�� <br /> Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> g. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer 111 Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used:moon rester <br /> Sump/IJDC ID UDC 516 uoc 7/8 <br /> E) Sump Manufacturer Bravo Bravo <br /> Sump Depth (inches) 12" 12" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 4" 4" <br /> (inches) <br /> Test Start Time 9:58 am 9:58 am <br /> Initial Reading 1.0488 1.0446 <br /> Test End Time 10:14 am -10:14 am <br /> Final Reading 1.0486 1.0445 <br /> Change in Reading 0.0002 0.0001 <br /> Pass/Fail Criteria 0.002 0.002 <br /> Tightness Test Results CI Pass ❑ Fail 0 Pass El Fail ❑ Pass Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID <br /> i Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ElFail ElPass ElFail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. Page 3 o <br />