Laserfiche WebLink
Program Element: 2303 - UST/PIPING INSTALLATION <br />Telephone: (559) 444-1730 Requestor: JAMES OTTO, LC SERVICES <br />Inspection Type: 298 - UST RETROFIT REPAIR INSPECTION <br />Address: 710 N JACK TONE RD , RIPON 95366 <br />Date: 09/22/2022Name of Facility: GRAPPA MARKET SHELL <br />Underground Storage Tank Program Service Request Inspection Report <br />Request #: SR0084854 <br />Environmental Health Department <br />Onsite Service Technician: Michael Lemon ICC Service Tech/Installer Exp. Date: 11/23/2022 <br />Manufacturer training: Xerxes, 06/14/24; NOV, 07/02/23 <br />OVERALL INSPECTION NOTES AND COMMENTS <br />NOTES <br />On site for primary piping soap test of all piping and penetrations (product, vapor recovery, and vent): <br />- One-hour pressure test at 110% or 40 psi <br />- Primary tank test <br />- Primary piping testing and primary tank passed. <br />Note: <br />***Additional inspection needed. See the approval letter for more information. Please give a 48 hours notification prior to <br />inspection. <br />The person in charge is responsible for ensuring that the above mentioned facility is in compliance with all applicable sections of the California Health and <br />Safety Code. If a reinspection is required, fees will be assessed at the current hourly rate. <br />Received by: Name and Title: <br />EH Specialist:Phone:(209) 616-3045 <br />Emailed to James Otto, Contractor <br />KRISTINA SAETERN <br />Page 1 of 1EHD 23-01 Rev. 07/05/2022 Underground Storage Tank Program Service Request Inspection Report <br /> SR0084854 SC298 09/22/2022