMENT IN ALL HORIZONTAL DIRECTIONS. ALTERNATIVELY, A SWING JOINTTHAT CAN ACCOMMODATE 1 INCH OF CEILING MOVEMENT IN ALL HORIZONTAL DIRECTIONS ISPERMITTED TO BE PROVIDED AT THE TOP OF THE SPRINKLER HEAD EXTENSION.EXCEPT WHERE RIGID BRACES ARE USED TO LIMIT LATERAL DEFLECTIONS,SPRINKLER HEADS, OR OTHER PENETRATIONS SHALL HAVE A 2 INCH OVERSIZERING, SLEEVE, OR ADAPTOR THROUGH THE CEILING TILE TO ALLOW FOR FREEMOVEMENT OF AT LEAST 1 INCH OF CEILING MOVEMENT IN ALL HORIZONTALDIRECTIONS. ALTERNATIVELY, A SWING JOINT THAT CAN ACCOMMODATE 1 INCH OFCEILING MOVEMENT IN ALL HORIZONTAL DIRECTIONS IS PERMITTED TO BEPROVIDED AT THE TOP OF THE SPRINKLER HEAD EXTENSION.NORTHNOTE:REFER TO A0.0 FOR GENERAL NOTESAND NOTES TO BIDDERSPLANTYP.4A6.04'-0" <br />TO MENU <br />BOARD <br />10"2'-6" <br />CL CLORDER101NEW "C1" CEILINGAT 12'-4" A.F.F.SALES104NEW "C2" CEILINGAT 9'-0" A.F.F.COOKING105NEW "C2" CEILINGAT 9'-0" A.F.F.PREP106NEW "C2" CEILINGAT 9'-0" A.F.F.JANITOR107NEW "C2" CEILINGAT 10'-0" A.F.F.COOLER108FREEZER109UNISEX110LIGHTING, DIFFUSERS, & GRILLE SCHEDULESPECIFICATIONSSYMBOLMK.MOUNTING HEIGHTNOTESFIXTURE: 2'-0" TRACK W/ (2) FIXTURES (HEAD)SUPPLIER: MELETIO ELECTRICAL SUPPLYAMOUNT TO BOTTOM OF SCHEDULED CLG., BOTTOM OF TRACKMOUNTED TO BOTTOM OF FRAMING AND 3'-0" FROM ADJACENTWALLS UNLESS NOTED OTHERWISEFIXTURE: 16" ROUND PENDANT W/ 15'-0" CORD (BLACK)SUPPLIER MELETIO ELECTRICAL SUPPLYFIXTURE: 4" ROUND RECESSED CAN LIGHTSUPPLIER MELETIO ELECTRICAL SUPPLYFIXTURE: 2'x4' TROFFER W/ ACRYLIC LENSSUPPLIER: MELETIO ELECTRICAL SUPPLYFIXTURE: WALL MOUNTED FLAT PANEL DISPLAYTV WALL MOUNTING BRACKET FOR FLAT SCREEN TV'S 32" TO 42" MODELSCONTRACTOR TO COORDINATE BRACKET WITH MANUFACTURER'SRECOMMENDATION AND OWNER SELECTIONSUPPLIED BY OWNERBCDFLCDSMELETIO ELECTRICAL SUPPLY: 10930 HARRY HINES, DALLAS, TEXAS 75220CONTACT: JIM ELLIS (SALES MANAGER), PHONE 1-800-777-4993 EXT. 1143 OFFICE, 972-559-6943 DIRECT, 214-353-3425 FAX, JELLIS@MELETIO.COMSUPPLIER NOTE:SCHEDULE SHEET A4.0SUSPEND FROM CLG. W/ 3/8"ALL-THREADMOUNT TO SCHEDULED CLG. AS FOLLOWS:FLUSH MOUNTN/AMOUNT TO SCHEDULED ACOUSTICAL CLG.N/AMOUNT TO SCHEDULED ACOUSTICAL CLG.NOTE: CLG. INSULATION MUST BE 3" AWAY ON ALL SIDESN/AMOUNT TO