Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for LODI FOOD & LIQUOR* as of January 10 , 2023 . <br /> Open violations from November 29, 2022 inspection <br /> Violation #301 - Failure to operate UST system to prevent unauthorized releases including leaks , spills and <br /> overfills . <br /> OBSERVATION The fuel filters under the dispensers are not located to allow drips and leaks to drain back into the <br /> UDC . <br /> REGULATION GUIDANCE: The underground storage tank system shall be operated to prevent unauthorized <br /> releases . <br /> CORRECTIVE ACTION : Immediately provide approved secondary containment for the filters under permit and <br /> inspection by the EHD . <br /> ❑ This violation was corrected ❑ This violation will be corrected by (date) . <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> Page 2 of 2 <br />