Laserfiche WebLink
WATER/VENT/GAS PLUMBING PLANSCALE: 1/4" = 1'-0"NOTE:REFER TO SHEET A0.0 FORCOMPLETE OCCUPANCY DATAVENTING ABOVE HIGHRIM, 6" MINIMUMP2NOTE:DATEFOR PERMIT & BID01-25-22SEAL:PROJECT LOCATION:SHEET NUMBER:REVISION:DATE:CHECKED BY:ISSUE:DRAWN BY:PROJECT NO.:DATE:PROJECT INFORMATION:CLIENT:CONSULTANT:THESE DRAWINGS, IDEAS, SPECIFICATIONS ANDDESIGNS ARE EXCLUSIVE PROPERTY OF WINGSTOPRESTAURANTS, INC. NO PART OF THESE DRAWINGSMAY BE COPIED, REPRODUCED, OR OTHERSTRUCTURES BUILT FROM SUCH WITHOUT THEWRITTEN CONSENT OF WINGSTOP RESTAURANTS, INC.COPYRIGHT R 2022WINGSTOP RESTAURANTS, INC.ALL RIGHTS RESERVED15505 WRIGHT BROTHERS DRIVEADDISON, TX 75001TELEPHONE: (972) 686-6500FAX: (972) 686-6502DISCLAIMER:STOCKTON, CA2021-0486STORE NUMBER: GL#Z060 <br />GILL GROVE <br />1687 N CALIFORNIA STREET SUITE #TBD <br />STOCKTON, CA 95204JJVDRC2/3/22796 Merus Court <br />St. Louis, MO 63026 <br />T 636.349.1600 <br />F 636.349.1730 TABLE TO CALCULATE WATER FIXTURE UNITSPLUMBING FIXTUREWATER FIXTUREUNITSNUMBER OFFIXTURESSFUSWATER CLOSET (WC-1)414LAVATORIES (LAV-1)2123 COMPARTMENT SINK4142 COMPARTMENT SINK414HAND SINK (HS-1)224MOP SINK313BEVERAGE DISPENSORS133HOSE BIBB2.52.5TOTAL WATER FIXTURE UNITS26.5GPM36.0WATER SERVICE , TYPE L COPPER1-1/4"2036-12060-12060-11824-51860-5 1836-42060-11860-51836-51836-51836-51836-51836-51836-52048-12024-1DARPRO <br />BACK FLOW PREVENTER ASSEMBLY REQUIREMENTSTYPE OFEQUIPMENT ONSYSTEMMETHOD OF CROSSCONNECTION CONTROLMANUFACTUREAND MODELNUMBERREMARKSCARBONATORSODA SYSTEMATMOSPHERIC CHECK VALVESTAINLESS STEEL BODY WITHQUARTER TURN VALVE SSSTRAINER.ICE MACHINEWATTS LF-009-QT-SSTAINLESS STEEL BODY WITHQUARTER TURN VALVE BRONZESTRAINER.TEA MACHINEDOUBLE CHECK VALVE ASSEMBLYWATTS SD3LFASSE 1022/1024 CERT.STAINLESS STEEL BODY WITHQUARTER TURN VALVE BRONZESTRAINER.WATER SERVICEREDUCED PRESSURE ZONE ASSEMBLYWATTS LF-919-QTLEAD FREE CAST COPPER WITHQUATER TURN1. CONTRACTOR SHALL PROVIDE INDIVIDUAL BACKFLOW PREVENTERS FOR EACH PIECE OF EQUIPMENT. 2. EACHBACKFLOW PREVENTER MUST HAVE TESTING PORTS.3. BRONZE BODIED BACKFLOW PREVENTERS ARE PERMISSABLE IF ALLOWED BY LOCAL CODES.12345678910111213141516171819202122LOW PRESSURE GAS PIPING RUN ON ROOF TOP.HAND SINK. SEE ITEM 22 ON SCHEDULE SHEET P5 AND RISER ON P3 FOR ADDITIONAL INFORMATION.3-COMPARTMENT SINK AND FAUCETS PROVIDED BY OWNER AND INSTALLED BY PLUMBING CONTRACTOR.SEE ITEM 17 ON SCHEDULE SHEET P5 AND RISER ON SHEET P3 FOR ADDITIONAL INFORMATION.3/4" (140°F) HOT WATER HOSE BIB UNDER 3-COMPARTMENT SINK, SEE ITEM 23 ON SCHEDULE SHEET P5.1/2" COLD WATER LINE TO ICE MACHINE, PROVIDE WATER FILTER AND BACKFLOW PREVENTER, SEE ITEM 19ON SCHEDULE SHEET P5.1/2" COLD WATER LINE TO CARBONATOR, PROVIDE BACKFLOW PREVENTER, THE PIPING MATERIALDOWNSTREAM OF BACKFLOW DEVICE SHALL NOT BE AFFECTED BY CO2 GAS. PROVIDE 1/4" CONNECTIONTO CARBONATOR. SEE ITEM 24 ON SCHEDULE SHEET P5.3/4" (140°F) HOT AND COLD WATER TO MOP SINK, SEE ITEM 3 ON SCHEDULE SHEET P5.THERMOSTATIC MIXING VALVE (MV-1) SUPPLIED AND INSTALLED BY PLUMBING CONTRACTOR. SET WATERTEMPERATURE FOR 110°F MAXIMUM, SEE ITEM 7 ON SCHEDULE SHEET P5.GAS FIRED WATER HEATERS, SEE WATER HEATER DETAIL THIS SHEET AND EQUIPMENT SCHEDULE ITEMS 8AND 9, SHEET P5. SET WATER TEMPERATURE FOR 140°F MAXIMUM.ROUTE TO CONNECT TO EXISTING 1-1/2" CAPPED AND SUB METERED WATER SERVICE. VERIFY EXACTLOCATION AND SIZE IN FIELD PRIOR TO WORK. CONTACT ENGINEER IMMEDIATELY IF DISCREPANCIES AREDISCOVERED. VERIFY WITH LANDLORD AND WATER COMPANY EXACT CONNECTION AND METERREQUIREMENTS PRIOR TO WORK.CIRCULATION PUMP. ITEM 29 P5.1/2" COLD WATER LINE TO WATER CLOSET. REFER TO ITEM 1 ON SCHEDULE SHEET P5 AND RISER DIAGRAMSHEET P3 FOR MORE INFORMATION, TYP. OF 2.1/2" HOT & COLD WATER LINES TO LAVATORIES. REFER TO ITEM 2 ON SCHEDULE SHEET P5, AND RISERDIAGRAM SHEET P3 FOR MORE INFORMATION.GAS DOWN TO KITCHEN EQUIPMENT. PROVIDE AUTOMATIC EMERGENCY FUEL SHUT-OFF VALVE IN RISER,EMERGENCY SHUT OFF INTERLOCKED TO HOOD FIRE SUPPRESSION SYSTEM.GAS LINE TO FRYERS.PROVIDE MANUAL SHUT-OFF VALVE FOR GAS LINE ABOVE AUTOMATIC EMERGENCY FUEL SHUT-OFF VALVEIN RISER. SEE GAS RISER DIAGRAM ON SHEET P3.1/2" COLD WATER LINE TO TOP MOUNTED ICE MACHINE, PROVIDE WATER FILTER AND BACKFLOWPREVENTER, AS SCHEDULED THIS SHEET.1/2" CW TO WALL MOUNTED TRAP PRIMER, SEE ITEM 10, SCHEDULE SHEET P5 AND WATER RISER DIAGRAMSHEET P3CONNECT TO 2" LOW PRESSURE GAS CAPPED TO SPACE. VERIFY WITH GAS COMPANY EXACTCONNECTION AND METER INSTALLATION REQUIREMENTS PRIOR TO WORK. GAS METER SHALL BE REPLACEWHEN NEW LOAD EXCEEDS RATING OF EXISTING.4" VENT UP THROUGH ROOF, MAINTAIN MINIMUM 10'-0" FROM OUTSIDE AIR INTAKES.5" PVC INTAKE PIPE THROUGH ROOF FOR WATER HEATER. REFER TO DETAIL THIS SHEET. INSTALL PERMANUFACTURERS RECOMMENDATION.3/4" CW UP TO MAU-1. PROVIDE WATTS 007 DCV OR EQUAL. COORDINATE WITH MECHANICAL SHEET H4.6"Ø SODA LINE CONDUIT ABOVE CEILING, SEE SHEETS A1.1 AND EQ.1.DRAIN FROM MAU-1 SHALL DISCHARGE INDIRECTLY ONTO ROOF, PAST P-TRAP. REFER TO H4.GAS DOWN TO GWH.5" CPVC OR PVDF FLUE PIPE THROUGH ROOF FOR WATER HEATER, REFER TO DETAIL THIS SHEET, OFFSETFOR MINIMUM 10'-0" CLEARANCE FROM OUTSIDE AIR INTAKE. MOUNT AS HIGH AS POSSIBLE.1/2" COLD AND HOT WATER LINES TO TWO COMPARTMENT SINK. SINK AND FAUCETS PROVIDED BY OWNERAND INSTALLED BY PLUMBING CONTRACTOR. REFER TO ITEM 18 ON SCHEDULE SHEET P5 AND RISER ONSHEET P3 FOR ADDITIONAL INFORMATION.PLUMBING KEYED NOTESWATTS SD3LFASSE 1022/1024 CERT.REDUCED PRESSURE ZONE ASSEMBLYGAS LOAD SUMMARYSYSTEMDESIGNATIONEQUIPMENTMBHDOMESTIC WATERHEATINGGWHWATER HEATER400SUB-TOTAL400KITCHEN EQUIPMENT"KEYNOTE" 15FRYER105"KEYNOTE" 15FRYER105"KEYNOTE" 15FRYER105"KEYNOTE" 15FRYER105"KEYNOTE" 15FRYER105SUB-TOTAL525TOTAL NATURAL GAS CONNECTED LOAD925GAS METERREQUIREMENTSMBH CAPACITY925TOTAL DEVELOPED LENGTH INCLUDING EQUIVALENT PIPELENGTH FOR FITTING AND VALVE FRICTION LOSSES TO GASMETER.80 FT X 1.2 =96 FTCONSULT GAS UTILITY COMPANY FOR REGULATOR RATINGEQUIPMENT REQUIRING 140° F WATER:1. (1) 3-COMPARTMENT SINK2. (1) MOB SINK BASIN3. (1) HOSE BIBB UNDER 3-COMPARTMENT SINK.EQUIPMENT REQUIRING 110° F WATER:1. (1) 2-COMPARTMENT SINK2. (2 HAND SINKS3. (1) LAVATORYWATER HEATER DISTRIBUTION:EXHAUST6'1'-2'INTAKEHOSE BIBBUNIONPRESSURE RELIEFVALVEPROVIDE RAIN CAPWATER HEATERGAS SUPPLY LINECOLD WATER SUPPLY LINEROOFPROVIDE RAIN CAP2' MINEXHAUST6'1'-2'INTAKEUNIONPIPE TOINDIRECT TOWASTE FIXTUREPRESSURE RELIEFVALVEPROVIDE RAIN CAPWATER HEATERHOT WATER SUPPLY LINEGAS SUPPLY LINEROOFPROVIDE RAIN CAP2' MINPRIMARYSUB 1AQUAREX WK1 WATERCONDTIONER OR EQUAL110V-11WFLOW RATES PER UNIT3011.14045606.5705.6804.9904.450FLOW RATE (GPM)TEMPERATURERISE (°F)1003.91103.61203.31302.8NORITZ NCC 199 CDV9.88.77.8PIPE TOINDIRECT TOWASTE FIXTUREHOT WATER RETURNPROVIDE EXPANSION RELIEFVALVE: SHARKBITE TER-1 OREQUAL. DISCHARGE INTO MOPBASINWHEN REQUIRED BY CODE ROUTE,THRU ACID NEUTRALIZER. REFER TOMFGR. FOR MODEL.CDNON CORROSIVE PIPING- 1" SCH. 40PVC OR RATED EQUAL·One neutralizer unit can sufficiently treat a maximum offifteen (15) condensing water heaters in a multi-system.·Internal neutralizing agent must be replaced once a year.See Installation/OperationManual for details onreplacingthe media.·For locations that exceed 2,000 ft above sea level, insureto follow manufacturer's installation settings.NON CORROSIVE PIPING- 1-1/2"SCH. 40 PVC OR RATED EQUALINDIRECT DISCHARGE TOFIXTURE INDICATED ON PLANKATHY SHAWNATIONAL HOT WATERNATIONAL ACCOUNT SALES888-444-4435214-876-0938 CELLwww.nationalhotwater.com2324252627HOSE BIBBHOSE BIBBHOSE BIBB(E)2"CWMGG61HS-128HS-128HS-1283-COMPSINK33-COMPSINK3115MSB-17921(TYP. OF 2)2610LAV-113818WC-112161415171920232224252-COMPSINK27