-24-hour hydrostatic test(or equivalent) on waste oil tank(tank 6)piping sump <br /> -Primary piping soap test and one hour pneumatic pressure test at 110% of operating pressure, or 40 psi, <br /> whichever is greater on waste oil tank(tank 6)primary pipe that was disconnected to newly installed <br /> penetration. <br /> Thanks, <br /> Karli Karns <br /> Job Supervisor at Nwestco <br /> A 2209 Zeus Court Bakersfield, CA 93308 <br /> P 661-631-3870 <br /> E karli.karns(a)nwestco.com <br /> W https://www.nwestco.com/ <br /> On Thu, Jan 19, 2023 at 2:39 PM Martinez, Genesis [EHD] <gmartinez�kj ov.org>wrote: <br /> Hi Karli, <br /> Thank you for the email. I have logged your appointment and will forward it to the area inspector. An inspector will <br /> only contact you if there is a conflict. <br /> Thank you, <br /> Ge*%,eyi y Mo4-f-i*x,&z I Sr. Office Assistant <br /> San Joaquin County Environmental Health Department <br /> 1868 E. Hazelton Ave. Stockton, CA 95205 <br /> M (209)468-021718 (209) 468-34331 D-� gmartinez@sigov.org <br /> EHD Website: https://www.sigov.org/department/envhealth/ <br /> 3 <br />