Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-87-PS 2-Diesel-PS 3-91-PS <br /> Sump Manufacturer OPW OPW OPW <br /> Sump Depth (inches) 42" 40" 40" <br /> Sump Bottom to Top of 15" 12" 16" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 12:27 12:32 1:17 <br /> Initial Reading .001 .001 .001 <br /> Test End Time 12:57 1:02 1:47 <br /> Final Reading .001 .001 .001 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 <br /> Tightness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 1&2 UDC 3&4 UDC 5&6 UDC 7&8 <br /> Sump Manufacturer Total Cont Total Cont Total Cont Total Cont <br /> Sump Depth (inches) 28" 31" 32" 35" <br /> Sump Bottom to Top of 12" 15" 14" 14" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 12:37 12:42 1:22 1:27 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 1:07 1:12 1:52 1:57 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />