Laserfiche WebLink
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> H&S ENERGY PRODUCTS, LLC 3083 3775 N TRACY BLVD,TRACY February 28, 2023 <br /> Single-Walled Non-Pressurized Piping <br /> 404 CCR 2643(e),2661(f) Failure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair(pre-1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 306 HSC 25291(e)Failure to remove, analyze, and properly dispose of water in secondary containment(pre-Jul 2003). <br /> OBSERVATION: Liquid was observed in the diesel and 87 STP sumps. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: The service technician removed approximately 30oz of liquid from the diesel and 87 STP <br /> sumps. Ensure that all sumps and annular spaces are maintained free of liquid. <br /> This was corrected on site. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> Completed routine monitoring system certification, one violation was observed during the inspection and was <br /> corrected by the service Technician. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($156). To schedule an appointment, please call (209)468-3420. <br /> *No DO reports before 10/22 and 2020 monitoring system certification test results on site- New Owner from <br /> 11/2022. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: February 28, 2023 Inspector: Inspector Phone: <br /> Printed Name and Title: PAUL NSO, EH Specialist (209)616-3049 <br /> E mail report to: Christian Torres, Environmental Contact. <br /> FA0003715 PR0231418 SCO01 02/28/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 4 of 4 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />