BUILDING CODES AND STANDARDS USED FOR DESIGN <br />1.2019 CALIFORNIA BUILDING CODE <br />OCCUPANCY CATEGORY: II <br />DESIGN LOADS <br />1.DESIGN LOADS <br />ROOF LIVE LOAD:20 psf <br />ROOF DEAD LOAD:15 psf <br />2.WIND LOAD DESIGN CRITERIA <br />WIND IMPORTANCE FACTOR, I:1.0 <br />BASIC WIND SPEED:93 MPH (3 SEC GUST) <br />WIND EXPOSURE CATEGORY:B <br />GCpi:+/-0.18 <br />3.SEISMIC LOAD DESIGN CRITERIA <br />SEISMIC IMPORTANCE FACTOR, I:1.0 <br />SITE CLASS:D <br />SPECTRAL RESPONSE ACCELERATION:Ss=0.719g,S1=0.282g <br />Sds=0.587g, Sd1=0.383g <br />SEISMIC DESIGN CATEGORY:D <br />EXISTING CONSTRUCTION NOTES <br />1.ALL DIMENSIONS AND ELEVATIONS TO EXISTING CONSTRUCTION ARE FOR <br />REFERENCE ONLY. FIELD VERIFY DIMENSIONS AND ELEVATIONS PRIOR TO <br />PREPARING SHOP DRAWINGS, FABRICATING MEMBERS (STRUCTURAL ITEMS), AND <br />INSTALLATION. <br />2.ALL HOLES THROUGH EXISTING CONSTRUCTION SHALL BE CORE-DRILLED OR <br />SAWCUT. DO NOT CUT ANY REINFORCING STEEL WHILE DRILLING INTO EXISTING <br />CONCRETE. DO NOT TORCH CUT. <br />3.NOTIFY STRUCTURAL ENGINEER IMMEDIATELY OF ANY DISCREPANCIES BETWEEN <br />EXISTING CONDITIONS AND STRUCTURAL DRAWINGS. <br />4.FOR ALL EXISTING CONSTRUCTION: DUE TO LIMITED OBSERVATION, OR NOT BEING <br />ABLE TO VISIT THE EXISTING BUILDING DURING THE PREPARATION OF THESE <br />DOCUMENTS, CASE ENGINEERING HAS ASSUMED THE EXISTING STRUCTURE IS IN <br />LIKE-NEW CONDITION WITH NO CORROSION, DETERIORATION, OR DAMAGE, AND <br />WAS CONSTRUCTED PER ANY ORIGINAL CONSTRUCTION DOCUMENTS PROVIDED <br />(IF ANY EXIST). CONTRACTOR SHALL VERIFY THESE ASSUMPTIONS TO THE BEST <br />OF THEIR ABILITY AND NOTIFY THE ENGINEER OF ANY CONCERNS, ISSUES, OR <br />DISCREPANCIES. <br />5.CONTRACTOR TO VERIFY TOP OF ROOF SLOPE IS AT LEAST ¼" PER FOOT AFTER <br />PLACEMENT OF ANY NEW LOADS APPLIED TO ROOF OR HUNG FROM ROOF <br />FRAMING. LOADS FROM NEW OR REPLACED ITEMS MAY INCLUDE, BUT ARE NOT <br />LIMITED TO, ROOF TOP MECHANICAL UNITS (RTU'S) AND ASSOCIATED DUCTWORK, <br />HUNG HOODS, MAKE-UP AIR UNITS, CONDENSERS, COMPRESSORS, EXHAUST <br />FANS, HUNG TRANSFORMERS, ROOFTOP GENERATOR(S), RE-ROOF MATERIALS, <br />NEW CEILINGS, HUNG SIGNAGE, HUNG SPRINKLER PIPING, ETC. ALSO VERIFY THAT <br />ALL ROOF DRAINS INCLUDING INTERIOR PRIMARY AND SECONDARY EMERGENCY <br />OVERFLOW DRAINS AND ANY WALL SCUPPERS ARE CLEAR AND FREE-DRAINING. <br />REPORT RESULTS IN WRITING TO ARCHITECT AND STRUCTURAL ENGINEER AS <br />SOON AS PRACTICAL DURING THE CONSTRUCTION PROCESS. <br />GENERAL STRUCTURAL NOTES <br />1.THIS DRAWING SET IS TO BE VIEWED AS A WHOLE AND COORDINATED WITH <br />ARCHITECTURAL, MECHANICAL AND OTHER DISCIPLINES. ALL WORK PERTAINING <br />TO A SPECIFIC CONTRACTOR MAY OR MAY NOT BE SHOWN ON SPECIFIC DRAWING <br />SECTIONS. IT IS EACH SUBCONTRACTOR'S RESPONSIBILITY TO PREPARE HIS BID <br />FROM A COMPLETE SET OF PLANS. <br />2.THE CONTRACTOR SHALL FOLLOW WRITTEN DIMENSIONS ONLY. DO NOT SCALE <br />DRAWINGS. DIMENSIONS NOT SHOWN ON PLAN TO BE COORDINATED WITH <br />ARCHITECTURAL PLANS. <br />3.WHERE INFORMATION PROVIDED IN THESE STRUCTURAL DRAWINGS <br />CONTRADICTS INFORMATION PROVIDED IN PROJECT SPECIFICATIONS, THE <br />SPECIFICATIONS SHALL TAKE PRECEDENCE. <br />4.ALL DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE INTENDED TO BE <br />TYPICAL AND SHALL APPLY AT ANY SIMILAR SITUATION ELSEWHERE ON THE JOB, <br />EXCEPT WHERE A DIFFERENT DETAIL OR SECTION IS SHOWN. <br />5.THE STRUCTURE SHALL BE ADEQUATELY BRACED AND SHORED DURING <br />ERECTION AGAINST WIND AND ERECTION LOADS. STRUCTURAL MEMBERS ARE <br />DESIGNED FOR "IN-PLACE" LOADS ONLY. <br />6.THE GENERAL CONTRACTOR SHALL VERIFY ALL OPENING SIZES, PAD SIZES, AND <br />LOCATIONS WITH THE RESPECTIVE CONTRACTORS. <br />7.THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER IMMEDIATELY <br />OF ANY DISCREPANCIES BETWEEN CONSTRUCTION DOCUMENTS AND ACTUAL <br />FIELD CONDITIONS. <br />8.SEE ARCHITECTURAL PLANS FOR ADDITIONAL DETAILS AND INFORMATION. <br />9.WHERE GENERAL NOTES OR TYPICAL DETAILS CONTRADICT INFORMATION <br />PROVIDED IN BUILDING SECTIONS, THE BUILDING SECTIONS TAKE PRECEDENCE. <br />10.ALL REINFORCEMENT AND SUBFRAMING INDICATED ON PLAN SHALL BE INSTALLED <br />PRIOR TO PLACING EQUIPMENT. <br />11.EQUIPMENT WEIGHING LESS THAN 100LBS NOT SHOWN ON PLAN. SEE <br />MECHANICAL DRAWINGS. <br />12.WEIGHTS SHOWN ON DRAWING INCLUDE WEIGHTS OF UNIT, CURB, AND ALL <br />ACCESSORIES. DO NOT PLACE UNIT WHEN OPERATING WEIGHT EXCEEDS THAT <br />INDICATED. NOTIFY STRUCTURAL ENGINEER. <br />13.VERIFY LOCATIONS OF ALL MECHANICAL EQUIPMENT WITH MECHANICAL <br />DRAWINGS. <br />14.STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING DESIGNATIONS AND <br />GRADES: <br />-ANGLES, CHANNELS, PLATES, BARS AND RODS TO BE: <br />-ASTM A36 <br />-GRADE 36 <br />-Fy = 36ksi <br />17.FV = FIELD VERIFY <br />(E) = EXISTING <br />2x6 BLKG -TYP <br />8d NAILS @ 3" oc @ PERIMETER OF <br />OPENING (EXISTING PLYWOOD <br />DECK TO BLKG) <br />SIMPSON LUS26 HGR -TYP OF (8) <br />(E) WOOD TRUSS TOP CHORD <br />COLD-FORMED STEEL FRAMING NOTES <br />1.STEEL FOR COLD-FORMED SECTIONS, AND STEEL SHEET AND PLATE USED IN COLD- <br />FORMED STEEL CONSTRUCTION SHALL CONFORM TO SECTION A2.1 OF AISI STANDARD: <br />"NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL <br />STRUCTURAL MEMBERS", LATEST EDITION. <br />2.ALL 12, 14, AND 16 GAUGE MEMBERS SHALL MEET THE REQUIREMENTS OF ASTM A1003, <br />GRADE ST50H (MINIMUM YIELD