Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ARCO STATION#826951 130 S WILSON WAY, STOCKTON January 25, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 306 HSC 25291(e) Failure to remove, analyze, and properly dispose of water in secondary containment(pre-Jul 2003). <br /> OBSERVATION: Liquid was observed inside the 3/4 UDC, 87 Master STP sump, 87 Slave STP sump, and 91 STP <br /> sump. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: The service technician removed liquid from the 3/4 UDC, 87 Master STP sump, 87 Slave <br /> STP sump, and 91 STP sump. Ensure that all sumps and annular spaces are maintained free of liquid. <br /> This was corrected on site. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> An inspection checklist was provided to the facility operator on the day of inspection. A complete report was <br /> finished on 3/16/2023 and replaces the initial checklist. <br /> - Paper work inspection was conducted on 3/16/2023 <br /> The partial inspection was conducted on 1/25/2023. <br /> -Witnessed start of spill container testing. <br /> -Witnessed partial monitoring system certification; testing of sensors for 87, 87, & 91 and sensors in 1-2, 3-4, <br /> 5-6, & 7-8 <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days of receiving the complete inspection report. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: March 16, 2023 Inspector: Inspector Phone: <br /> Printed Name and Title: KRISTINA SAETERN, EH Specialist (209)616-3045 <br /> Emailed to Barjinder Chana, Owner <br /> FA0003601 PR0231861 SCO01 01/25/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 5 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />