SAN JOAQUIN <br />CCUNT <br />Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: —Fe: <br />ARCO CHEROKEE GAS & MART <br />900 S CHEROKEE LN, LODI <br />ptember 06, 2023 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />203 <br />CCR 2712(b)(1-2) Failure to maintain monitoring records for 36 months and maintenance records for 60 months. <br />OBSERVATION: Monitoring records for the last three years were not found on site. The 09/22/2022 monitoring <br />system certification and spill container test results were not found on site. <br />REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records <br />include: (1) date and time of all monitoring or sampling; (2) monitoring equipment calibration and maintenance <br />records; (3) results of any visual observations; (4) results of sample analysis performed a lab or in the field; (5) logs <br />of all readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6) results of <br />inventory readings and reconciliations. <br />CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the <br />last three years on site. <br />This is a repeat violation, Class ll. <br />205 <br />CCR 2712(i) Failure to submit and have current UST Monitoring Plan readily accessible at the facility. <br />OBSERVATION: An approved copy of the monitoring plans were not available for inspection. <br />REGULATION GUIDANCE: A copy of these plans shall be accessible on site at all times. <br />CORRECTIVE ACTION: Immediately locate and retain an updated copy on site. <br />This is a repeat violation, Class Il. <br />208 <br />CCR 2716(a -e) Failure to comply with the designated operator inspection requirements. <br />OBSERVATION: The designated operator failed to check and note the correct test dates for the secondary <br />containment testing on the designated operator inspection reports. The 7/21/23, 5/26/23, 12/9/22, and 9/15/22 <br />reports incorrectly noted the secondary containment test date as 10/4/21. The correct date for the secondary <br />containment test is 10/05/2021. <br />REGULATION GUIDANCE: During the inspection, the designated operator shall check that all required testing and <br />maintenance for the UST system have been completed and document the dates they were done. <br />CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br />the required information on the reports. <br />This is a repeat violation, Class Il. <br />Overall Inspection Comments: <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, by October 6, 2023. <br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br />of having them sign. Starting September 1, 2018, all in -office CERS help will be provided at EHD hourly rate <br />FA0000556 PR0231841 SCO01 09/06/2023 <br />EHD 23-01 Rev. 12/06/2021 Page 5 of 6 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />