Laserfiche WebLink
SAN J O A R N Environmental Health Department <br /> i ,�% �V <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> PLAZA LIQUOR#1 T800 S CHEROKEE LN, LODI March 20, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 208 CCR 2716(a-e) Failure to comply with the designated operator inspection requirements. <br /> OBSERVATION: The designated operator failed to check and note all required items on the visual inspection <br /> reports.The incorrect and missing information included the following from the inspection reports: <br /> -The DO report of 2/23/2023 did not include the DO signature and date. <br /> REGULATION GUIDANCE: During the visual inspection,the designated operator shall check that all required <br /> testing and maintenance for the UST system have been completed and shall check all required items on the report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing visual inspections at this facility are including <br /> all of the required information on the reports. <br /> This is a repeat violation, Class II. <br /> 306 HSC 25291(e)Failure to remove, analyze, and properly dispose of water in secondary containment(pre-Jul 2003). <br /> OBSERVATION: Liquid was observed in the 91 STP sump, 91 STP spill container and UDC 3/4. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: The service technician removed approximately one gallon of liquid from the 91 STP sump, <br /> 91 Spill Container and UDc 3/4 Ensure that all sumps and annular spaces are maintained free of liquid. <br /> This was corrected on site. <br /> This is a minor violation. <br /> 308 CCR 2632(c), 2634(d), 2636(f) Failure of the leak detection equipment to have an audible and visual alarm. <br /> OBSERVATION: The float and chain in the UDCs 3/4 failed to stop the flow of product at the dispenser when tested. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: The service technician adjusted the float and chain and verified functionality. <br /> This was corrected on site. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 04/19/2023 . <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> FA0003997 PR0231325 SCO01 03/20/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />