Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Farre <br /> 8. SUMPIUDC TEST <br /> Test Method Developed by ❑ Manufacturer 0 Industry Standard ❑ Professional Engineer <br /> Test Type LJ Pressure U Vacuum 0 Hydrostatic <br /> Test Equipment Used: lake test <br /> SumpfUDC ID 1/2 3/4 5/6 7/8 <br /> Sump Manufacturer unknown unknown unknown unknown <br /> Sump Depth (inches) 30 30 30 30 <br /> Sump Bottom to Top of 11 11 11 11 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:43 10:43 10:43 10:43 <br /> Initial Reading 21 in 21 in 21 in 21 in <br /> Test End Time 11:43 11:43 11:43 11:43 <br /> Final Reading 21 in 21 in 21 in 21 in <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria .125in .125in .125in .125in <br /> Tightness Test Results 0 Pass ❑ Fail 0 Pass ❑ Fail PI Pass ❑ Fail RI Pass ❑ Fail <br /> SumpfUDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> lritlal Reading <br /> Test End Time <br /> Final Reading <br /> Change in beading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fall ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attacher!. <br /> All tests marked `'Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />