My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2023
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
E
>
EMBARCADERO
>
6649
>
2300 - Underground Storage Tank Program
>
PR0231098
>
COMPLIANCE INFO_2023
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
4/24/2023 9:26:09 AM
Creation date
1/30/2023 12:04:45 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2023
RECORD_ID
PR0231098
PE
2361
FACILITY_ID
FA0003830
FACILITY_NAME
VILLAGE WEST MARINA
STREET_NUMBER
6649
STREET_NAME
EMBARCADERO
STREET_TYPE
DR
City
STOCKTON
Zip
95219
APN
09815006
CURRENT_STATUS
01
SITE_LOCATION
6649 EMBARCADERO DR
P_LOCATION
01
P_DISTRICT
002
QC Status
Approved
Scanner
SJGOV\kblackwell
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
21
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 7. LINE LEAK DETECTOR TESTING <br /> ❑Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) <br /> Simulated release rate verified: (Check all that apply.) k <br /> Yes No <br /> x3 GPH 00.1 GPH❑0.2 GPH N <br /> Has the testing apparatus been properly calibrated? x ❑ ❑ <br /> For emergency generator tank systems, does the LLD create an audible and visual alarm ❑ ❑ x <br /> when a leak is detected? <br /> For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is x ❑ ❑ <br /> detected? <br /> For electronic LLDs, does the turbine automatically shut off when a release is detected? ❑ ❑ x <br /> For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring ❑ ❑ x <br /> system is disabled or disconnected? <br /> For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring ❑ ❑ x <br /> system malfunctions or fails a tightness test? <br /> For electronic LLDs, have all accessible wiring connections been visually inspected for ❑ ❑ x <br /> kinks and breaks? <br /> Were all items on the equipment manufacturer's maintenance checklist completed? x ❑ ❑ <br /> Were all LLDs confirmed operational within regulatory requirements? x ❑ <br /> LLD 1D LLD Model Lines Monitored Pass Fail <br /> T1:DIESEL VM199LD2000 DIESEL X ❑ <br /> T2: 91 VM199LD2000 91 X ❑ <br /> El <br /> ❑ ❑ <br /> ❑ ❑ <br /> O ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> Describe all answers marked "No"or"Fail"and proposed remedy in Section 9. <br /> List all monitoring equipment either replaced or repaired in Section 9 <br /> Page 4 of 6 <br />
The URL can be used to link to this page
Your browser does not support the video tag.