Laserfiche WebLink
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> HARNEY LANE AM PM 255 E Harney Ln, Lodi June 01, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 307 HSC 25290.1(c3), 25290.2(c3) Failure to keep water out of the secondary containment system (post-Jul 2003). <br /> OBSERVATION:Water was found in the vent sump. <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION: The service technician removed approximately 30oz of liquid from the vent sump and <br /> returned the sensor to its proper location. Immediately contact a properly licensed,trained, and certified contractor <br /> to address the water intrusion into the vent sump under permit and inspection of the EHD. <br /> This was corrected on site. <br /> This is a minor violation. <br /> 318 CCR 2635, 2637.1,2665, 2712 Failed to meet spill container requirements. <br /> OBSERVATION: The 91 and 87-1 spill containers failed when tested. <br /> REGULATION GUIDANCE:All spill containers shall have a minimum capacity of five gallons and be capable of <br /> containing a spill or overfill until it is detected or cleaned up. <br /> CORRECTIVE ACTION: Immediately contact a properly licensed,trained, and certified contractor to repair or <br /> replace the spill container under permit and inspection of the EHD. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> An inspection checklist was provided to the facility operator on the day of inspection. A complete report was <br /> finished on 06/08/2023 and replaces the initial checklist. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days of receiving the complete inspection report. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: June 08, 2023 Inspector: Inspector Phone: <br /> Printed Name and Title: PAUL NSO, EH Specialist (209)616-3049 <br /> Email report to:Arminder Lada, Environmental Contact. <br /> FA0021617 PR0537549 SCO01 06/01/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 5 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />