Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2348239 Date: 3/9/2021 <br /> Site Name/ID. CHEVRON 307709/307709 <br /> Address: 10858 TRINITY PKWY <br /> City: STOCKTON State: CA Zip: 95219 <br /> Tank ID T1 -87 T-2-91 T-3-Diesel <br /> Product UNLEADED PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 11 11 11 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD <br /> Serial No. 303074 303057 303058 <br /> Pump Operating Pressure(psi) 52.00 50.00 41.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI <br /> NIA for Electronic Lo's <br /> Resiliency(ml) <br /> NIA for Electronic Lo's <br /> Metering PSI <br /> NIA for Electronic Lo's <br /> Opening Time(sec) <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: Expire Date: 1/27/2022 <br /> Environmental Compliance for Petroleum Systems <br /> ©2023 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />