<br />SECTION 16200
<br />SECTION 16100
<br />DIVISION 16 - ELECTRICAL SPECIFICATIONS
<br />ELECTRICAL SPECIAL CONDITIONS
<br />ELECTRICAL POWER AND LIGHTING
<br />1. GENERAL
<br />A.APPLICABLE PROVISIONS OF AIA DOCUMENT A201, "GENERAL CONDITIONS OF THE CONTRACT FOR
<br />CONSTRUCTION", AND DIVISION 1 GENERAL CONDITIONS GOVERN WORK UNDER THIS SECTION AND ALL
<br />OTHER SECTIONS OF DIVISION 16.
<br />B.APPLICABLE PROVISIONS OF THIS SECTION GOVERN WORK UNDER ALL OTHER SECTIONS OF DIVISION 16.
<br />WORK COVERED BY THIS SECTION SHALL CONSIST OF PROVIDING ALL MATERIAL, LABOR, EQUIPMENT AND
<br />SERVICES NECESSARY FOR A COMPLETE, TESTED AND ADJUSTABLE ELECTRICAL INSTALLATION READY FOR
<br />OPERATION AS SPECIFIED HEREIN AND AS SHOWN ON THE DRAWINGS.
<br />C.THE TERM CONTRACTOR AS USED IN THIS SECTION SHALL MEAN ANY CONTRACTOR OR SUBCONTRACTOR
<br />WHO HAS CONTRACTED TO PERFORM WORK INCLUDED IN AND DEFINED BY THIS SECTION AND ALL OTHER
<br />SECTIONS OF DIVISION 16.
<br />D.PROVIDE ALL LABOR, MATERIALS, EQUIPMENT AND TOOLS TO PERFORM ELECTRICAL WORK SHOWN, NOTED
<br />OR SCHEDULED FOR A COMPLETE AND FINISHED INSTALLATION. ALL MATERIALS AND EQUIPMENT SHALL BE
<br />COMMERCIAL GRADE AND SHALL CARRY A U.L. LABEL.
<br />E.MATERIALS, PRODUCTS AND EQUIPMENT, INCLUDING COMPONENTS THEREOF SHALL BE NEW AND SUCH AS
<br />APPEARS ON THE UNDERWRITER'S LABORATORY LIST OF APPROVED ITEMS AND SHALL MEET THE
<br />REQUIREMENTS OF RECOGNIZED STANDARDS. EQUIPMENT SHALL BE SIZED IN CONFORMITY WITH
<br />REQUIREMENTS OF THE CALIFORNIA ELECTRICAL CODE (C.E.C.) AND OTHER APPLICABLE CODES.
<br />2. EXISTING CONDITIONS
<br />A.THESE DRAWINGS ARE BASED ON INFORMATION PROVIDED TO OUR OFFICE AT THE TIME OF DESIGN.
<br />THEREFORE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY ALL EXISTING CONDITIONS INCLUDING BUT
<br />NOT LIMITED TO, SERVICE LOCATION, SERVICE LAYOUTS, SECONDARY FEEDER LENGTH, TELEPHONE
<br />SERVICE LOCATION, ETC... AND REPORT ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO BID. FAILURE TO
<br />DO SO MAY CONSTITUTE THAT THE CONTRACTOR PROVIDE ANY AND ALL ADDITIONAL EQUIPMENT, LABOR,
<br />ETC... TO MEET THE INTENDED DESIGN PARAMETERS.
<br />B.CONTRACTORS SHALL VISIT THE SITE PRIOR TO BIDDING. BIDS SHALL SERVE AS EVIDENCE OF KNOWLEDGE
<br />OF EXISTING CONDITIONS.
<br />3. CONTRACTOR'S RESPONSIBILITY
<br />A.PRIOR TO SUBMITTING HIS BID, CONTRACTOR SHALL CAREFULLY EXAMINE THESE CONSTRUCTION
<br />DOCUMENTS, THE DEVELOPER'S EXHIBITS, AND THE SITE, TO INQUIRE FULLY INTO DIFFICULTIES AND COSTS
<br />OF WORK, AND TO DETERMINE THE SCOPE AND CHARACTER OF WORK TO BE DONE. CONTRACTOR SHALL
<br />INCLUDE ALL NECESSARY COSTS TO LOCATE AND/OR EXTEND ALL UTILITIES INCLUDING LIGHTING PANELS,
<br />POWER PANELS, ELECTRICAL SERVICE, PHONE SERVICE AND/OR MODIFY EQUIPMENT TO MEET THE INTENT
<br />OF THE CONTRACT DOCUMENTS. THE OWNER, OWNER'S AGENT, ARCHITECT, ENGINEER OR DESIGNER SHALL
<br />NOT BE RESPONSIBLE FOR FAILURE OF THE CONTRACTOR TO DETERMINE DIFFICULTIES AND COSTS IN THE
<br />PROJECT OR FOR HIS OVERLOOKING OF THE REQUIREMENTS.
<br />B.IF THIS CONTRACTOR DOES NOT CLEARLY UNDERSTAND THE PLANS AND SPECIFICATIONS, OR IF THERE ARE
<br />ANY REQUIREMENTS WHICH ARE AMBIGUOUS IN THE CONTRACTOR'S OPINION, HE SHOULD CALL THIS TO THE
<br />ATTENTION OF THE ARCHITECT PRIOR TO BIDDING, SINCE THIS CONTRACTOR WILL BE HELD RIGIDLY TO THE
<br />INTERPRETATIONS OF THE ARCHITECT AND ENGINEER.
<br />C.CONTRACTOR SHALL SCHEDULE HIS WORK IN COOPERATION WITH OTHER TRADES INSTALLING
<br />INTERRELATED WORK. ALL WORK SHALL BE SCHEDULED TO MAINTAIN SERVICE TO ALL REQUIRED AREAS
<br />DURING THE COURSE OF THE CONSTRUCTION EXCEPT FOR SHORT TERM PLANNED SHUTDOWNS, ANY OF
<br />WHICH SHALL BE PRE-SCHEDULED WITH THE OWNERS AGENT AND THE LANDLORD.
<br />4. WORKMANSHIP AND GUARANTEE
<br />A.IN ENTERING INTO A CONTRACT COVERING THIS WORK, THE CONTRACTOR ACCEPTS THE SPECIFICATIONS,
<br />AND GUARANTEES THAT THE WORK WILL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF
<br />THE CONTRACT DOCUMENTS. CONTRACTOR FURTHER GUARANTEES THAT THE WORKMANSHIP AND
<br />MATERIAL WILL BE OF THE BEST PROCURABLE AND THAT NONE BUT EXPERIENCED WORKMEN EXPERIENCED
<br />IN EACH PARTICULAR CLASS OF WORK WILL BE EMPLOYED. CONTRACTOR FURTHER GUARANTEES TO
<br />REPLACE AND MAKE GOOD AT HIS OWN EXPENSE ANY DEFECTS DUE TO FAULTY WORKMANSHIP OR
<br />MATERIAL WHICH MAY DEVELOP WITHIN ONE (1) YEAR AFTER FINAL PAYMENT AND ACCEPTANCE BY THE
<br />ARCHITECT.
<br />5. CODES AND STANDARDS
<br />A.CONTRACTOR WILL COMPLY IN ALL RESPECTS WITH THE ADOPTED BUILDING CODES, APPLICABLE LAWS,
<br />ORDINANCES, AND REGULATIONS AS MAY APPLY ACCORDING TO THE RULING OF THE CONTROLLING PUBLIC
<br />OFFICIAL SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE
<br />REQUIREMENTS OF THE APPLICABLE LAWS, ORDINANCES AND REGULATIONS, OR WHICH DOES NOT RECEIVE
<br />THE APPROVAL OF THE CONTROLLING PUBLIC OFFICIAL, HE SHALL BEAR ALL COSTS ARISING IN CORRECTING
<br />THE DEFICIENCIES. ALL ELECTRICAL EQUIPMENT SHALL SHALL BEAR THE UNDERWRITER'S LABORATORY
<br />LABEL.
<br />6. FEES ON PERMITS
<br />A.CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND MAKING PAYMENT FOR ALL FEES, PERMITS AND
<br />INSPECTIONS RELATING TO HIS WORK.
<br />7. CONTRACT DRAWINGS
<br />A.THE DRAWINGS SHOW THE GENERAL ARRANGEMENT AND INTENT OF THE DESIGN AND SHALL BE FOLLOWED
<br />AS CLOSELY AS ACTUAL BUILDING CONDITIONS AND THE WORK OF OTHER TRADES WILL PERMIT. BECAUSE
<br />OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, FITTINGS, AND
<br />ACCESSORIES WHICH MAY BE REQUIRED, NOR IS IT IMPLIED THAT ALL CONFLICTS BETWEEN VARIOUS
<br />ELEMENTS OF THE SYSTEMS OR BUILDING COMPONENTS HAVE BEEN INDICATED. THE CONTRACTOR SHALL
<br />INVESTIGATE ALL EXISTING CONDITIONS AFFECTING THE WORK AND ARRANGE HIS WORK ACCORDINGLY,
<br />PROVIDING SUCH FITTINGS, OFFSETS, ACCESSORIES AND DEVICES AS MAY BE REQUIRED. THE DRAWINGS
<br />AND SPECIFICATIONS ARE MUTUALLY COMPLEMENTARY, AND ANY WORK REQUIRED BY ONE BUT NOT BY THE
<br />OTHER SHALL BE PERFORMED BY BOTH. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL
<br />MATERIALS AND SERVICES REQUIRED FOR A COMPLETE AND WORKING PROJECT AT NO ADDITIONAL COST
<br />EVEN THOUGH EACH AND EVERY NECESSARY ELEMENT THEREOF IS NOT SPECIFICALLY IDENTIFIED HEREIN
<br />EACH AND EVERY NECESSARY ELEMENT THEREOF IS NOT SPECIFICALLY IDENTIFIED HEREIN.
<br />B.CONTRACTOR SHALL NOT SCALE FROM THE DRAWINGS BUT SHALL FOLLOW THE ARCHITECTURAL DRAWINGS
<br />OR EXISTING BUILDING CONDITIONS WHERE APPLICABLE, IN ESTABLISHING DIMENSIONS AND LINES OF RUN,
<br />SINCE DIMENSIONS ON THE FINAL ARCHITECTURAL DRAWINGS OR AT THE SITE MAY NOT COINCIDE WITH
<br />THOSE SHOWN ON THE ELECTRICAL DRAWINGS, THE CONTRACTORS SHALL VERIFY WITH THE DIMENSIONED
<br />ARCHITECTURAL DRAWINGS OR THE SITE CONDITIONS THE EXACT MATERIAL QUANTITIES AND LENGTHS
<br />NECESSARY.
<br />C.SIGNIFICANT DEVIATIONS OR CHANGES FROM THE DRAWINGS WHICH ARE REQUIRED TO ACCOMPLISH THE
<br />INTENT OF THE CONTRACT DOCUMENTS MUST BE REVIEWED WITH THE ARCHITECT AND APPROVED BEFORE
<br />PROCEEDING.
<br />8. SHOP DRAWINGS
<br />A.CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, FOUR (4) COPIES MINIMUM, FOR ALL MANUFACTURED
<br />PRODUCTS. EACH SHOP DRAWING SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO
<br />ASSURE THAT ALL DIMENSIONS, QUANTITIES, CONNECTIONS, CAPACITATES AND ACCESSORIES SHOWN ARE
<br />IN CONFORMANCE WITH THE CONTRACT DOCUMENTS, AND SHALL BE MARKED OR STAMPED TO CONFIRM
<br />THAT SUCH REVIEW WAS MADE AND COMPLIANCE WAS CONFIRMED.
<br />B.APPROVAL OF SHOP DRAWINGS BY THE OWNER, OWNER'S AGENT, ARCHITECT, ENGINEER OR DESIGNER,
<br />WILL NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF COMPLYING WITH ALL TERMS OF THE
<br />CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR PERFORMANCE OF ALL
<br />EQUIPMENT PURCHASED, FOR PROPER FIT, AND OTHER DIMENSIONAL REQUIREMENTS.
<br />9. RECORD DRAWINGS
<br />A.CONTRACTOR SHALL MAINTAIN AT THE JOB SITE ONE SET OF DOCUMENTS AS "RECORD DRAWINGS" FOR THE
<br />PURPOSE OF DAILY MARKING OF ALL SUBSTANTIAL REVISIONS TO THE DOCUMENTS INCLUDING BUT NOT
<br />LIMITED TO ELECTRICAL CHANGES, AND LOCATIONS OF UTILITIES, PANELBOARDS, DISCONNECTS, STARTERS
<br />AND OTHER DEVICES REQUIRING PERIODIC OPERATIONAL ATTENTION, ADJUSTMENT, OR SERVICE INCLUDING
<br />ACCESS THERETO, AT THE COMPLETION OF THE PROJECT, THIS SET SHALL BE RETURNED TO THE
<br />ARCHITECT FOR THE PURPOSE OF MAKING FINAL "AS-BUILT DRAWINGS".
<br />10. EQUIPMENT SUBSTITUTION
<br />A.SPECIFIC MANUFACTURERS AND MODELS OF EQUIPMENT HAVE BEEN USED IN THE DEVELOPMENT OF THE
<br />DRAWINGS AND DESIGNS. THIS CONTRACTOR MUST SUBMIT TO THE OWNER ANY CHANGES AND/OR
<br />SUBSTITUTIONS FOR APPROVAL PRIOR TO INSTALLATION OR EXECUTION. ANY CHANGES WHICH DO NOT
<br />RECEIVE THE OWNER'S APPROVAL MAY BE SUBJECT TO REMOVAL OR REPLACEMENT AS ORIGINALLY
<br />SPECIFIED, AND WILL BE AT THE CONTRACTOR'S EXPENSE.
<br />B.IF THIS CONTRACTOR SUBSTITUTES FOR SPECIFIED EQUIPMENT ANY OTHER EQUIPMENT WHICH REQUIRES
<br />ANY CHANGES TO THE DESIGN, ALL COST OF REDESIGN AND RECONFIGURATION RESULTING FROM SAID
<br />SUBSTITUTION SHALL BE BORNE BY THE SUBMITTING CONTRACTOR.
<br />11. EQUIPMENT INSTALLATION AND SUPPORT
<br />A.CONTRACTOR SHALL SUPPORT PLUMB, RIGID AND TRUE-TO-LINE ALL WORK AND EQUIPMENT INSTALLED.
<br />THIS CONTRACTOR SHALL DETERMINE HOW EQUIPMENT, FIXTURES, ETC., ARE TO BE SUPPORTED, MOUNTED,
<br />OR SUSPENDED AND SHALL PROVIDE ACCESSORIES REQUIRED FOR PROPER SUPPORT WHETHER SHOWN ON
<br />THE DRAWINGS OR NOT. IF SUPPORTS ARE REQUIRED, CONTRACTOR SHALL SUBMIT DRAWINGS TO THE
<br />ARCHITECT FOR APPROVAL.
<br />C.ALL CONDUIT CONNECTING TO SWITCHGEAR, PANELS, MOTORS, AND OTHER EQUIPMENT SHALL BE
<br />INSTALLED WITHOUT STRAIN AT THE CONNECTIONS. THE CONTRACTOR MAY BE REQUIRED, AS DIRECTED, TO
<br />DISCONNECT CONDUITS TO DEMONSTRATE THAT THEY HAVE BEEN SO CONNECTED.
<br />12. DEMOLITION
<br />A.ALL EXISTING EQUIPMENT, NOT INDICATED TO BE INCORPORATED INTO THE NEW SYSTEM SHALL BE
<br />DISCONNECTED BY THIS CONTRACTOR FOR REMOVAL BY OTHERS FROM THE JOB SITE. CARE SHALL BE USED
<br />SO THAT NO DAMAGE IS DONE TO EXISTING BUILDING, PIPING, DUCTWORK, AND/OR ELECTRICAL EQUIPMENT.
<br />ANY DAMAGE ATTRIBUTED TO THIS CONTRACTOR SHALL BE REPAIRED OR REPLACED BY THIS CONTRACTOR.
<br />13. CUTTING AND PATCHING
<br />A.ALL CUTTING THAT MAY BE NECESSARY FOR THE INSTALLATION OF THE WORK OR ANY REQUIRED PATCHING
<br />THAT RESULTS THEREFROM SHALL BE DONE BY THE PROPER TRADE INVOLVED AND SHALL BE INCLUDED AS
<br />PART OF THIS CONTRACT. PATCH TO DUPLICATE UNDISTURBED ADJACENT FINISHES, COLORS, TEXTURES
<br />AND PROFILES. COLUMNS, BEAMS, GIRDERS OR JOISTS SHALL NOT BE CUT.
<br />B.ALL WORK AFFECTING ROOF OR STRUCTURES SHALL BE PERFORMED BY LANDLORD'S CONTRACTOR AT
<br />TENANT'S EXPENSE.
<br />14. CLEANING
<br />A.COMPLETION AS IT PERTAINS TO THE CONTRACT COMPLETION DATE IS DEFINED AS THE DAY THE PROJECT IS
<br />TURNED OVER TO THE OWNER IN THOROUGHLY CLEAN CONDITION. READY FOR THE OWNER TO TAKE
<br />POSSESSION. ALL FIXTURES, MOTORS, EQUIPMENT AND ALL OTHER ELECTRICAL EQUIPMENT FURNISHED OR
<br />INSTALLED BY THE CONTRACTOR SHALL BE THOROUGHLY CLEANED.
<br />15. TESTS
<br />A.PROVIDE THE TESTS AS OUTLINED HEREINAFTER AND OTHER TESTS NECESSARY TO ESTABLISH THE
<br />ADEQUACY, QUALITY, SAFETY, COMPLETED STATUS AND SUITABLE OPERATION OF EACH SYSTEM. CORRECT
<br />PROMPTLY ANY FAILURE OR DEFECTS REVEALED BY THESE TESTS AND RECONDUCT TEST ON THE
<br />CORRECTED ITEMS.
<br />B.TEST THE GROUNDS WITH A GROUND RESISTANCE DIRECT READING SINGLE-TEST MEGGER.
<br />C.INSULATION RESISTANCE BETWEEN PHASE CONDUCTORS AND GROUND NOT LESS THAN 1,000,000 OHMS.
<br />D.THE PANELBOARDS SHALL HAVE PHASE CURRENTS BALANCED TO WITHIN +/- 10% VARIATION BETWEEN
<br />AVERAGE PHASE CURRENT AND MEASURED INDIVIDUAL PHASE.
<br />E.AN OPERATIONAL TEST OF THE EMERGENCY LIGHTS AND THE EXIT LIGHTS SHALL BE PERFORMED FOR THE
<br />OWNER TO DEMONSTRATE CONFORMANCE TO THE SPECIFICATIONS.
<br />16. TEMPORARY ELECTRICAL SERVICE
<br />A.TEMPORARY ELECTRICAL SERVICE SHALL BE IN ACCORDANCE WITH THE BUILDING CODE. TEMPORARY
<br />LIGHTING SHALL BE PROVIDED BY A LAMP LOCATED FOR EVERY 625 SQUARE FEET OF BUILDING AREA WITH A
<br />MINIMUM OF ONE PER ROOM. THE LAMP TO BE 100 WATT AND SHALL BE MAINTAINED BY THE GENERAL
<br />CONTRACTOR.
<br />B.TEMPORARY POWER DISTRIBUTION SHALL BE SUFFICIENT TO ACCOMMODATE THE TEMPORARY LIGHTING
<br />AND CONSTRUCTION OPERATIONS, INCLUDING THE USE OF POWER TOOLS (BUT NOT INCLUDING HEAVY-DUTY
<br />ELECTRICAL WELDING UNITS), ELECTRICAL HEATING UNITS, AND START-UP OF SPECIFIED BUILDING
<br />EQUIPMENT, WHICH IS TO BE TESTED, STARTED OR PLACED INTO OUR USE PRIOR TO COMPLETION OF ITS
<br />PERMANENT POWER CONNECTIONS.
<br />17. EXCAVATION AND BACKFILL
<br />A.CONTRACTOR SHALL DO ALL EXCAVATION REQUIRED AS SHOWN ON PLANS OR REQUIRED FOR PROPER
<br />OPERATION. EXCESS EXCAVATION BELOW THE REQUIRED LEVEL SHALL BE BACKFILLED WITH EARTH AND
<br />THOROUGHLY TAMPED. UTILITY SERVICES, SHALL BE INSPECTED AND APPROVED BY THE PROPER
<br />INSPECTION AUTHORITY BEFORE BACKFILLING.
<br />18. WEATHERPROOFING
<br />A.CONTRACTOR SHALL ENSURE ALL PENETRATIONS THROUGH EXTERIOR ENVELOPE ARE COMPLETELY SEALED
<br />AGAINST ALL AIR AND WATER INFILTRATION.
<br />1. RELATED DOCUMENTS
<br />A.APPLICABLE PROVISIONS OF AIA DOCUMENT A201, "GENERAL CONDITIONS OF THE CONTRACT FOR
<br />CONSTRUCTION", DIVISION 1 GENERAL CONDITIONS AND SECTION 16100 ELECTRICAL SPECIAL CONDITIONS
<br />GOVERN WORK UNDER THIS SECTION.
<br />B.REFER TO SECTION 16100 ELECTRICAL SPECIAL CONDITIONS REGARDING REGULATIONS AND REQUIREMENTS
<br />AFFECTING ALL WORK DESCRIBED IN THIS SECTION.
<br />2. POWER SERVICE
<br />A.POWER SERVICE FOR THIS PROJECT SHALL BE PROVIDED FROM THE UTILITY CO. THE ELECTRICAL
<br />CONTRACTOR SHALL COORDINATE WITH TO INSURE THAT ALL WORK AND MATERIALS ARE IN CONFORMANCE
<br />WITH THE UTILITY CO'S REQUIREMENTS.
<br />3. NAMEPLATES
<br />A.ELECTRICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO, PANELBOARDS, DISCONNECTS TRANSFORMERS,
<br />CONTROLS, ETC., SHALL BE IDENTIFIED WITH THREE PLY LAMINATED PLASTIC. THE OUTSIDE LAMINATIONS
<br />SHALL BE BLACK. ENGRAVING SHALL EXTEND THROUGH THE FRONT LAMINATION SO THAT THE BLACK
<br />LETTERS APPEAR ON A WHITE BACKGROUND. NAMEPLATES SHALL BE PERMANENTLY ATTACHED WITH
<br />SCREWS.
<br />B.CIRCUIT DIRECTORY SHALL BE TYPEWRITTEN (HANDWRITTEN IS NOT ACCEPTABLE) AND SHALL IDENTIFY
<br />CIRCUIT AS TO TYPE AND LOCATION AS FOLLOWS:
<br />"LTG" - FOR LIGHTING CIRCUIT FOLLOWED BY AREA IN WHICH CIRCUIT APPEARS, I.E., "STOCKROOM", "CASH
<br />WRAP", ETC.
<br />"RECEPT" - FOR RECEPTACLE CIRCUIT FOLLOWED BY AREA IN WHICH RECEPTACLE APPEARS,
<br />"STOREFRONT", "CASH REGISTER", ETC.
<br />"MOTOR" - FOR MOTOR FOLLOWED BY THE EQUIPMENT IDENTIFICATION AND AREA IN WHICH MOTOR IS
<br />LOCATED, I.E. "EXH FAN TOILET", "AHU-ROOF", ETC.
<br />4. CONDUIT
<br />A.CONDUIT SHALL BE STANDARD STEEL, RIGID IMC OR EMT (THIN WALL). CONDUIT SHALL BE CONCEALED IN
<br />FINISHED AREAS. EXCEPT AS OTHERWISE APPROVED BY OWNER'S REPRESENTATIVE. INDOOR EMT
<br />CONNECTIONS SHALL BE SET SCREW TYPE FITTING WHERE ALLOWED BY LOCAL AUTHORITY HAVING
<br />JURISDICTION. EXTERIOR EMT CONNECTIONS SHALL BE COMPRESSION TYPE.
<br />B.MINIMUM SIZES OF CONDUIT SHALL BE 3/4" EXCEPT 1/2" FOR SWITCH LEGS. EMT SHALL BE GALVANIZED OR
<br />ELECTRO-GALVANIZED. EMT SHALL BE USED FOR FEEDERS AND BRANCH CIRCUITS RUN ABOVE SUSPENDED
<br />CEILINGS OR CONCEALED IN INTERIOR PARTITIONS. EMT SHALL NOT BE CONCEALED IN POURED CONCRETE
<br />FLOOR OR WALLS.
<br />C.USE HEAVY WALL CONDUIT OR PVC FOR UNDER SLAB INSTALLATIONS.
<br />D.THE USE OF NONMETALLIC-SHEATHED CABLE, TYPE NM, IS NOT ACCEPTABLE.
<br />1.THE USE OF METAL CLAD CABLES, TYPE MC, IS ACCEPTABLE WHERE APPROVED BY THE LOCAL AHJ.
<br />ALL BRANCH CIRCUIT HOME RUNS TO PANELBOARDS AND DEDICATED BRANCH CIRCUITS SHALL BE IN
<br />EMT.
<br />2.ALL METAL CLAD CABLES, SHALL BE PROVIDED WITH A GROUND WIRE.
<br />E.ALL OPENINGS IN FIRE AND SMOKE WALLS, PARTITIONS, FLOORS AND OTHER SIMILAR PENETRATIONS FOR
<br />ELECTRICAL CONDUITS, CABLE OR EQUIPMENT, WHETHER CUT OR IN PLACE, SHALL BE CLOSED WITH A UL
<br />APPROVED FIRE RESISTANT SILICONE FOAM SEALANT TO MAINTAIN THE FULL RATING AND INTEGRITY OF THE
<br />PARTITIONS, WALLS OR FLOOR.
<br />F.CONDUIT BENDS FOR POWER AND LIGHTING CIRCUITS SHALL NOT BE LESS THAN STANDARD RADIUS BENDS.
<br />CONDUIT BENDS FOR FEEDERS, TELEPHONE AND COMMUNICATION CIRCUITS SHALL NOT BE LESS THAN LONG
<br />RADIUS BENDS.
<br />G.O.Z. TYPE DX, TX, OR AX CONDUIT EXPANSION DEFLECTION FITTINGS ARE REQUIRED IN ALL CONDUIT RUNS
<br />WHERE MOVEMENT MAY BE ENCOUNTERED. ALL EMT COUPLINGS SHALL BE COMPRESSION TYPE.
<br />H.EXPOSED CONDUIT SHALL BE SECURELY SUPPORTED IN PLACE PER CODE BUT ON A MAXIMUM OF 10 FOOT
<br />INTERVALS, WITHIN THREE FEET OF EACH BEND, AT EVERY OUTLET OR JUNCTION BOX AND AT THE END OF
<br />EACH STRAIGHT RUN TERMINATING AT A BOX OR CABINET. CONDUIT SHALL NOT BE SUPPORTED FROM
<br />DUCTWORK OR PIPE WORK. CONDUITS SHALL BE RUN PARALLEL TO AND AT RIGHT ANGLES TO THE BUILDING
<br />LINES. GENERALLY, CONDUIT SHALL BE RUN IN CONTACT WITH STRUCTURAL PARTS OF THE BUILDING SO AS
<br />TO AVOID SUSPENDED LENGTHS OF CONDUIT. CONDUIT SHALL BE INSTALLED AS TO BE ACCESSIBLE FOR
<br />REPLACEMENT AND MAINTENANCE AND GENERALLY CONDUIT SHALL BE INSTALLED TO PERMIT DRAINAGE.
<br />5. WIRE AND CABLE
<br />A.ALL WIRE AND CABLE SHALL BE COPPER AND RUN IN CONDUIT. ALL WIRE AND CABLE FEEDERS AND BRANCH
<br />CIRCUITS SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE CURRENT EDITION OF THE C.E.C. AND
<br />SHALL MEET ALL ASTM SPECIFICATIONS. WIRE AND CABLE SHALL BE NEW, SHALL HAVE SIZE, GRADE OF
<br />INSULATION VOLTAGE AND MANUFACTURER'S NAME PERMANENTLY MARKED ON OUTER COVERING AT
<br />REGULAR INTERVAL AND SHALL BE DELIVERED IN COMPLETE COILS OR REELS WITH IDENTIFYING SIZE AND
<br />INSULATION TAGS.
<br />B.THE ELECTRICAL CONTRACTOR SHALL CALCULATE VOLTAGE DROP ON CONDUCTORS WITH LENGTHS
<br />GREATER THAN 75 FEET FROM THE PANELBOARD AND PROPERLY SIZE THE CONDUCTORS PER C.E.C.
<br />C.POWER CONDUCTORS: NO WIRE LESS THAN NO. 12 SHALL BE USED EXCEPT FOR CONTROL CIRCUITS OR
<br />LOW VOLTAGE WIRING. WIRE SIZES NO. 12 TO NO. 10 SHALL BE SOLID EXCEPT WHERE OTHERWISE
<br />INDICATED. WIRE SIZES NO. 8 AND LARGER SHALL BE STRANDED. ALL WIRE SIZES SHOWN ARE AMERICAN
<br />WIRE GAUGE SIZES. SIZES NO. 12 AWG THROUGH NO. 8 AWG SHALL BE "THHN." SIZE 4 AWG AND LARGER
<br />SHALL BE "THW."
<br />D.CONTINUITY: ALL WIRES SHALL BE CONTINUOUS FROM OUTLET TO OUTLET.
<br />E.ACCEPTABLE MANUFACTURERS: CABLE AND WIRE SHALL BE STANDARD TYPE AS MANUFACTURED BY
<br />GENERAL CABLE COMPANY, CAROL, ANACONDA, ROM OR ITT ROYAL.
<br />6. COLOR CODING
<br />A.A COLOR CODING SYSTEM AS LISTED BELOW SHALL BE FOLLOWED THROUGHOUT FOR FEEDERS AND
<br />BRANCH CIRCUITS AND USED AS A BASIS FOR BALANCING LOAD.
<br />--120/208V:PHASE A--BLACK, PHASE B--RED, PHASE C--BLUE, NEUTRAL--WHITE, GROUND--GREEN
<br />--277/480V:PHASE A--BROWN, PHASE B--ORANGE, PHASE C--YELLOW, NEUTRAL--GRAY, GROUND--GREEN
<br />7. BOXES AND FITTINGS
<br />A.ALL OUTLETS SHALL BE PROVIDED WITH GALVANIZED OR SHERARDIZED BOXES SUITABLE IN DESIGN TO THE
<br />SPACE THEY OCCUPY AND THE PURPOSE THEY SERVE. WALL MOUNTED OUTLET BOXES, EXCEPT FOR 2"
<br />PARTITIONS SHALL BE AT LEAST 1 1/2" DEEP AND/OR DEEPER IF REQUIRED BY THE DEVICE THEY HOLD OR
<br />THE CALIFORNIA ELECTRICAL CODE.
<br />B.ALL PULLBOXES SHALL BE MADE OF GALVANIZED STEEL, OF METAL GAUGE AND PHYSICAL SIZE AS REQUIRED
<br />BY THE C.E.C. FOR THE NUMBER AND SIZE OF RACEWAYS AND CONDUCTORS INVOLVED.
<br />C.FIXTURE OUTLET BOXES IN OR ON CEILINGS SHALL NOT BE LESS THAN 1-1/2" DEEP OR LESS THAN 4" SQUARE.
<br />ALL OUTLET BOXES INTENDED TO SUPPORT FIXTURES SHALL BE EQUIPPED WITH 3/8" FIXTURE STUDS
<br />FASTENED THROUGH THE BOTTOM OF THE BOX WITH FOUR BOLTS.
<br />8. CIRCUIT BREAKER PANELBOARDS
<br />A.PANELS SHALL BE DEAD FRONT, SAFETY TYPE, FURNISHED WITH BRANCH CIRCUIT PROTECTING DEVICES,
<br />EQUIPMENT GROUNDING BOX, MAIN BUS AND CABLE LUGS FACTORY ASSEMBLED, WITH ALL COMPONENTS IN
<br />PLACE, READY FOR INSTALLATION.
<br />B.CURRENT CARRYING CONTACT SURFACES SHALL BE SILVER OR TIN PLATED. THE CIRCUIT BREAKERS SHALL
<br />BE OF THE MOLDED CASE, PLUG-IN TYPE SUITABLE FOR VOLTAGE AND AMPERE RATINGS INDICATED ON
<br />DRAWINGS AND IN SCHEDULES AND SHALL HAVE A MINIMUM INTERRUPTING CAPACITY OF 22,000 AMPERES
<br />FOR 120/208V AND 25,000 AMPERES AT 277/480V.
<br />C.MAIN BUSES AND CONNECTORS SHALL BE HARD DRAWN COPPER OF 98% CONDUCTIVITY, WITH CURRENT
<br />CARRYING CAPACITY TO MAINTAIN ESTABLISHED RISE TESTS AS DEFINED IN UL STANDARD UL 67.
<br />D.CABINET SIZES ARE BASED UPON A 20" WIDE BY 6" DEEP PANEL UNLESS OTHERWISE NOTED. PANELBOARDS
<br />SHALL BE EQUIPPED WITH FLUSH TYPE LOCK AND CATCH. ALL LOCKS SHALL BE KEYED ALIKE, AND TWO KEYS
<br />ARE TO BE SUPPLIED WITH EACH LOCK.
<br />E.BREAKERS SERVING LIGHTING CIRCUITS SHALL BE RATED FOR SWITCH DUTY.
<br />F.BREAKERS SERVING COOLER, FREEZER AND HVAC EQUIPMENT SHALL BE HACR RATED.
<br />G.ALL LUGS SHALL BE OF THE SOLDERLESS TYPE AND RATED AT A MINIMUM OF 75 DEGREES.
<br />H.PROVIDE PANEL DIRECTORY, TYPED AND INSTALLED BEHIND CLEAR PLASTIC COVER ON INSIDE OF THE DOOR.
<br />I.PANELBOARDS TO BE BY SQUARE D, GENERAL ELECTRIC, SIEMENS OR EATON.
<br />9. TRANSFORMERS
<br />A.DRY-TYPE TRANSFORMERS (DOE 2016) SHALL BE OF THE ENCLOSED VENTILATED TYPE WITH KVA AND
<br />VOLTAGE RATING AS CALLED FOR ON THE DRAWINGS AND WITH 150° CLASS H INSULATION AND MINIMUM OF
<br />SIX STANDARD FULL CAPACITY TAPS. SOUND LEVEL SHALL BE LOW AND INSTALLATION SHALL INCLUDE
<br />KORFUND OR EQUAL VIBRATION DAMPENING MOUNTS AND FLEXIBLE STEEL CONDUIT FOR PRIMARY AND
<br />SECONDARY. (MOUNT TRANSFORMER ON VIBRATION ISOLATORS). LOCATE TRANSFORMER AS NOT TO CAUSE
<br />SERVICING OR CLEARANCE DIFFICULTIES OF VIOLATIONS WITH OTHER EQUIPMENT.
<br />B.COMPARABLE EQUIPMENT AS MANUFACTURED BY SQUARE D, GENERAL ELECTRIC, SIEMENS OR EATON.
<br />10. TOGGLE SWITCHES
<br />A.TOGGLE SWITCHES SHALL BE WHITE AND SHALL BE RATED 20 AMPERES 120/277 VOLT AC TYPE AS
<br />MANUFACTURED BY HUBBELL AND SHALL BE AS FOLLOWS:
<br />SINGLE POLE - 1221-W
<br />THREE WAY - 1223-W
<br />B.TOGGLE SWITCHES SHALL BE MOUNTED 4'-0" ABOVE FINISHED FLOOR TO TOP OF MOUNTING PLATE AND, AT
<br />DOORS, INSTALLED ADJACENT TO THE TRIM ON THE STRIKING SIDE OF THE DOOR, REGARDLESS OF THE
<br />LOCATION INDICATED ON THE DRAWINGS; THEREFORE, CHECK ALL DOOR SWINGS BEFORE INSTALLATION OF
<br />CONDUIT OUTLETS.
<br />C.COMPARABLE EQUIPMENT AS MANUFACTURED BY COOPER WIRING, SLATER, LEVITON, AND BRYANT WILL BE
<br />ACCEPTABLE.
<br />11. RECEPTACLES
<br />A.RECEPTACLES SHALL BE WHITE AS MANUFACTURED BY HUBBELL AND SHALL BE AS FOLLOWS:
<br />DUPLEX RECEPTACLE - 20A-125 VOLT 5362-W
<br />GFCI DUPLEX RECEPTACLE - 20A-125 VOLT GF5362-W
<br />B.RECEPTACLES SHALL BE MOUNTED 18" ABOVE THE FINISHED FLOOR TO BOTTOM OF BOX UNLESS
<br />OTHERWISE NOTED.
<br />C.COMPARABLE EQUIPMENT AS MANUFACTURED BY COOPER WIRING, SIERRA ELECTRIC CORPORATION,
<br />SLATER, BRYANT AND LEVITON WILL BE ACCEPTABLE.
<br />12. DEVICE PLATES
<br />A.DEVICE PLATES SHALL BE STAINLESS STEEL UNLESS OTHERWISE NOTED. COMPARABLE EQUIPMENT AS
<br />MANUFACTURED BY COOPER WIRING, SIERRA ELECTRIC CORPORATION, HARVEY HUBBLE INC., BRYANT AND
<br />LEVITON WILL BE ACCEPTABLE. PAINT MATCH ADJACENT FINISH COLOR.
<br />13. DISCONNECT SWITCHES
<br />A.FURNISH AND INSTALL DISCONNECT SWITCHES AS REQUIRED BY CODE. DISCONNECT SWITCHES SHALL BE
<br />NEMA HEAVY DUTY TYPE AND UNDERWRITERS LABORATORIES LISTED, MANUFACTURED BY SQUARE D,
<br />GENERAL ELECTRIC, EATON OR SIEMENS.
<br />14. FUSES
<br />A.PROVIDE CARTRIDGE FUSES RATED FOR 250 V AC AND 600 V AC AND LESS FOR USE AS SPECIFIED HEREIN.
<br />B.COORDINATE FUSE RATINGS WITH UTILIZATION EQUIPMENT NAMEPLATE LIMITATIONS OF MAXIMUM FUSE SIZE
<br />AND WITH SYSTEM SHORT-CIRCUIT CURRENT LEVELS.
<br />C.CARTRIDGE FUSE APPLICATIONS:
<br />1.FEEDERS, UP TO AND INCLUDING 600 AMPS: CLASS RK1, BUSSMANN LPN-RK-SP FOR 250 VOLTS,
<br />BUSSMANN LPS-RK-SP FOR 600 VOLTS .
<br />2.FEEDERS, FROM 601 AMPS TO 4,000 AMPS: CLASS RK1, BUSSMANN KRP-C FOR UP TO 600 VOLTS,
<br />BUSSMANN .
<br />D.BASIS OF DESIGN FOR FUSES SHALL BE BUSSMANN. ADDITIONAL ACCEPTABLE MANUFACTURERS FOR
<br />SPECIFIED FUSES SHALL BE LITTLEFUSE AND MERSEN
<br />1. GENERAL
<br />A.WINGSTOP'S GC TO COORDINATE ALL LOCAL FIRE ALARM REQUIREMENTS WITH LOCAL FIRE MARSHALL AND
<br />PROVIDE ALL DEVICES REQUIRED FOR A COMPLETE SYSTEM.
<br />B.WINGSTOP'S GC SHALL VERIFY MANUFACTURER AND MODEL OF LANDLORD'S EXISTING FIRE ALARM SYSTEM.
<br />C.WINGSTOP'S GC SHALL COORDINATE REQUIREMENTS WITH LANDLORD'S FIRE ALARM VENDOR.
<br />D.WINGSTOP'S GC SHALL VERIFY ALL FIRE ALARM DEVICES THAT ARE EXISTING TO REMAIN ARE IN PROPER
<br />WORKING CONDITION. REPLACE ANY FAULTY DEVICES AS REQUIRED FOR A COMPLETE AND OPERATIONAL
<br />SYSTEM.
<br />E.ALL FIRE ALARM WORK SHALL BE PERFORMED BY A LANDLORD APPROVED FIRE ALARM CONTRACTOR.
<br />F.WINGSTOP'S GC IS RESPONSIBLE FOR FIRE ALARM PERMIT. IT IS THE TENANTS CONTRACTOR'S
<br />RESPONSIBILITY TO OBTAIN ALL REQUIREMENTS PRIOR TO SUBMISSION FOR PERMIT.
<br />SECTION 16700
<br />FIRE ALARM SPECIAL CONDITIONS (WHERE REQUIRED)
<br />15. GROUNDING
<br />A.CONTRACTOR SHALL INSTALL GROUNDING PER C.E.C. ARTICLE 250 EQUIPMENT GROUNDING SHALL USE ONLY
<br />APPROVED GROUNDING CLAMPS AND CONNECTORS AS MANUFACTURED BY PENN-UNION, BURNDY, OR O-Z
<br />MFG. COMPANY.
<br />B.GROUNDING SHALL BE INSTALLED IN ACCORDANCE WITH THE C.E.C. ARTICLE 250 AND THE UTILITY COMPANY
<br />REGULATIONS. CONTRACTOR SHALL CONNECT THE GROUNDING ELECTRODE CONDUCTORS TO THE NEUTRAL
<br />BAR INSIDE THE MAIN PANEL.
<br />C.THE EQUIPMENT GROUNDING SYSTEM SHALL CONSIST OF A CONTINUOUS CONDUIT INSTALLATION AND A
<br />GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR. THIS GROUNDING CONDUCTOR SHALL BE
<br />INSTALLED IN EVERY CONDUIT OR RACEWAY WITH THE FEEDER OR BRANCH CIRCUIT CONDUCTORS. THIS
<br />GROUNDING SHALL BE EXTENDED FROM THE HOUSING OF EVERY ELECTRICAL LOAD, THROUGH PANELBOARD
<br />STATIC GROUNDING BUSSES, TO THE STATIC GROUNDING BUS IN THE MAIN PANEL. THE GROUNDING BUS
<br />SHALL BE BONDED TO THE GROUNDING NEUTRAL BAR INSIDE THE MAIN PANEL.
<br />16. LIGHTING FIXTURES
<br />A.ALL LIGHTING FIXTURES AND LAMPS SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR, UNLESS NOTED
<br />OTHERWISE, THIS CONTRACTOR SHALL INSTALL LIGHTING FIXTURES AND LAMPS AS INDICATED ON THE
<br />DRAWINGS AND AS SPECIFIED BELOW, COMPLETE WITH HANGERS, PLASTER FRAMES AND ALL OTHER
<br />NECESSARY ACCESSORIES.
<br />B.LED LUMINAIRES
<br />14.LED FIXTURES SHALL COMPLY WITH IES LM-79-08 APPROVED METHOD FOR MEASURING LUMEN MAINTENANCE OF
<br />LED LIGHT SOURCES, COMPLY WITH IES LM-80-08 APPROVED FOR ELECTRICAL AND PHOTOMETRIC MEASUREMENT
<br />OF SSL PRODUCT, COMPLY WITH IN-SITU TESTING FOR MORE RELIABLE RESULTS.
<br />15.LED'S SHALL BE RESTRICTED OF HAZARDOUS SUBSTANCES DIRECTIVE (ROHS) COMPLIANT.
<br />16.LED ARRAYS SHALL BE SEALED, HIGH PERFORMANCE, LONG LIFE TYPE; MINIMUM 70% RATED OUTPUT AT 50,000
<br />HOURS.
<br />17.LUMINAIRES SHALL BE FULLY ACCESSIBLE FROM BELOW CEILING PLANE FOR CHANGING DRIVERS, POWER
<br />SUPPLIES AND ARRAYS.
<br />18.DRIVERS SHALL BE SOLID STATE AND ACCEPT 120 THROUGH 277 VAC AT 60 HZ INPUT.
<br />19.THE LED LIGHT SOURCE SHALL BE FULLY DIMMABLE WITH USE OF COMPATIBLE DIMMERS SWITCH DESIGNATED
<br />FOR LOW VOLTAGE LOADS.
<br />20.LED COLOR TEMPERATURES: SHALL BE AS NOTED ON DRAWING.
<br />21.LUMINAIRES SHALL HAVE INTERNAL THERMAL PROTECTION.
<br />22.INDOOR LUMINAIRES SHALL HAVE A MINIMUM CRI OF 85.
<br />C.LED POWER SUPPLIES AND DRIVERS
<br />1.SHALL HAVE A POWER FACTOR: 0.90 OR HIGHER.
<br />D.CONTROLLER AND CONTROL SYSTEMS
<br />1.THE CONTRACTOR SHALL ENSURE THAT EXTERNAL CONTROL EQUIPMENT IS COMPATIBLE WITH LED CONTROL
<br />REQUIREMENTS.
<br />2.PROVIDE CONNECTOR TYPES AND WIRING AS APPROPRIATE FOR UN-INTERRUPTED COMMUNICATION BETWEEN
<br />DEVICES, CONSIDERING DISTANCE MAXIMUMS, FIELD OBSTRUCTIONS, AND ACCESSIBILITY.
<br />3.ENSURE THAT CONNECTION POINTS ARE OPTICALLY ISOLATED FOR SYSTEM NOISE REDUCTION. FOR CONTROL
<br />COMPONENTS THAT ARE PART OF THE OVERALL AREA CONTROL SYSTEM. SEE DIMMING CONTROLS
<br />SPECIFICATIONS. COMPATIBILITY: CERTIFIED BY MANUFACTURER FOR USE WITH INDIVIDUALLY SPECIFIED
<br />LUMINAIRE AND INDIVIDUALLY SPECIFIED POWER SUPPLIES AND/OR DRIVERS.
<br />E.THIS CONTRACTOR SHALL VERIFY THE FINAL CEILING AND FINISH SCHEDULES TO ENSURE THE PROPER
<br />INSTALLATION AND MOUNTING OF FIXTURES AND SHALL COORDINATE BEFORE MAKING SUBMITTALS.
<br />17. LIGHTING CONTROLS
<br />A.TIME SWITCHES SHALL BE 24 HOUR, 7 DAY, DAY SKIPPER 365 DAYS AND HOLIDAYS TYPE EQUAL TO
<br />INTERMATIC ET2825C TIME SWITCH. CONTACTOR SHALL BE SQUARE D LXG-xx IN NEMA 1 ENGLOSURE.
<br />B.PANEL #GR1408LTENC-xMNE1-GR1408-DTCMOD WITH 8 RELAYS AND BUILT-IN TIME CLOCK AND AS
<br />MANUFACTURED BY LC&D.
<br />18.TELEPHONE SERVICE
<br />A.THIS CONTRACTOR SHALL INSTALL A TELEPHONE SERVICE CONDUIT AS SHOWN ON THE DRAWINGS AND
<br />FURNISH AND INSTALL (1) 3' x 4' x 3/4" PLYWOOD PANEL MOUNTED ON THE WALL AT LOCATION SHOWN ON
<br />PLANS.
<br />18. SURFACE METAL RACEWAY
<br />A.SURFACE METAL RACEWAY SHALL BE TWO PIECE #2100 AS MANUFACTURED BY WIREMOLD. ALL NECESSARY
<br />ACCESSORIES REQUIRED TO FIT THE CONFIGURATION SHOWN SHALL BE PROVIDED. RECEPTACLES SHALL BE
<br />120 VAC, 23 APMS, CATALOG NUMBER #2127GT.
<br />DATE
<br />FOR PERMIT & BID 01-25-22
<br />SEAL:
<br />PROJECT LOCATION:
<br />SHEET NUMBER:
<br />REVISION:DATE:
<br />CHECKED BY:
<br />ISSUE:
<br />DRAWN BY:
<br />PROJECT NO.:
<br />DATE:
<br />PROJECT INFORMATION:
<br />CLIENT:
<br />CONSULTANT:
<br />THESE DRAWINGS, IDEAS, SPECIFICATIONS AND
<br />DESIGNS ARE EXCLUSIVE PROPERTY OF WINGSTOP
<br />RESTAURANTS, INC. NO PART OF THESE DRAWINGS
<br />MAY BE COPIED, REPRODUCED, OR OTHER
<br />STRUCTURES BUILT FROM SUCH WITHOUT THE
<br />WRITTEN CONSENT OF WINGSTOP RESTAURANTS, INC.
<br />COPYRIGHT R 2022
<br />WINGSTOP RESTAURANTS, INC.
<br />ALL RIGHTS RESERVED
<br />15505 WRIGHT BROTHERS DRIVE
<br />ADDISON, TX 75001
<br />TELEPHONE: (972) 686-6500
<br />FAX: (972) 686-6502
<br />DISCLAIMER:
<br />STOCKTON, CA
<br />2021-0486STORE NUMBER: GL#Z060GILL GROVE1687 N CALIFORNIA STREET SUITE #TBDSTOCKTON, CA 95204JJV
<br />DRC
<br />1/20/22 796 Merus CourtSt. Louis, MO 63026T 636.349.1600F 636.349.1730
|