Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 7. LINE LEAK DETECTOR TESTING <br /> ❑Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) <br /> Simulated release rate verified: (Check all that apply.) Yes No NA <br /> x3 GPH 00.1 GPH❑0.2 GPH <br /> Has the testing apparatus been properly calibrated? x ❑ ❑ <br /> For emergency generator tank systems, does the LLD create an audible and visual alarm ❑ ❑ x <br /> when a leak is detected? <br /> For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is ❑ X <br /> detected? <br /> For electronic LLDs, does the turbine automatically shut off when a release is detected? X ❑ <br /> For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring X ❑ <br /> system is disabled or disconnected? <br /> For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring X D <br /> system malfunctions or fails a tightness test? <br /> For electronic LLDs, have all accessible wiring connections been visually inspected for X ❑ <br /> kinks and breaks? <br /> Were all items on the equipment manufacturer's maintenance checklist completed? x ❑ D <br /> Were all LLDs confirmed operational within regulatory requirements? x ❑ ❑ <br /> LLD ID LLD Model Lines Monitored Pass Fail <br /> Q1 VIR 8484 87 X ❑ <br /> Q2 VIR 8484 91 X ❑ <br /> ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> Describe all answers marked "No"or "Fail"and proposed remedy in Section 9. <br /> List al1 monitoring equipment either replaced or repaired in Section 9 <br /> Page 4 of 6 <br />