OF 50,000 psi). ALL 18 AND 20 GAUGE MEMBERS SHALL <br />MEET THE REQUIREMENTS OF ASTM A1003 GRADE ST33H (MINIMUM YIELD OF 33,000 psi). <br />3.SCREWS FOR COLD-FORMED STEEL CONSTRUCTION SHALL BE ITW BUILDEX TEK <br />SCREWS (ICC ESR-1976) OR APPROVED EQUAL. <br />4.ALL SCREWS SHALL BE INSTALLED SO THAT HEADS ARE FLUSH WITH OUTSIDE <br />MATERIAL. DO NOT OVERDRIVE SCREWS. SCREWS WITH WING-TIPS ARE NOT <br />PERMITTED IN SHEAR WALLS OR DIAPHRAGMS. <br />5.SCREW FASTENERS MUST BE INSTALLED PERPENDICULAR, FULLY SEATED AND WITH A <br />MINIMUM (3) SCREW THREADS EXPOSED BACKSIDE OF CONNECTION (UNO). <br />6.SECTION PROPERTIES ARE ASSUMED TO BE IN ACCORDANCE WITH THE AMERICAN IRON <br />AND STEEL INSTITUTE ‘’NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD- <br />FORMED STEEL STRUCTURAL MEMBERS’’2012 EDITION WITH SUPPLEMENTS. THE <br />CONTRACTORS IS TO VERIFY THAT THE MATERIALS INSTALLED MEET OR EXCEED THESE <br />DESIGN VALUES. <br />7.MECHANICAL BRIDGING SHALL BE USED IN ALL CASES WHERE INDICATED. INSTALLATION <br />OF BRIDGING MUST BE COMPLETED BEFORE ANY LOADS ARE APPLIED TO THE SYSTEM. <br />ALL BRIDGING SHALL BE TERMINATED AT JAMBS, CORNER STUDS OR COLUMNS. <br />BRIDGING ENDS SHALL NOT HANG LOOSE. STUDS SHALL BE BRACED AGAINST <br />ROTATION. <br />8.ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENT TO <br />PERPENDICULAR MEMBERS. STUD ENDS MUST SEAT TIGHTLY INTO TRACKS IN ALL <br />BEARING APPLICATIONS. <br />9.NO SPLICES IN STUDS, JOISTS, HEADERS, OR OTHER LOAD CARRYING MEMBERS MAY BE <br />MADE WITHOUT PRIOR ENGINEERING REVIEW AND SPECIFIC DETAILS FOR ANY SUCH <br />REVISION TO THE ORIGINAL DESIGN. <br />10.ALL WELDING SHALL BE PERFORMED BY AWS WELDERS QUALIFIED FOR WELDING COLD- <br />FORMED STEEL CONFORMANCE WITH AWS D1.3 USING E60 ELECTRODES, UNLESS <br />OTHERWISE NOTED. STEEL REQUIRING WELDING SHALL BE 16ga MINIMUM. <br />11.ALL COLD-FORMED STUDS AND JOISTS SHALL BE INSTALLED PER MANUFACTURER'S <br />RECOMMENDATIONS REGARDING MINIMUM INSTALLATION STANDARDS FOR BEARING, <br />BRIDGING, AND BRACING. <br />12.BOTTOM TRACK TO MATCH STUD GAUGE WITH A MINIMUM 1-1/4" FLANGE UNLESS <br />OTHERWISE NOTED. <br />13.ALL EXTERIOR WALLS TO HAVE HORIZONTAL BRIDGING @ 4'-0" MAXIMUM. <br />BOX COLUMN <br />PER PLAN <br />PROVIDE 362T200-54 TRACK <br />SECTION w/ SNIPPED ENDS TO <br />BLOCK COLUMNS ATTACH TO (E) <br />WALL STUDS AND TOP OF BOX <br />COLUMN w/ (2) #10 SCREWS <br />(E) BOTTOM <br />TRACK <br />#10 SCREWS <br />(E) SLAB <br />A <br />A <br />BEAM PER <br />PLAN <br />A-A <br />(E) PLYWOOD DECK <br />BOX BEAM PER <br />PLAN <br />BOX COLUMN <br />PER PLAN <br />SIMPSON SSC CLIP <br />T&B & SIDES <br />SIMPSON SSC CLIP <br />T&B & SIDE <br />TYP <br />48"oc <br />1/4" TITEN SCREW ANCHOR (LARR 25741)WALL BOTTOM TRACK <br />PROVIDE (1) 1/4" TITEN SCREW <br />ANCHOR @ BOX COL (LARR 25741) <br />BOX COL PER PLAN. ATTACH TO <br />TRACK w/ (2) #10 TEK SCREWS EA <br />SIDE MIN (LARR 25915) <br />16ga TRACK <br />#10 SCREWS @ <br />12"oc -TYP <br />STUD SIZE <br />PER PLAN <br />16ga TRACK <br />BOX BEAM/BOX COLUMN BACK-TO-BACK BEAM <br />HGR ROD BY OTHERS <br />DBL NUT & PL WASHER <br />PEEN THREADS AFTER <br />INSTALL <br />#10 TEK SCREWS <br />@ 12"oc <br />STUD SIZE PER <br />PLAN <br />SIMPSON FC62-5/97 <br />CLIP EA SIDE OF <br />HOOD BM TO <br />SUPPORT BM <br />BEYOND <br />600T100-54 T&B <br />SINGLE ROW <br />OF HANGERS <br />DOUBLE ROW <br />OF HANGERS <br />CLR - TYP <br />1" MAX <br />CLR <br />1" MAX <br />800T100-54 T&B <br />RTU PER MECH <br />CURB PER MECH <br />SIMPSON FCB43.5 CLIP <br />BEAM PER PLAN ALIGN w/ RTU CURB <br />BOX COL PER PLAN <br />BACK-TO-BACK <br />BEAM PER PLAN <br />(6) #10 SELF TAPPING SCREWS <br />PER SIDE MIN RTU TO CURB <br />(E) TRUSS <br />(6) #10 SELF TAPPING SCREWS PER <br />SIDE MIN CURB TO JOIST <br />MIN1" CLRA <br />A3" MINRTU PER MECH <br />CURB PER MECH <br />STUB BOX COL PER PLAN <br />SIMPSON FCB43.5 CLIP <br />BEAM PER PLAN -ALIGN <br />w/ RTU CURB <br />(6) #12 SCREWS -TYP <br />16ga TRACK SECTION <br />COL CAP -TYP <br />16ga TRACK SECTION -TYP MIN1" CLRSIMPSON DTC DEFLECTION <br />CLIP (2) PER STUB COL <br />A-AMIN3"ATTCH PER BOX <br />COL DETAIL <br />DRAWN BY: <br />SHEET NUMBER / TITLE: <br />PROJECT LOCATION: <br />CHECKED BY: <br />PROJECT INFO: <br />REVISION:DATE: <br />ISSUE:DATE: <br />SEAL:WINGPROJECT INFORMATION: <br />DISCLAIMER: <br />CONSULTANT: <br />THESE DRAWINGS, IDEAS, SPECIFICATIONS AND DESIGNS ARE <br />EXCLUSIVE PROPERTY OF WINGSTOP RESTAURANTS, INC. NO <br />PART OF THESE DRAWINGS MAY BE COPIED, REPRODUCED, OR <br />OTHER STRUCTURES BUILT FROM SUCH WITHOUT THE <br />WRITTEN CONSENT OF WINGSTOP RESTAURANTS, INC. <br />COPYRIGHT R 2018 <br />WINGSTOP RESTAURANTS, INC. <br />ALL RIGHTS RESERVED <br />STOPCLIENT: <br />DLP <br />KN <br />WIL-CA-01-22 <br />DATE <br />FOR PERMIT & BID 01-25-22 <br />STOCKTON, CASTORE NUMBER: GL#Z060GILL GROVE1687 N CALIFORNIA STREET SUITE #TBDSTOCKTON, CA 952041/21/22 <br />15505 WRIGHT BROTHERS DRIVE <br />ADDISON, TX 75001 <br />TELEPHONE: (972) 686-6500 <br />FAX: (972) 686-6502 <br />S1 <br />GENERAL NOTES & <br />DETAILS <br />N.T.S.S1 <br />E 2x6 BLOCKING - ROOF OPENING <br />N.T.S.S1 <br />B BOX COLUMN DETAIL <br />N.T.S.S1 <br />C TYP BOX COL/TRACK ANCHORAGE TO SLAB DETAIL <br />N.T.S.S1 <br />F TYP BUILT UP MEMBER CONSTRUCTION DETAIL <br />N.T.S.S1 <br />D HANGER ROD AT HOOD DETAIL <br />N.T.S.S1 <br />A FRAMING SECTION <br />2/2/22