S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> NASHIR MAIN ST INC. 3440 E MAIN ST, STOCKTON February 07, 2023 <br /> Single-Walled Non-Pressurized Piping <br /> 404 CCR 2643(e),2661(f) Failure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair(pre-1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 107 HSC 25292.2; CCR 2711(a)(11)Failure to submit and maintain complete and current financial responsibility <br /> documents. <br /> OBSERVATION: Current financial responsibility documents were not found on site. <br /> REGULATION GUIDANCE:A copy of current financial responsibility documents are required to be maintained on <br /> site. <br /> CORRECTIVE ACTION: Immediately obtain a copy of the facility's financial responsibility documents and maintain a <br /> copy on site. <br /> This is a repeat violation, Class ll. <br /> 208 CCR 2716(a-e) Failure to comply with the designated operator inspection requirements. <br /> OBSERVATION: The designated operator failed of check and note the correct test dates for the Secondary <br /> Containment Test on the designated operator inspection reports. On 11/4/2022 designated operator report, the <br /> designated operator incorrectly noted the Secondary Containment Report inspection date as 1/24/2020.The correct <br /> date for the Secondary Containment Test is 6/6/2022. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall check that all required testing and <br /> maintenance for the UST system have been completed and shall check all required items on the report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br /> the required information on the reports. <br /> This is a repeat violation, Class ll. <br /> 308 CCR 2632(c), 2634(d), 2636(f) Failure of the leak detection equipment to have an audible and visual alarm. <br /> OBSERVATION: The float and chain in the 1/2 UDC failed to stop the flow of product at the dispenser when tested. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: The service technician adjusted the float and chain and verified functionality. <br /> This was corrected on site. <br /> This is a repeat violation, Class ll. <br /> FA0006423 PR0231173 SCO01 02/07/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 4 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />