<br />Underground Storage Tank <br />Secondary Containment Testing Report Form <br />All tests marked “Fail” and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 3 of 5 <br />Test Method Developed by ☐ Manufacturer ☐ Industry Standard ☒ Professional Engineer <br />Test Type ☐ Pressure ☐ Vacuum ☒ Hydrostatic <br />Test Equipment Used: Caldwell Level Change Indicator <br /> <br />Sump/UDC ID 1-87-PS 2-91-PS 3-Diesel-PS <br />Sump Manufacturer Western FG Western FG Western FG <br />Sump Depth (inches) 40" 40" 40 1/2" <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />13" 16" 17" <br />Test Start Time 9:52 10:35 9:57 <br />Initial Reading .001 .001 .001 <br />Test End Time 10:22 11:05 10:27 <br />Final Reading .001 .001 .001 <br />Change in Reading 0 0 0 <br />Pass/Fail Criteria > .002 > .002 > .002 <br />Tightness Test Results ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☐ Pass ☐ Fail <br /> <br />Sump/UDC ID UDC 1&2 UDC 3&4 UDC 5&6 UDC 7&8 <br />Sump Manufacturer Bravo Bravo Bravo Bravo <br />Sump Depth (inches) 9" 9" 9" 9" <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />BP BP BP BP <br />Test Start Time 10:02 10:07 10:40 10:43 <br />Initial Reading .001 .001 .001 .001 <br />Test End Time 10:32 10:37 11:10 11:13 <br />Final Reading .001 .001 .001 .001 <br />Change in Reading 0 0 0 0 <br />Pass/Fail Criteria > .002 > .002 > .002 > .002 <br />Tightness Test Results ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail <br /> <br />Additional copies of this page may be attached. <br /> <br />8. SUMP/UDC TEST