Laserfiche WebLink
SAN J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> MID VALLEY AG SERVICES INC 1 16401 E HWY 26 , LINDEN November 14, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 601 CFR 112.7 Failure of Plan to fulfill basic requirements including a cross-referencing section. <br /> OBSERVATION: The Spill Prevention, Control, and Countermeasure(SPCC)Plan reviewed at the time of <br /> inspection,dated 3/21/2018, did not follow the order or requirements of 40 CFR Part 112.7. Section 2.5 Discharge <br /> Controls, 2.8 Emergency Contact List, and 13.3 Drainage of Storm Water From Secondary Containment doesn't <br /> follow the required SPCC rule sequence. The sections incorrectly reference other information in the plan (incorrect <br /> location referenced). <br /> REGULATION GUIDANCE: If you are the owner or operator of a facility subject to this part you must prepare a Plan <br /> in accordance with good engineering practices.The Plan must have the full approval of management at a level of <br /> authority to commit the necessary resources to fully implement the Plan.You must prepare the Plan in writing. If you <br /> do not follow the sequence specified in this section for the Plan, you must prepare an equivalent Plan acceptable to <br /> the Regional Administrator that meets all of the applicable requirements listed in this part, and you must supplement <br /> it with a section cross-referencing the location of requirements listed in this part and the equivalent requirements in <br /> the other prevention plan. If the Plan calls for additional facilities or procedures, methods, or equipment not yet fully <br /> operational, you must discuss these items in separate paragraphs and must explain separately the details of <br /> installation and operational start-up. <br /> CORRECTIVE ACTION: Ensure that your SPCC Plan follows the required SPCC rule sequence and/or includes <br /> adequate cross-reference. Provide proof of correction to the EHD. <br /> This is a minor violation. <br /> FA0009357 PR0528828 SCO01 11/14/2022 <br /> EHD 28-01 Rev.12/06/2021 Page 7 of 10 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />