Laserfiche WebLink
r- - <br />EXHAUST DUCT: <br />Duct Size 14" <br />Square feet of duct area 1 <br />Number of ducts 1 <br />Type of Metal welded steel exh . duct <br />Exhaust duct velocity 613 <br />(Recommended 1800 FPM) <br />In. <br />GREASE FILTERS or EXTRACTORS: <br />(1 outlet per 12 feet or fraction thereof) <br />Gauge 16 gauge <br />FPM (CFM divided by sq. ft. of duct) <br />Manufacturer FTL listed per UL 705 Model <br />Type (with handles) aluminum mesh filter <br />Rating: CFM at sp (static pressure) <br />Dimensions: 12 inches x 12 inches <br />Functional surface area per filter sq. ft. <br />Number of filters to be used: 1 <br />Total filter area sq. ft. <br />Number of spacers size of spacers: in. x in. <br />Minimum distance between lowest edge of grease filters and cooking surface: in.. <br />STATIC PRESSURE: <br />Filters <br />Entrance loss <br />Duct Length <br />Elbows <br />Loss to outside Atmosphere <br />EXHAUST FAN/BLOWER:. <br />0.25" <br />sp <br />+0.25" <br />sp <br />+ 0.25" <br />sp <br />+ <br />sp <br />+ <br />sp <br />= 0. 75" <br />Total sp <br />Manufacturer capt,iveaire Model No. DU33HFA <br />Exhaust 650 CFM at 0.25" sp. <br />Blower RPM Horsepower <br />MAKE-UP AIR: <br />Fan Manufacturer (make-up air provided by RTU -1 & RTU -2) <br />Model Number <br />CFM at sp <br />Duct size Square feet of duct. area <br />Number of ducts Duct velocity <br />Type of opening Opening size <br />Number of openings CFM per opening, <br />Electrical interlocking switch with exhaust fan <br />EHD 1&01 19 PLAN CHECK GUIDE <br />811114 <br />