SCHEDULED PARTITION WITH BOTTOM OF LCD PANEL ASINDICATED ON THE REFLECTED CLG. PLANN/AFIXTURE: 6'-0" TRACK WITH AMP CURRENT LIMITER (4) WALL WASHTRACK HEADS (WHITE)SUPPLIER: MELETIO ELECTRICAL SUPPLYMOUNT TO SCHEDULED CLG.CLG. INSULATION MUST BE 3" AWAY ONALL SIDES8" CEILING RECESSED SPEAKERPROVIDED BY OWNER, SUPPLIED BY APPROVED VENDOR, COORDINATED BY GC -PROVIDE MIN. 6" ADDITIONAL WIRE PER SPEAKER AT J-BOXMOUNT IN TILEPROVIDE IN FACTORY FINISHED FLATBLACKFIXTURE: 2'x4' TROFFER W/ ACRYLIC LENSSUPPLIER: MELETIO ELECTRICAL SUPPLYCAMOUNT TO SCHEDULED ACOUSTICAL CLG.N/AN/ANORTHTRUEFIXTURE: 6" ROUND RECESSED CAN LIGHTSUPPLIER MELETIO ELECTRICAL SUPPLYDAMOUNT TO SCHEDULED ACOUSTICAL CLG.NOTE: CLG. INSULATION MUST BE 3" AWAY ON ALL SIDESN/AMOUNT TO SCHEDULED CLG. AS FOLLOWS:ALL AREAS SUSPEND TO 8'-6" A.F.F. TO BOTTOM OF FIXTUREN/AFIXTURE: 10" ROUND PENDANT, 10 1/4" H, FLUSH MOUNT (SATIN ALUMINUM)SUPPLIER: HI-LITE MFG. CO.FIXTURE: 6" ROUND RECESSED CAN LIGHTSUPPLIER MELETIO ELECTRICAL SUPPLYDBMOUNT TO SCHEDULED ACOUSTICAL CLG.NOTE: CLG. INSULATION MUST BE 3" AWAY ON ALL SIDESBA52'-0"2'-0"68EQ.4'-0"EQ.EQ.EQ.EQ.3'-6"EQ.EQ.3'-6"3'-6"EQ.A2.03TYP.A2.031'-1"2'-11 1/4"2A6.02A6.05A6.02424NEW "C3" CEILINGAT 9'-0" A.F.F.1NEW "C1" CEILINGAT 14'-4" A.F.F.CEILING LEGEND1INSTALL ALL WALL MOUNTED LCD/TV OUTLETS 7'-0" A.F.F. - REFER TO 2/A2.0 - TYP.2TRACK LIGHTING (BLACK) MOUNTED TO BOTTOM OF THE CEILING TILE - TYP.3NOT USED4SPEAKER LOCATIONS - PROVIDED BY OWNER, SUPPLIED BY APPROVED VENDOR,AND COORDINATED BY GC5MENU BOARD - MOUNT BOTTOM OF MENU BOARD AT 7'-0" A.F.F. - REFER TO A3.0FOR ADD. INFO.67CEILING GRID STARTING POINT8NOT USEDORDER AHEAD SIGN, ORIENTATE TO FRONT DOOR - REFER TO A3.1 FOR ADD.INFO.CEILING PLAN NOTES1.LIGHT FIXTURES SHALL BE PLACED AS DIMENSIONED AND SCHEDULED - ALLLIGHT FIXTURES SUPPLIED AS SCHEDULED WITH NO EXCEPTIONS3. REFER TO MECHANICAL DRAWINGS FOR RETURN AND DIFFUSER LOCATIONS- ALL RETURNS AND DIFFUSERS IN SALES, ORDER, AND SEATING AREAS TOBE FACTORY FINISHED IN FLAT BLACK4.VERIFY LOCATION AND QUANTITIES FOR EMERGENCY LIGHTING WITH ELECTRICAL DRAWINGS, LOCAL INSPECTION AGENCY, AND LOCAL FIRE MARSHALL - EXIT SIGNS SHALL BE CONNECTED TO AN EMERGENCYELECTRICAL SYSTEM PROVIDED FROM STORAGE BATTERIES, UNITEQUIPMENT OR AN ON-SITE GENERATOR - THE SYSTEM SHALL BEINSTALLED IN ACCORDANCE WITH THE ELECTRICAL CODE5.REFER TO DETAIL 4/A2.0 FOR SUSPENDED CEILING DETAIL6.REFER TO THE FINISH SCHEDULE ON SHEET A4.0 FOR CEILING FINISHINFORMATIONA2.04 NOT USED3'-0"2A2.03/4" = 1'-0"WALL-MOUNT BRACKET DETAILFLAT PANEL DISPLAY (SIZEVARIES), CONTRACTOR TOCOORDINATE SIZE & TYPE OFDISPLAY W/ OWNERFLAT PANEL DISPLAY WALLMOUNT BRACKET,CONTRACTOR TOCOORDINATE TYPE W/ OWNER& DISPLAY MANUF. REQ'S.PRIOR TO INSTALLATION5/8" PLYWD. BACKINGINSTALLED AT MOUNTINGBRACKET LOCATION7'-0" A.F.F. <br />(MAX.) <br />SEE RCP7'-0" <br />A.F.F.3A2.01" = 1'-0"VENT DETAIL @ COOLERSCHEDULED CLG. - REFER TOFINISH SCHEDULE ON SHEETA4.0ATTACH CONT.INUOUS ALUM.HORIZONTAL LEG TO CLG.SYSTEM W/ RIVETS AT 12" O.C.(MIN.)REMOVABLE VINYL COATEDCLG. PANELS FOR ACCESS TOCONDENSING UNITSATTACH CONT. ALUM.HORIZONTAL LEG TO WALK-INCOOLER/FREEZER W/ 1-1/4"METAL SCREWS AT 12" O.C.(MIN.)WALK-IN COOLER/FREEZERBELOWWHITE 350 SERIES RETURNGRILLE. COORDINATE LOCATIONWITH MECHANICAL DWGS.4A2.01" = 1'-0"DETAIL @ STEPPED CEILINGSCHEDULED CLG. - REFER TOFINISH SCHEDULE ON SHEETA4.0ATTACH CONTINUOUS ALUM.HORIZONTAL LEG TO CLG.SYSTEM W/ RIVETS AT 12" O.C.(MIN.)INSTALL SEISMIC CLIPS TOHOLD VERTICAL TILES INPLACE2'-0"ATTACH CONTINUOUS ALUM.HORIZONTAL LEG TO CLG.SYSTEM W/ RIVETS AT 12" O.C.(MIN.)2'-0"A2.0REFLECTED CEILING PLANSEAL:STORE NUMBER: GL#Z060 <br />GILL GROVE <br />1687 N CALIFORNIA STREET SUITE #TBD <br />STOCKTON, CA 95204PROJECT LOCATION:SHEET NUMBER / TITLE:REVISION:DATE:CHECKED BY:ISSUE:DRAWN BY:PROJECT NO.:DATE:PROJECT INFORMATION:CLIENT:CONSULTANT:STOCKTON, CAXXXJSS2021-0486THESE DRAWINGS, IDEAS, SPECIFICATIONS ANDDESIGNS ARE EXCLUSIVE PROPERTY OF WINGSTOPRESTAURANTS, INC. NO PART OF THESE DRAWINGSMAY BE COPIED, REPRODUCED, OR OTHERSTRUCTURES BUILT FROM SUCH WITHOUT THEWRITTEN CONSENT OF WINGSTOP RESTAURANTS, INC.COPYRIGHT R 2013WINGSTOP RESTAURANTS, INC.ALL RIGHTS RESERVED15505 WRIGHT BROTHERS DRIVEADDISON, TX 75001TELEPHONE: (972) 686-6500FAX: (972) 686-6502DISCLAIMER:PERMIT & BID SET01-25-22DATE01-25-22EXPIRATION DATE: 06-30-2023MATTHEW M. WILKUS, ARCHITECTLICENSE NUMBER: C-37430