Laserfiche WebLink
Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Date: <br />February 14, 2023 <br /> Facility Address: <br /> 16 E HARDING WAY, STOCKTON <br /> Facility Name: <br /> A&A GAS & FOOD MART <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br /> 206 CCR 2712(i), 2634(e) Failure to submit and have a current UST Response Plan readily available on site. <br />OBSERVATION: An approved copy of the response plan was not available for inspection. <br />REGULATION GUIDANCE: A copy of this plan shall be accessible on site at all times. <br />CORRECTIVE ACTION: Immediately locate and retain a copy on site. <br />This is a repeat violation, Class II. <br /> 209 CCR 2715(c)(3), 2715(c)(4) Failure to maintain a copy of the "Facility Employee Training Certificate" on-site. <br />OBSERVATION: The Facility Employee Training Certificate dated 4/8/2022 and 1/14/2022 lists incorrect initial <br />training dates for Shakir Hussain and Kamran Malik. <br />REGULATION GUIDANCE: All site employees must be trained prior to taking responsibility as a facility employee if <br />after October 1, 2018, or within 30 days of hire if prior to October 1, 2018. The Facility Employee Training <br />Certificate shall contain accurate information for all employees trained. <br />CORRECTIVE ACTION: Update the Facility Employee Training Certificate to contain the accurate information and <br />submit a copy of the updated form to the EHD. <br />This is a repeat violation, Class II. <br /> 318 CCR 2635, 2637.1, 2665, 2712 Failed to meet spill container requirements. <br />OBSERVATION: The diesel spill container was not capable of containing five gallons for product delivery operations <br />at the time of the inspection. Approximately, three gallons of liquid was observed in the diesel spill container prior to <br />testing. <br />REGULATION GUIDANCE: All spill containers shall have a minimum capacity of five gallons. <br />CORRECTIVE ACTION: The liquid was removed and the spill container was tested. Ensure the spill containers are <br />empty. <br />This is a Class II violation. <br />Overall Inspection Comments: <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, by 3/16/2023. <br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br />of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br />($156). To schedule an appointment, please call (209) 468-3420. <br />FA0003610 PR0231136 SC001 02/14/2023 <br />EHD 23-01 Rev. 12/06/2021 Underground Storage Tank Program OIRPage 5 of 6 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD