Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2358589 Date: 2/21/2023 <br /> Site Name/ID. 7 ELEVEN 35355/35355 <br /> Address: 3202 W HAMMER LANE(N-136) <br /> City: STOCKTON State: CA Zip: 95209 <br /> Tank ID T1: Regular T2: Premium T3: Diesel <br /> Product RUL PUL Diesel <br /> Product Line 1 1 1 <br /> Tested From 8 8 8 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model FE Petro MLD FE Petro MLD Vaporless LD-2000 <br /> Serial No. UNREADABLE 02070690 05071049 <br /> Pump Operating Pressure(psi) 28.00 29.00 29.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 28.00 29.00 29.00 <br /> NIA for Electronic Lo's <br /> Resiliency(ml) 175.00 150.00 205.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 12 12 17 <br /> NIA for Electronic Lo's <br /> Opening Time(sec) 7 7 4 <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus S�/aldivar Certification#: 115237 <br /> Technician Signature: /-1 1�� Expire Date: 11/7/2024 <br /> Environmental Compliance for Petroleum Systems <br /> ©2023 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />