Laserfiche WebLink
E3 <br /> END OF DIVISION 16 <br />SECTION 16200 <br />SECTION 16100 <br />DIVISION 16 - ELECTRICAL SPECIFICATIONS <br />ELECTRICAL SPECIAL CONDITIONS <br />ELECTRICAL POWER AND LIGHTING <br />1. GENERAL <br />A.APPLICABLE PROVISIONS OF AIA DOCUMENT A201, "GENERAL CONDITIONS OF THE CONTRACT FOR <br />CONSTRUCTION", AND DIVISION 1 GENERAL CONDITIONS GOVERN WORK UNDER THIS SECTION AND ALL <br />OTHER SECTIONS OF DIVISION 16. <br />B.APPLICABLE PROVISIONS OF THIS SECTION GOVERN WORK UNDER ALL OTHER SECTIONS OF DIVISION 16. <br />WORK COVERED BY THIS SECTION SHALL CONSIST OF PROVIDING ALL MATERIAL, LABOR, EQUIPMENT AND <br />SERVICES NECESSARY FOR A COMPLETE, TESTED AND ADJUSTABLE ELECTRICAL INSTALLATION READY FOR <br />OPERATION AS SPECIFIED HEREIN AND AS SHOWN ON THE DRAWINGS. <br />C.THE TERM CONTRACTOR AS USED IN THIS SECTION SHALL MEAN ANY CONTRACTOR OR SUBCONTRACTOR <br />WHO HAS CONTRACTED TO PERFORM WORK INCLUDED IN AND DEFINED BY THIS SECTION AND ALL OTHER <br />SECTIONS OF DIVISION 16. <br />D.PROVIDE ALL LABOR, MATERIALS, EQUIPMENT AND TOOLS TO PERFORM ELECTRICAL WORK SHOWN, NOTED <br />OR SCHEDULED FOR A COMPLETE AND FINISHED INSTALLATION. ALL MATERIALS AND EQUIPMENT SHALL BE <br />COMMERCIAL GRADE AND SHALL CARRY A U.L. LABEL. <br />E.MATERIALS, PRODUCTS AND EQUIPMENT, INCLUDING COMPONENTS THEREOF SHALL BE NEW AND SUCH AS <br />APPEARS ON THE UNDERWRITER'S LABORATORY LIST OF APPROVED ITEMS AND SHALL MEET THE <br />REQUIREMENTS OF RECOGNIZED STANDARDS. EQUIPMENT SHALL BE SIZED IN CONFORMITY WITH <br />REQUIREMENTS OF THE CALIFORNIA ELECTRICAL CODE (C.E.C.) AND OTHER APPLICABLE CODES. <br />2. EXISTING CONDITIONS <br />A.THESE DRAWINGS ARE BASED ON INFORMATION PROVIDED TO OUR OFFICE AT THE TIME OF DESIGN. <br />THEREFORE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY ALL EXISTING CONDITIONS INCLUDING BUT <br />NOT LIMITED TO, SERVICE LOCATION, SERVICE LAYOUTS, SECONDARY FEEDER LENGTH, TELEPHONE <br />SERVICE LOCATION, ETC... AND REPORT ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO BID. FAILURE TO <br />DO SO MAY CONSTITUTE THAT THE CONTRACTOR PROVIDE ANY AND ALL ADDITIONAL EQUIPMENT, LABOR, <br />ETC... TO MEET THE INTENDED DESIGN PARAMETERS. <br />B.CONTRACTORS SHALL VISIT THE SITE PRIOR TO BIDDING. BIDS SHALL SERVE AS EVIDENCE OF KNOWLEDGE <br />OF EXISTING CONDITIONS. <br />3. CONTRACTOR'S RESPONSIBILITY <br />A.PRIOR TO SUBMITTING HIS BID, CONTRACTOR SHALL CAREFULLY EXAMINE THESE CONSTRUCTION <br />DOCUMENTS, THE DEVELOPER'S EXHIBITS, AND THE SITE, TO INQUIRE FULLY INTO DIFFICULTIES AND COSTS <br />OF WORK, AND TO DETERMINE THE SCOPE AND CHARACTER OF WORK TO BE DONE. CONTRACTOR SHALL <br />INCLUDE ALL NECESSARY COSTS TO LOCATE AND/OR EXTEND ALL UTILITIES INCLUDING LIGHTING PANELS, <br />POWER PANELS, ELECTRICAL SERVICE, PHONE SERVICE AND/OR MODIFY EQUIPMENT TO MEET THE INTENT <br />OF THE CONTRACT DOCUMENTS. THE OWNER, OWNER'S AGENT, ARCHITECT, ENGINEER OR DESIGNER SHALL <br />NOT BE RESPONSIBLE FOR FAILURE OF THE CONTRACTOR TO DETERMINE DIFFICULTIES AND COSTS IN THE <br />PROJECT OR FOR HIS OVERLOOKING OF THE REQUIREMENTS. <br />B.IF THIS CONTRACTOR DOES NOT CLEARLY UNDERSTAND THE PLANS AND SPECIFICATIONS, OR IF THERE ARE <br />ANY REQUIREMENTS WHICH ARE AMBIGUOUS IN THE CONTRACTOR'S OPINION, HE SHOULD CALL THIS TO THE <br />ATTENTION OF THE ARCHITECT PRIOR TO BIDDING, SINCE THIS CONTRACTOR WILL BE HELD RIGIDLY TO THE <br />INTERPRETATIONS OF THE ARCHITECT AND ENGINEER. <br />C.CONTRACTOR SHALL SCHEDULE HIS WORK IN COOPERATION WITH OTHER TRADES INSTALLING <br />INTERRELATED WORK. ALL WORK SHALL BE SCHEDULED TO MAINTAIN SERVICE TO ALL REQUIRED AREAS <br />DURING THE COURSE OF THE CONSTRUCTION EXCEPT FOR SHORT TERM PLANNED SHUTDOWNS, ANY OF <br />WHICH SHALL BE PRE-SCHEDULED WITH THE OWNERS AGENT AND THE LANDLORD. <br />4. WORKMANSHIP AND GUARANTEE <br />A.IN ENTERING INTO A CONTRACT COVERING THIS WORK, THE CONTRACTOR ACCEPTS THE SPECIFICATIONS, <br />AND GUARANTEES THAT THE WORK WILL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF <br />THE CONTRACT DOCUMENTS. CONTRACTOR FURTHER GUARANTEES THAT THE WORKMANSHIP AND <br />MATERIAL WILL BE OF THE BEST PROCURABLE AND THAT NONE BUT EXPERIENCED WORKMEN EXPERIENCED <br />IN EACH PARTICULAR CLASS OF WORK WILL BE EMPLOYED. CONTRACTOR FURTHER GUARANTEES TO <br />REPLACE AND MAKE GOOD AT HIS OWN EXPENSE ANY DEFECTS DUE TO FAULTY WORKMANSHIP OR <br />MATERIAL WHICH MAY DEVELOP WITHIN ONE (1) YEAR AFTER FINAL PAYMENT AND ACCEPTANCE BY THE <br />ARCHITECT. <br />5. CODES AND STANDARDS <br />A.CONTRACTOR WILL COMPLY IN ALL RESPECTS WITH THE ADOPTED BUILDING CODES, APPLICABLE LAWS, <br />ORDINANCES, AND REGULATIONS AS MAY APPLY ACCORDING TO THE RULING OF THE CONTROLLING PUBLIC <br />OFFICIAL SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE <br />REQUIREMENTS OF THE APPLICABLE LAWS, ORDINANCES AND REGULATIONS, OR WHICH DOES NOT RECEIVE <br />THE APPROVAL OF THE CONTROLLING PUBLIC OFFICIAL, HE SHALL BEAR ALL COSTS ARISING IN CORRECTING <br />THE DEFICIENCIES. ALL ELECTRICAL EQUIPMENT SHALL SHALL BEAR THE UNDERWRITER'S LABORATORY <br />LABEL. <br />6. FEES ON PERMITS <br />A.CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND MAKING PAYMENT FOR ALL FEES, PERMITS AND <br />INSPECTIONS RELATING TO HIS WORK. <br />7. CONTRACT DRAWINGS <br />A.THE DRAWINGS SHOW THE GENERAL ARRANGEMENT AND INTENT OF THE DESIGN AND SHALL BE FOLLOWED <br />AS CLOSELY AS ACTUAL BUILDING CONDITIONS AND THE WORK OF OTHER TRADES WILL PERMIT. BECAUSE <br />OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, FITTINGS, AND <br />ACCESSORIES WHICH MAY BE REQUIRED, NOR IS IT IMPLIED THAT ALL CONFLICTS BETWEEN VARIOUS <br />ELEMENTS OF THE SYSTEMS OR BUILDING COMPONENTS HAVE BEEN INDICATED. THE CONTRACTOR SHALL <br />INVESTIGATE ALL EXISTING CONDITIONS AFFECTING THE WORK AND ARRANGE HIS WORK ACCORDINGLY, <br />PROVIDING SUCH FITTINGS, OFFSETS, ACCESSORIES AND DEVICES AS MAY BE REQUIRED. THE DRAWINGS <br />AND SPECIFICATIONS ARE MUTUALLY COMPLEMENTARY, AND ANY WORK REQUIRED BY ONE BUT NOT BY THE <br />OTHER SHALL BE PERFORMED BY BOTH. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL <br />MATERIALS AND SERVICES REQUIRED FOR A COMPLETE AND WORKING PROJECT AT NO ADDITIONAL COST <br />EVEN THOUGH EACH AND EVERY NECESSARY ELEMENT THEREOF IS NOT SPECIFICALLY IDENTIFIED HEREIN <br />EACH AND EVERY NECESSARY ELEMENT THEREOF IS NOT SPECIFICALLY IDENTIFIED HEREIN. <br />B.CONTRACTOR SHALL NOT SCALE FROM THE DRAWINGS BUT SHALL FOLLOW THE ARCHITECTURAL DRAWINGS <br />OR EXISTING BUILDING CONDITIONS WHERE APPLICABLE, IN ESTABLISHING DIMENSIONS AND LINES OF RUN, <br />SINCE DIMENSIONS ON THE FINAL ARCHITECTURAL DRAWINGS OR AT THE SITE MAY NOT COINCIDE WITH <br />THOSE SHOWN ON THE ELECTRICAL DRAWINGS, THE CONTRACTORS SHALL VERIFY WITH THE DIMENSIONED <br />ARCHITECTURAL DRAWINGS OR THE SITE CONDITIONS THE EXACT MATERIAL QUANTITIES AND LENGTHS <br />NECESSARY. <br />C.SIGNIFICANT DEVIATIONS OR CHANGES FROM THE DRAWINGS WHICH ARE REQUIRED TO ACCOMPLISH THE <br />INTENT OF THE CONTRACT DOCUMENTS MUST BE REVIEWED WITH THE ARCHITECT AND APPROVED BEFORE <br />PROCEEDING. <br />8. SHOP DRAWINGS <br />A.CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, FOUR (4) COPIES MINIMUM, FOR ALL MANUFACTURED <br />PRODUCTS. EACH SHOP DRAWING SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO <br />ASSURE THAT ALL DIMENSIONS, QUANTITIES, CONNECTIONS, CAPACITATES AND ACCESSORIES SHOWN ARE <br />IN CONFORMANCE WITH THE CONTRACT DOCUMENTS, AND SHALL BE MARKED OR STAMPED TO CONFIRM <br />THAT SUCH REVIEW WAS MADE AND COMPLIANCE WAS CONFIRMED. <br />B.APPROVAL OF SHOP DRAWINGS BY THE OWNER, OWNER'S AGENT, ARCHITECT, ENGINEER OR DESIGNER, <br />WILL NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF COMPLYING WITH ALL TERMS OF THE <br />CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR PERFORMANCE OF ALL <br />EQUIPMENT PURCHASED, FOR PROPER FIT, AND OTHER DIMENSIONAL REQUIREMENTS. <br />9. RECORD DRAWINGS <br />A.CONTRACTOR SHALL MAINTAIN AT THE JOB SITE ONE SET OF DOCUMENTS AS "RECORD DRAWINGS" FOR THE <br />PURPOSE OF DAILY MARKING OF ALL SUBSTANTIAL REVISIONS TO THE DOCUMENTS INCLUDING BUT NOT <br />LIMITED TO ELECTRICAL CHANGES, AND LOCATIONS OF UTILITIES, PANELBOARDS, DISCONNECTS, STARTERS <br />AND OTHER DEVICES REQUIRING PERIODIC OPERATIONAL ATTENTION, ADJUSTMENT, OR SERVICE INCLUDING <br />ACCESS THERETO, AT THE COMPLETION OF THE PROJECT, THIS SET SHALL BE RETURNED TO THE <br />ARCHITECT FOR THE PURPOSE OF MAKING FINAL "AS-BUILT DRAWINGS". <br />10. EQUIPMENT SUBSTITUTION <br />A.SPECIFIC MANUFACTURERS AND MODELS OF EQUIPMENT HAVE BEEN USED IN THE DEVELOPMENT OF THE <br />DRAWINGS AND DESIGNS. THIS CONTRACTOR MUST SUBMIT TO THE OWNER ANY CHANGES AND/OR <br />SUBSTITUTIONS FOR APPROVAL PRIOR TO INSTALLATION OR EXECUTION. ANY CHANGES WHICH DO NOT <br />RECEIVE THE OWNER'S APPROVAL MAY BE SUBJECT TO REMOVAL OR REPLACEMENT AS ORIGINALLY <br />SPECIFIED, AND WILL BE AT THE CONTRACTOR'S EXPENSE. <br />B.IF THIS CONTRACTOR SUBSTITUTES FOR SPECIFIED EQUIPMENT ANY OTHER EQUIPMENT WHICH REQUIRES <br />ANY CHANGES TO THE DESIGN, ALL COST OF REDESIGN AND RECONFIGURATION RESULTING FROM SAID <br />SUBSTITUTION SHALL BE BORNE BY THE SUBMITTING CONTRACTOR. <br />11. EQUIPMENT INSTALLATION AND SUPPORT <br />A.CONTRACTOR SHALL SUPPORT PLUMB, RIGID AND TRUE-TO-LINE ALL WORK AND EQUIPMENT INSTALLED. <br />THIS CONTRACTOR SHALL DETERMINE HOW EQUIPMENT, FIXTURES, ETC., ARE TO BE SUPPORTED, MOUNTED, <br />OR SUSPENDED AND SHALL PROVIDE ACCESSORIES REQUIRED FOR PROPER SUPPORT WHETHER SHOWN ON <br />THE DRAWINGS OR NOT. IF SUPPORTS ARE REQUIRED, CONTRACTOR SHALL SUBMIT DRAWINGS TO THE <br />ARCHITECT FOR APPROVAL. <br />C.ALL CONDUIT CONNECTING TO SWITCHGEAR, PANELS, MOTORS, AND OTHER EQUIPMENT SHALL BE <br />INSTALLED WITHOUT STRAIN AT THE CONNECTIONS. THE CONTRACTOR MAY BE REQUIRED, AS DIRECTED, TO <br />DISCONNECT CONDUITS TO DEMONSTRATE THAT THEY HAVE BEEN SO CONNECTED. <br />12. DEMOLITION <br />A.ALL EXISTING EQUIPMENT, NOT INDICATED TO BE INCORPORATED INTO THE NEW SYSTEM SHALL BE <br />DISCONNECTED BY THIS CONTRACTOR FOR REMOVAL BY OTHERS FROM THE JOB SITE. CARE SHALL BE USED <br />SO THAT NO DAMAGE IS DONE TO EXISTING BUILDING, PIPING, DUCTWORK, AND/OR ELECTRICAL EQUIPMENT. <br />ANY DAMAGE ATTRIBUTED TO THIS CONTRACTOR SHALL BE REPAIRED OR REPLACED BY THIS CONTRACTOR. <br />13. CUTTING AND PATCHING <br />A.ALL CUTTING THAT MAY BE NECESSARY FOR THE INSTALLATION OF THE WORK OR ANY REQUIRED PATCHING <br />THAT RESULTS THEREFROM SHALL BE DONE BY THE PROPER TRADE INVOLVED AND SHALL BE INCLUDED AS <br />PART OF THIS CONTRACT. PATCH TO DUPLICATE UNDISTURBED ADJACENT FINISHES, COLORS, TEXTURES <br />AND PROFILES. COLUMNS, BEAMS, GIRDERS OR JOISTS SHALL NOT BE CUT. <br />B.ALL WORK AFFECTING ROOF OR STRUCTURES SHALL BE PERFORMED BY LANDLORD'S CONTRACTOR AT <br />TENANT'S EXPENSE. <br />14. CLEANING <br />A.COMPLETION AS IT PERTAINS TO THE CONTRACT COMPLETION DATE IS DEFINED AS THE DAY THE PROJECT IS <br />TURNED OVER TO THE OWNER IN THOROUGHLY CLEAN CONDITION. READY FOR THE OWNER TO TAKE <br />POSSESSION. ALL FIXTURES, MOTORS, EQUIPMENT AND ALL OTHER ELECTRICAL EQUIPMENT FURNISHED OR <br />INSTALLED BY THE CONTRACTOR SHALL BE THOROUGHLY CLEANED. <br />15. TESTS <br />A.PROVIDE THE TESTS AS OUTLINED HEREINAFTER AND OTHER TESTS NECESSARY TO ESTABLISH THE <br />ADEQUACY, QUALITY, SAFETY, COMPLETED STATUS AND SUITABLE OPERATION OF EACH SYSTEM. CORRECT <br />PROMPTLY ANY FAILURE OR DEFECTS REVEALED BY THESE TESTS AND RECONDUCT TEST ON THE <br />CORRECTED ITEMS. <br />B.TEST THE GROUNDS WITH A GROUND RESISTANCE DIRECT READING SINGLE-TEST MEGGER. <br />C.INSULATION RESISTANCE BETWEEN PHASE CONDUCTORS AND GROUND NOT LESS THAN 1,000,000 OHMS. <br />D.THE PANELBOARDS SHALL HAVE PHASE CURRENTS BALANCED TO WITHIN +/- 10% VARIATION BETWEEN <br />AVERAGE PHASE CURRENT AND MEASURED INDIVIDUAL PHASE. <br />E.AN OPERATIONAL TEST OF THE EMERGENCY LIGHTS AND THE EXIT LIGHTS SHALL BE PERFORMED FOR THE <br />OWNER TO DEMONSTRATE CONFORMANCE TO THE SPECIFICATIONS. <br />16. TEMPORARY ELECTRICAL SERVICE <br />A.TEMPORARY ELECTRICAL SERVICE SHALL BE IN ACCORDANCE WITH THE BUILDING CODE. TEMPORARY <br />LIGHTING SHALL BE PROVIDED BY A LAMP LOCATED FOR EVERY 625 SQUARE FEET OF BUILDING AREA WITH A <br />MINIMUM OF ONE PER ROOM. THE LAMP TO BE 100 WATT AND SHALL BE MAINTAINED BY THE GENERAL <br />CONTRACTOR. <br />B.TEMPORARY POWER DISTRIBUTION SHALL BE SUFFICIENT TO ACCOMMODATE THE TEMPORARY LIGHTING <br />AND CONSTRUCTION OPERATIONS, INCLUDING THE USE OF POWER TOOLS (BUT NOT INCLUDING HEAVY-DUTY <br />ELECTRICAL WELDING UNITS), ELECTRICAL HEATING UNITS, AND START-UP OF SPECIFIED BUILDING <br />EQUIPMENT, WHICH IS TO BE TESTED, STARTED OR PLACED INTO OUR USE PRIOR TO COMPLETION OF ITS <br />PERMANENT POWER CONNECTIONS. <br />17. EXCAVATION AND BACKFILL <br />A.CONTRACTOR SHALL DO ALL EXCAVATION REQUIRED AS SHOWN ON PLANS OR REQUIRED FOR PROPER <br />OPERATION. EXCESS EXCAVATION BELOW THE REQUIRED LEVEL SHALL BE BACKFILLED WITH EARTH AND <br />THOROUGHLY TAMPED. UTILITY SERVICES, SHALL BE INSPECTED AND APPROVED BY THE PROPER <br />INSPECTION AUTHORITY BEFORE BACKFILLING. <br />18. WEATHERPROOFING <br />A.CONTRACTOR SHALL ENSURE ALL PENETRATIONS THROUGH EXTERIOR ENVELOPE ARE COMPLETELY SEALED <br />AGAINST ALL AIR AND WATER INFILTRATION. <br />1. RELATED DOCUMENTS <br />A.APPLICABLE PROVISIONS OF AIA DOCUMENT A201, "GENERAL CONDITIONS OF THE CONTRACT FOR <br />CONSTRUCTION", DIVISION 1 GENERAL CONDITIONS AND SECTION 16100 ELECTRICAL SPECIAL CONDITIONS <br />GOVERN WORK UNDER THIS SECTION. <br />B.REFER TO SECTION 16100 ELECTRICAL SPECIAL CONDITIONS REGARDING REGULATIONS AND REQUIREMENTS <br />AFFECTING ALL WORK DESCRIBED IN THIS SECTION. <br />2. POWER SERVICE <br />A.POWER SERVICE FOR THIS PROJECT SHALL BE PROVIDED FROM THE UTILITY CO. THE ELECTRICAL <br />CONTRACTOR SHALL COORDINATE WITH TO INSURE THAT ALL WORK AND MATERIALS ARE IN CONFORMANCE <br />WITH THE UTILITY CO'S REQUIREMENTS. <br />3. NAMEPLATES <br />A.ELECTRICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO, PANELBOARDS, DISCONNECTS TRANSFORMERS, <br />CONTROLS, ETC., SHALL BE IDENTIFIED WITH THREE PLY LAMINATED PLASTIC. THE OUTSIDE LAMINATIONS <br />SHALL BE BLACK. ENGRAVING SHALL EXTEND THROUGH THE FRONT LAMINATION SO THAT THE BLACK <br />LETTERS APPEAR ON A WHITE BACKGROUND. NAMEPLATES SHALL BE PERMANENTLY ATTACHED WITH <br />SCREWS. <br />B.CIRCUIT DIRECTORY SHALL BE TYPEWRITTEN (HANDWRITTEN IS NOT ACCEPTABLE) AND SHALL IDENTIFY <br />CIRCUIT AS TO TYPE AND LOCATION AS FOLLOWS: <br />"LTG" - FOR LIGHTING CIRCUIT FOLLOWED BY AREA IN WHICH CIRCUIT APPEARS, I.E., "STOCKROOM", "CASH <br />WRAP", ETC. <br />"RECEPT" - FOR RECEPTACLE CIRCUIT FOLLOWED BY AREA IN WHICH RECEPTACLE APPEARS, <br />"STOREFRONT", "CASH REGISTER", ETC. <br />"MOTOR" - FOR MOTOR FOLLOWED BY THE EQUIPMENT IDENTIFICATION AND AREA IN WHICH MOTOR IS <br />LOCATED, I.E. "EXH FAN TOILET", "AHU-ROOF", ETC. <br />4. CONDUIT <br />A.CONDUIT SHALL BE STANDARD STEEL, RIGID IMC OR EMT (THIN WALL). CONDUIT SHALL BE CONCEALED IN <br />FINISHED AREAS. EXCEPT AS OTHERWISE APPROVED BY OWNER'S REPRESENTATIVE. INDOOR EMT <br />CONNECTIONS SHALL BE SET SCREW TYPE FITTING WHERE ALLOWED BY LOCAL AUTHORITY HAVING <br />JURISDICTION. EXTERIOR EMT CONNECTIONS SHALL BE COMPRESSION TYPE. <br />B.MINIMUM SIZES OF CONDUIT SHALL BE 3/4" EXCEPT 1/2" FOR SWITCH LEGS. EMT SHALL BE GALVANIZED OR <br />ELECTRO-GALVANIZED. EMT SHALL BE USED FOR FEEDERS AND BRANCH CIRCUITS RUN ABOVE SUSPENDED <br />CEILINGS OR CONCEALED IN INTERIOR PARTITIONS. EMT SHALL NOT BE CONCEALED IN POURED CONCRETE <br />FLOOR OR WALLS. <br />C.USE HEAVY WALL CONDUIT OR PVC FOR UNDER SLAB INSTALLATIONS. <br />D.THE USE OF NONMETALLIC-SHEATHED CABLE, TYPE NM, IS NOT ACCEPTABLE. <br />1.THE USE OF METAL CLAD CABLES, TYPE MC, IS ACCEPTABLE WHERE APPROVED BY THE LOCAL AHJ. <br />ALL BRANCH CIRCUIT HOME RUNS TO PANELBOARDS AND DEDICATED BRANCH CIRCUITS SHALL BE IN <br />EMT. <br />2.ALL METAL CLAD CABLES, SHALL BE PROVIDED WITH A GROUND WIRE. <br />E.ALL OPENINGS IN FIRE AND SMOKE WALLS, PARTITIONS, FLOORS AND OTHER SIMILAR PENETRATIONS FOR <br />ELECTRICAL CONDUITS, CABLE OR EQUIPMENT, WHETHER CUT OR IN PLACE, SHALL BE CLOSED WITH A UL <br />APPROVED FIRE RESISTANT SILICONE FOAM SEALANT TO MAINTAIN THE FULL RATING AND INTEGRITY OF THE <br />PARTITIONS, WALLS OR FLOOR. <br />F.CONDUIT BENDS FOR POWER AND LIGHTING CIRCUITS SHALL NOT BE LESS THAN STANDARD RADIUS BENDS. <br />CONDUIT BENDS FOR FEEDERS, TELEPHONE AND COMMUNICATION CIRCUITS SHALL NOT BE LESS THAN LONG <br />RADIUS BENDS. <br />G.O.Z. TYPE DX, TX, OR AX CONDUIT EXPANSION DEFLECTION FITTINGS ARE REQUIRED IN ALL CONDUIT RUNS <br />WHERE MOVEMENT MAY BE ENCOUNTERED. ALL EMT COUPLINGS SHALL BE COMPRESSION TYPE. <br />H.EXPOSED CONDUIT SHALL BE SECURELY SUPPORTED IN PLACE PER CODE BUT ON A MAXIMUM OF 10 FOOT <br />INTERVALS, WITHIN THREE FEET OF EACH BEND, AT EVERY OUTLET OR JUNCTION BOX AND AT THE END OF <br />EACH STRAIGHT RUN TERMINATING AT A BOX OR CABINET. CONDUIT SHALL NOT BE SUPPORTED FROM <br />DUCTWORK OR PIPE WORK. CONDUITS SHALL BE RUN PARALLEL TO AND AT RIGHT ANGLES TO THE BUILDING <br />LINES. GENERALLY, CONDUIT SHALL BE RUN IN CONTACT WITH STRUCTURAL PARTS OF THE BUILDING SO AS <br />TO AVOID SUSPENDED LENGTHS OF CONDUIT. CONDUIT SHALL BE INSTALLED AS TO BE ACCESSIBLE FOR <br />REPLACEMENT AND MAINTENANCE AND GENERALLY CONDUIT SHALL BE INSTALLED TO PERMIT DRAINAGE. <br />5. WIRE AND CABLE <br />A.ALL WIRE AND CABLE SHALL BE COPPER AND RUN IN CONDUIT. ALL WIRE AND CABLE FEEDERS AND BRANCH <br />CIRCUITS SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE CURRENT EDITION OF THE C.E.C. AND <br />SHALL MEET ALL ASTM SPECIFICATIONS. WIRE AND CABLE SHALL BE NEW, SHALL HAVE SIZE, GRADE OF <br />INSULATION VOLTAGE AND MANUFACTURER'S NAME PERMANENTLY MARKED ON OUTER COVERING AT <br />REGULAR INTERVAL AND SHALL BE DELIVERED IN COMPLETE COILS OR REELS WITH IDENTIFYING SIZE AND <br />INSULATION TAGS. <br />B.THE ELECTRICAL CONTRACTOR SHALL CALCULATE VOLTAGE DROP ON CONDUCTORS WITH LENGTHS <br />GREATER THAN 75 FEET FROM THE PANELBOARD AND PROPERLY SIZE THE CONDUCTORS PER C.E.C. <br />C.POWER CONDUCTORS: NO WIRE LESS THAN NO. 12 SHALL BE USED EXCEPT FOR CONTROL CIRCUITS OR <br />LOW VOLTAGE WIRING. WIRE SIZES NO. 12 TO NO. 10 SHALL BE SOLID EXCEPT WHERE OTHERWISE <br />INDICATED. WIRE SIZES NO. 8 AND LARGER SHALL BE STRANDED. ALL WIRE SIZES SHOWN ARE AMERICAN <br />WIRE GAUGE SIZES. SIZES NO. 12 AWG THROUGH NO. 8 AWG SHALL BE "THHN." SIZE 4 AWG AND LARGER <br />SHALL BE "THW." <br />D.CONTINUITY: ALL WIRES SHALL BE CONTINUOUS FROM OUTLET TO OUTLET. <br />E.ACCEPTABLE MANUFACTURERS: CABLE AND WIRE SHALL BE STANDARD TYPE AS MANUFACTURED BY <br />GENERAL CABLE COMPANY, CAROL, ANACONDA, ROM OR ITT ROYAL. <br />6. COLOR CODING <br />A.A COLOR CODING SYSTEM AS LISTED BELOW SHALL BE FOLLOWED THROUGHOUT FOR FEEDERS AND <br />BRANCH CIRCUITS AND USED AS A BASIS FOR BALANCING LOAD. <br />--120/208V:PHASE A--BLACK, PHASE B--RED, PHASE C--BLUE, NEUTRAL--WHITE, GROUND--GREEN <br />--277/480V:PHASE A--BROWN, PHASE B--ORANGE, PHASE C--YELLOW, NEUTRAL--GRAY, GROUND--GREEN <br />7. BOXES AND FITTINGS <br />A.ALL OUTLETS SHALL BE PROVIDED WITH GALVANIZED OR SHERARDIZED BOXES SUITABLE IN DESIGN TO THE <br />SPACE THEY OCCUPY AND THE PURPOSE THEY SERVE. WALL MOUNTED OUTLET BOXES, EXCEPT FOR 2" <br />PARTITIONS SHALL BE AT LEAST 1 1/2" DEEP AND/OR DEEPER IF REQUIRED BY THE DEVICE THEY HOLD OR <br />THE CALIFORNIA ELECTRICAL CODE. <br />B.ALL PULLBOXES SHALL BE MADE OF GALVANIZED STEEL, OF METAL GAUGE AND PHYSICAL SIZE AS REQUIRED <br />BY THE C.E.C. FOR THE NUMBER AND SIZE OF RACEWAYS AND CONDUCTORS INVOLVED. <br />C.FIXTURE OUTLET BOXES IN OR ON CEILINGS SHALL NOT BE LESS THAN 1-1/2" DEEP OR LESS THAN 4" SQUARE. <br />ALL OUTLET BOXES INTENDED TO SUPPORT FIXTURES SHALL BE EQUIPPED WITH 3/8" FIXTURE STUDS <br />FASTENED THROUGH THE BOTTOM OF THE BOX WITH FOUR BOLTS. <br />8. CIRCUIT BREAKER PANELBOARDS <br />A.PANELS SHALL BE DEAD FRONT, SAFETY TYPE, FURNISHED WITH BRANCH CIRCUIT PROTECTING DEVICES, <br />EQUIPMENT GROUNDING BOX, MAIN BUS AND CABLE LUGS FACTORY ASSEMBLED, WITH ALL COMPONENTS IN <br />PLACE, READY FOR INSTALLATION. <br />B.CURRENT CARRYING CONTACT SURFACES SHALL BE SILVER OR TIN PLATED. THE CIRCUIT BREAKERS SHALL <br />BE OF THE MOLDED CASE, PLUG-IN TYPE SUITABLE FOR VOLTAGE AND AMPERE RATINGS INDICATED ON <br />DRAWINGS AND IN SCHEDULES AND SHALL HAVE A MINIMUM INTERRUPTING CAPACITY OF 22,000 AMPERES <br />FOR 120/208V AND 25,000 AMPERES AT 277/480V. <br />C.MAIN BUSES AND CONNECTORS SHALL BE HARD DRAWN COPPER OF 98% CONDUCTIVITY, WITH CURRENT <br />CARRYING CAPACITY TO MAINTAIN ESTABLISHED RISE TESTS AS DEFINED IN UL STANDARD UL 67. <br />D.CABINET SIZES ARE BASED UPON A 20" WIDE BY 6" DEEP PANEL UNLESS OTHERWISE NOTED. PANELBOARDS <br />SHALL BE EQUIPPED WITH FLUSH TYPE LOCK AND CATCH. ALL LOCKS SHALL BE KEYED ALIKE, AND TWO KEYS <br />ARE TO BE SUPPLIED WITH EACH LOCK. <br />E.BREAKERS SERVING LIGHTING CIRCUITS SHALL BE RATED FOR SWITCH DUTY. <br />F.BREAKERS SERVING COOLER, FREEZER AND HVAC EQUIPMENT SHALL BE HACR RATED. <br />G.ALL LUGS SHALL BE OF THE SOLDERLESS TYPE AND RATED AT A MINIMUM OF 75 DEGREES. <br />H.PROVIDE PANEL DIRECTORY, TYPED AND INSTALLED BEHIND CLEAR PLASTIC COVER ON INSIDE OF THE DOOR. <br />I.PANELBOARDS TO BE BY SQUARE D, GENERAL ELECTRIC, SIEMENS OR EATON. <br />9. TRANSFORMERS <br />A.DRY-TYPE TRANSFORMERS (DOE 2016) SHALL BE OF THE ENCLOSED VENTILATED TYPE WITH KVA AND <br />VOLTAGE RATING AS CALLED FOR ON THE DRAWINGS AND WITH 150° CLASS H INSULATION AND MINIMUM OF <br />SIX STANDARD FULL CAPACITY TAPS. SOUND LEVEL SHALL BE LOW AND INSTALLATION SHALL INCLUDE <br />KORFUND OR EQUAL VIBRATION DAMPENING MOUNTS AND FLEXIBLE STEEL CONDUIT FOR PRIMARY AND <br />SECONDARY. (MOUNT TRANSFORMER ON VIBRATION ISOLATORS). LOCATE TRANSFORMER AS NOT TO CAUSE <br />SERVICING OR CLEARANCE DIFFICULTIES OF VIOLATIONS WITH OTHER EQUIPMENT. <br />B.COMPARABLE EQUIPMENT AS MANUFACTURED BY SQUARE D, GENERAL ELECTRIC, SIEMENS OR EATON. <br />10. TOGGLE SWITCHES <br />A.TOGGLE SWITCHES SHALL BE WHITE AND SHALL BE RATED 20 AMPERES 120/277 VOLT AC TYPE AS <br />MANUFACTURED BY HUBBELL AND SHALL BE AS FOLLOWS: <br />SINGLE POLE - 1221-W <br />THREE WAY - 1223-W <br />B.TOGGLE SWITCHES SHALL BE MOUNTED 4'-0" ABOVE FINISHED FLOOR TO TOP OF MOUNTING PLATE AND, AT <br />DOORS, INSTALLED ADJACENT TO THE TRIM ON THE STRIKING SIDE OF THE DOOR, REGARDLESS OF THE <br />LOCATION INDICATED ON THE DRAWINGS; THEREFORE, CHECK ALL DOOR SWINGS BEFORE INSTALLATION OF <br />CONDUIT OUTLETS. <br />C.COMPARABLE EQUIPMENT AS MANUFACTURED BY COOPER WIRING, SLATER, LEVITON, AND BRYANT WILL BE <br />ACCEPTABLE. <br />11. RECEPTACLES <br />A.RECEPTACLES SHALL BE WHITE AS MANUFACTURED BY HUBBELL AND SHALL BE AS FOLLOWS: <br />DUPLEX RECEPTACLE - 20A-125 VOLT 5362-W <br />GFCI DUPLEX RECEPTACLE - 20A-125 VOLT GF5362-W <br />B.RECEPTACLES SHALL BE MOUNTED 18" ABOVE THE FINISHED FLOOR TO BOTTOM OF BOX UNLESS <br />OTHERWISE NOTED. <br />C.COMPARABLE EQUIPMENT AS MANUFACTURED BY COOPER WIRING, SIERRA ELECTRIC CORPORATION, <br />SLATER, BRYANT AND LEVITON WILL BE ACCEPTABLE. <br />12. DEVICE PLATES <br />A.DEVICE PLATES SHALL BE STAINLESS STEEL UNLESS OTHERWISE NOTED. COMPARABLE EQUIPMENT AS <br />MANUFACTURED BY COOPER WIRING, SIERRA ELECTRIC CORPORATION, HARVEY HUBBLE INC., BRYANT AND <br />LEVITON WILL BE ACCEPTABLE. PAINT MATCH ADJACENT FINISH COLOR. <br />13. DISCONNECT SWITCHES <br />A.FURNISH AND INSTALL DISCONNECT SWITCHES AS REQUIRED BY CODE. DISCONNECT SWITCHES SHALL BE <br />NEMA HEAVY DUTY TYPE AND UNDERWRITERS LABORATORIES LISTED, MANUFACTURED BY SQUARE D, <br />GENERAL ELECTRIC, EATON OR SIEMENS. <br />14. FUSES <br />A.PROVIDE CARTRIDGE FUSES RATED FOR 250 V AC AND 600 V AC AND LESS FOR USE AS SPECIFIED HEREIN. <br />B.COORDINATE FUSE RATINGS WITH UTILIZATION EQUIPMENT NAMEPLATE LIMITATIONS OF MAXIMUM FUSE SIZE <br />AND WITH SYSTEM SHORT-CIRCUIT CURRENT LEVELS. <br />C.CARTRIDGE FUSE APPLICATIONS: <br />1.FEEDERS, UP TO AND INCLUDING 600 AMPS: CLASS RK1, BUSSMANN LPN-RK-SP FOR 250 VOLTS, <br />BUSSMANN LPS-RK-SP FOR 600 VOLTS . <br />2.FEEDERS, FROM 601 AMPS TO 4,000 AMPS: CLASS RK1, BUSSMANN KRP-C FOR UP TO 600 VOLTS, <br />BUSSMANN . <br />D.BASIS OF DESIGN FOR FUSES SHALL BE BUSSMANN. ADDITIONAL ACCEPTABLE MANUFACTURERS FOR <br />SPECIFIED FUSES SHALL BE LITTLEFUSE AND MERSEN <br />1. GENERAL <br />A.WINGSTOP'S GC TO COORDINATE ALL LOCAL FIRE ALARM REQUIREMENTS WITH LOCAL FIRE MARSHALL AND <br />PROVIDE ALL DEVICES REQUIRED FOR A COMPLETE SYSTEM. <br />B.WINGSTOP'S GC SHALL VERIFY MANUFACTURER AND MODEL OF LANDLORD'S EXISTING FIRE ALARM SYSTEM. <br />C.WINGSTOP'S GC SHALL COORDINATE REQUIREMENTS WITH LANDLORD'S FIRE ALARM VENDOR. <br />D.WINGSTOP'S GC SHALL VERIFY ALL FIRE ALARM DEVICES THAT ARE EXISTING TO REMAIN ARE IN PROPER <br />WORKING CONDITION. REPLACE ANY FAULTY DEVICES AS REQUIRED FOR A COMPLETE AND OPERATIONAL <br />SYSTEM. <br />E.ALL FIRE ALARM WORK SHALL BE PERFORMED BY A LANDLORD APPROVED FIRE ALARM CONTRACTOR. <br />F.WINGSTOP'S GC IS RESPONSIBLE FOR FIRE ALARM PERMIT. IT IS THE TENANTS CONTRACTOR'S <br />RESPONSIBILITY TO OBTAIN ALL REQUIREMENTS PRIOR TO SUBMISSION FOR PERMIT. <br />SECTION 16700 <br />FIRE ALARM SPECIAL CONDITIONS (WHERE REQUIRED) <br />15. GROUNDING <br />A.CONTRACTOR SHALL INSTALL GROUNDING PER C.E.C. ARTICLE 250 EQUIPMENT GROUNDING SHALL USE ONLY <br />APPROVED GROUNDING CLAMPS AND CONNECTORS AS MANUFACTURED BY PENN-UNION, BURNDY, OR O-Z <br />MFG. COMPANY. <br />B.GROUNDING SHALL BE INSTALLED IN ACCORDANCE WITH THE C.E.C. ARTICLE 250 AND THE UTILITY COMPANY <br />REGULATIONS. CONTRACTOR SHALL CONNECT THE GROUNDING ELECTRODE CONDUCTORS TO THE NEUTRAL <br />BAR INSIDE THE MAIN PANEL. <br />C.THE EQUIPMENT GROUNDING SYSTEM SHALL CONSIST OF A CONTINUOUS CONDUIT INSTALLATION AND A <br />GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR. THIS GROUNDING CONDUCTOR SHALL BE <br />INSTALLED IN EVERY CONDUIT OR RACEWAY WITH THE FEEDER OR BRANCH CIRCUIT CONDUCTORS. THIS <br />GROUNDING SHALL BE EXTENDED FROM THE HOUSING OF EVERY ELECTRICAL LOAD, THROUGH PANELBOARD <br />STATIC GROUNDING BUSSES, TO THE STATIC GROUNDING BUS IN THE MAIN PANEL. THE GROUNDING BUS <br />SHALL BE BONDED TO THE GROUNDING NEUTRAL BAR INSIDE THE MAIN PANEL. <br />16. LIGHTING FIXTURES <br />A.ALL LIGHTING FIXTURES AND LAMPS SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR, UNLESS NOTED <br />OTHERWISE, THIS CONTRACTOR SHALL INSTALL LIGHTING FIXTURES AND LAMPS AS INDICATED ON THE <br />DRAWINGS AND AS SPECIFIED BELOW, COMPLETE WITH HANGERS, PLASTER FRAMES AND ALL OTHER <br />NECESSARY ACCESSORIES. <br />B.LED LUMINAIRES <br />14.LED FIXTURES SHALL COMPLY WITH IES LM-79-08 APPROVED METHOD FOR MEASURING LUMEN MAINTENANCE OF <br />LED LIGHT SOURCES, COMPLY WITH IES LM-80-08 APPROVED FOR ELECTRICAL AND PHOTOMETRIC MEASUREMENT <br />OF SSL PRODUCT, COMPLY WITH IN-SITU TESTING FOR MORE RELIABLE RESULTS. <br />15.LED'S SHALL BE RESTRICTED OF HAZARDOUS SUBSTANCES DIRECTIVE (ROHS) COMPLIANT. <br />16.LED ARRAYS SHALL BE SEALED, HIGH PERFORMANCE, LONG LIFE TYPE; MINIMUM 70% RATED OUTPUT AT 50,000 <br />HOURS. <br />17.LUMINAIRES SHALL BE FULLY ACCESSIBLE FROM BELOW CEILING PLANE FOR CHANGING DRIVERS, POWER <br />SUPPLIES AND ARRAYS. <br />18.DRIVERS SHALL BE SOLID STATE AND ACCEPT 120 THROUGH 277 VAC AT 60 HZ INPUT. <br />19.THE LED LIGHT SOURCE SHALL BE FULLY DIMMABLE WITH USE OF COMPATIBLE DIMMERS SWITCH DESIGNATED <br />FOR LOW VOLTAGE LOADS. <br />20.LED COLOR TEMPERATURES: SHALL BE AS NOTED ON DRAWING. <br />21.LUMINAIRES SHALL HAVE INTERNAL THERMAL PROTECTION. <br />22.INDOOR LUMINAIRES SHALL HAVE A MINIMUM CRI OF 85. <br />C.LED POWER SUPPLIES AND DRIVERS <br />1.SHALL HAVE A POWER FACTOR: 0.90 OR HIGHER. <br />D.CONTROLLER AND CONTROL SYSTEMS <br />1.THE CONTRACTOR SHALL ENSURE THAT EXTERNAL CONTROL EQUIPMENT IS COMPATIBLE WITH LED CONTROL <br />REQUIREMENTS. <br />2.PROVIDE CONNECTOR TYPES AND WIRING AS APPROPRIATE FOR UN-INTERRUPTED COMMUNICATION BETWEEN <br />DEVICES, CONSIDERING DISTANCE MAXIMUMS, FIELD OBSTRUCTIONS, AND ACCESSIBILITY. <br />3.ENSURE THAT CONNECTION POINTS ARE OPTICALLY ISOLATED FOR SYSTEM NOISE REDUCTION. FOR CONTROL <br />COMPONENTS THAT ARE PART OF THE OVERALL AREA CONTROL SYSTEM. SEE DIMMING CONTROLS <br />SPECIFICATIONS. COMPATIBILITY: CERTIFIED BY MANUFACTURER FOR USE WITH INDIVIDUALLY SPECIFIED <br />LUMINAIRE AND INDIVIDUALLY SPECIFIED POWER SUPPLIES AND/OR DRIVERS. <br />E.THIS CONTRACTOR SHALL VERIFY THE FINAL CEILING AND FINISH SCHEDULES TO ENSURE THE PROPER <br />INSTALLATION AND MOUNTING OF FIXTURES AND SHALL COORDINATE BEFORE MAKING SUBMITTALS. <br />17. LIGHTING CONTROLS <br />A.TIME SWITCHES SHALL BE 24 HOUR, 7 DAY, DAY SKIPPER 365 DAYS AND HOLIDAYS TYPE EQUAL TO <br />INTERMATIC ET2825C TIME SWITCH. CONTACTOR SHALL BE SQUARE D LXG-xx IN NEMA 1 ENGLOSURE. <br />B.PANEL #GR1408LTENC-xMNE1-GR1408-DTCMOD WITH 8 RELAYS AND BUILT-IN TIME CLOCK AND AS <br />MANUFACTURED BY LC&D. <br />18.TELEPHONE SERVICE <br />A.THIS CONTRACTOR SHALL INSTALL A TELEPHONE SERVICE CONDUIT AS SHOWN ON THE DRAWINGS AND <br />FURNISH AND INSTALL (1) 3' x 4' x 3/4" PLYWOOD PANEL MOUNTED ON THE WALL AT LOCATION SHOWN ON <br />PLANS. <br />18. SURFACE METAL RACEWAY <br />A.SURFACE METAL RACEWAY SHALL BE TWO PIECE #2100 AS MANUFACTURED BY WIREMOLD. ALL NECESSARY <br />ACCESSORIES REQUIRED TO FIT THE CONFIGURATION SHOWN SHALL BE PROVIDED. RECEPTACLES SHALL BE <br />120 VAC, 23 APMS, CATALOG NUMBER #2127GT. <br />DATE <br />FOR PERMIT & BID 01-25-22 <br />SEAL: <br />PROJECT LOCATION: <br />SHEET NUMBER: <br />REVISION:DATE: <br />CHECKED BY: <br />ISSUE: <br />DRAWN BY: <br />PROJECT NO.: <br />DATE: <br />PROJECT INFORMATION: <br />CLIENT: <br />CONSULTANT: <br />THESE DRAWINGS, IDEAS, SPECIFICATIONS AND <br />DESIGNS ARE EXCLUSIVE PROPERTY OF WINGSTOP <br />RESTAURANTS, INC. NO PART OF THESE DRAWINGS <br />MAY BE COPIED, REPRODUCED, OR OTHER <br />STRUCTURES BUILT FROM SUCH WITHOUT THE <br />WRITTEN CONSENT OF WINGSTOP RESTAURANTS, INC. <br />COPYRIGHT R 2022 <br />WINGSTOP RESTAURANTS, INC. <br />ALL RIGHTS RESERVED <br />15505 WRIGHT BROTHERS DRIVE <br />ADDISON, TX 75001 <br />TELEPHONE: (972) 686-6500 <br />FAX: (972) 686-6502 <br />DISCLAIMER: <br />STOCKTON, CA <br />2021-0486STORE NUMBER: GL#Z060GILL GROVE1687 N CALIFORNIA STREET SUITE #TBDSTOCKTON, CA 95204JJV <br />DRC <br />1/20/22 796 Merus CourtSt. Louis, MO 63026T 636.349.1600F 636.349.1730